GE AF-650 GP Programming Manual page 114

General purpose drive
Hide thumbs Also See for AF-650 GP:
Table of Contents

Advertisement

Parameter Descriptions
PB-27 Parameter Edit
Option:
Function:
Edit parameters via:
PROFIBUS.
The standard RS485 interface.
The keypad.
[0]
Disabled Disables editing via PROFIBUS.
[1]
Enabled Enables editing via PROFIBUS.
*
PB-28 Process Control
Option:
Function:
Process control (setting of control word, speed
reference, and process data) is possible via either
PROFIBUS or standard Network, but not both
simultaneously. Local control is always possible via
the keypad. Control via process control is possible
via either terminals or Network depending on the
settings in parameter O-50 Coasting Select to
parameter O-56 Preset Reference Select.
[0]
Disable
Disables process control via PROFIBUS master
class 1 and enables process control via standard
Network or PROFIBUS master class 2.
[1]
Enable
Enables process control via PROFIBUS master class
cyclic
1 and disables process control via standard
*
master
Network or PROFIBUS master class 2.
PB-44 Fault Message Counter
Range:
Function:
0
[0 -
This parameter displays the number of error
*
65535]
events stored in parameter PB-45 Fault Code and
parameter PB-47 Fault Number. The maximum
buffer capacity is eight error events. The buffer
and counter are set to 0 upon reset or power-up.
PB-45 Fault Code
Range:
Function:
0
[0 - 0] This buffer contains the alarm word for all alarms
*
and warnings that have occurred since last reset or
power-up. The maximum buffer capacity is eight
error events.
PB-47 Fault Number
Range:
Function:
0
[0 - 0] This buffer contains the alarm number (e.g. 2 for
*
live zero error, 4 for mains phase loss) for all alarms
and warnings that have occurred since last reset or
power-up. The maximum buffer capacity is eight
error events.
DET-618D
AF-650 GP™ Programming Guide
PB-52 Fault Situation Counter
Range:
0
[0 - 1000] This parameter displays the number of error
*
PB-53 Profibus Warning Word
Read only
Range:
0
[0 - 65535] This parameter shows PROFIBUS communication
*
Bit
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
Table 3.22 PROFIBUS Warning Word
PB-63 Actual Baud Rate
Option:
[0]
[1]
[2]
[3]
[4]
[6]
[7]
[8]
[9]
[10]
[11]
[255]
*
02/2016 All rights reserved.
Function:
events which have occurred since last reset of
power-up.
Function:
warnings. Refer to the AF-650 GP & AF-600 FP
PROFIBUS DP Operating Instructions, DET-624 for
further information.
Description
Connection with DP-master is not OK.
Not used.
NDL (Network data link layer) is not OK.
Clear data command received.
Actual value is not updated.
Baud rate search.
PROFIBUS ASIC is not transmitting.
Restore of PROFIBUS is not OK.
Frequency converter is tripped.
Internal CAN error.
Wrong configuration data from PLC.
Wrong ID sent by PLC.
Internal fault occurred.
Not configured.
Timeout active.
Warning 34, Fieldbus fault active.
Function:
This parameter shows the actual
PROFIBUS baud rate. The PROFIBUS
master automatically sets the baud
rate.
9,6 kbit/s
19,2 kbit/s
93,75 kbit/s
187,5 kbit/s
500 kbit/s
1500 kbit/s
3000 kbit/s
6000 kbit/s
12000 kbit/s
31,25 kbit/s
45,45 kbit/s
No baudrate found
3
3
113

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents