Pr.
Name
502
Stop mode selection at
N013
communication error
Operation frequency
779
during communication
N014
error

Available when the FR-A8ND or FR-A8NF is installed. Not available during operation via CC-Link IE TSN.

Available when the HMS network option is installed. Not available during operation via CC-Link IE TSN.
(N) Operation via communication and its settings
Initial
Setting
value
range
Inverter operation when a
communication error
0
Output shutoff
"E.OP1" indication
ALM signal output
Output to decelerate and stop
the motor
1
"E.OP1" indication after stop
ALM signal output after stop
Output to decelerate and stop
2
the motor
0
"E.OP1" indication after stop
Operation continues at the
3
frequency set in Pr.779.
Operation continues at the
4
frequency set in Pr.779.
"CF" warning indication
Deceleration stop according to
the setting of Pr.111.
11
"E.OP1" indication after stop
ALM signal output after stop
Deceleration stop according to
12
the setting of Pr.111.
"E.OP1" indication after stop
Set the frequency for the operation when a communication error
0 to 590 Hz
occurs.
9999
Operation continues at the same frequency before the
9999
communication error.
Description
Inverter operation after a
communication error is
occurs
Output stop status continues.
("E.OP1" indication)
Output stop status continues.
("E.OP1" indication)
Restart
Normal
Normal
Output stop status continues.
("E.OP1" indication)
Restart
PARAMETER
cleared
2
GROUP
N
15