Function Code Descriptions; Basic Function - GE Fuji Electric AF-300ES Instructions Manual

1/2 - 350 horsepower
Table of Contents

Advertisement

LCD
GRAPHIC
Section 6: Function Code Descriptions
FUNCTION
DISPLAY
BASIC FUNCTIONS
LCD
GRAPHIC
FUNCTION
DISPLAY
00
FREQ COMND
01
OPR METHOD
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
SETTING
NOTE: * = Function can be changed while the Drive is operating.
SETTING
FREQUENCY COMMAND
Frequency reference can be supplied by
three different methods: Keypad
(digital), 0 to +10 VDC, 4 to 20 mA.
0:
Keypad operation (Digital setting with
/\ or \/ keys).
1:
0 to +10 VDC analog signal (terminal 12),
or a speed potentiometer connected to
terminal 11, 12 and 13.
2:
Sum of 0 to +10 VDC (terminal 12) and 4 to
20 mA (terminal C1).
NOTE : Drives 40HP & greater can use a 0
OPERATION METHOD
RUN, STOP, and RESET commands can be
supplied by two different methods: Keypad
(local) or terminal strip (remote).
0:
Keypad operation (RUN, STOP keys).
1:
Terminal strip operation (Keypad STOP key active).
2:
Terminal strip operation (Keypad STOP key inactive).
NOTE: Remote/local operation can be
NOTE: Contact between FWD or REV and CM must
DESCRIPTION
DESCRIPTION
to + 10 VDC analog signal input (ter-
minal V1) which is summed with the
0 to +10 VDC input.
toggled by pressing RESET and STOP
keys simultaneously when the
drive is in the STOP condition.
be open during power-up or "Er6" trip
will occur.
6-1
FACTORY
SETTING
FACTORY
SETTING
0
0

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents