Basic Installation and Operation Guide
Fn #
Group
F040
F041
F042
F043
F044
F045
F046
F047
Table 5.5.7: Current and Ground Protection Features Group
Fn #
Group
F048
F049
F050
F051
F052
F053
F054
F055
F056
F057
F058
F059
Table 5.5.8: Lockouts, Reset and Internal Protection Group
32 |
P a g e
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
5.5.7
Current and Ground Fault Protection Features
Function Description
Current Imbalance Trip
Current Imbalance Trip Delay
Over Current Trip
Over Current Trip Delay
Under Current Trip
Under Current Trip Delay
Ground Fault Trip
Ground Fault Trip Delay
5.5.8
Lockouts, Reset and Internal Protection Functions
Function Description
Coast Down (Back Spin)
Lockout Timer
Maximum Starts per Hour
Minimum Time Between
Starts
Internal Protection Settings
Auto Reset
on Selected Faults
Auto Reset Attempts
Restart Delay Time Value
Readout (for F028)
Coast Down Timer Value
for F048
Starts Per Hour Timer Value
for F049
Starts Per Hour
For F049
Time Value Between Starts
for F050
Thermal Capacity to Start
for F005
TE Series Digital Solid State Soft Starters 18 – 1250A
Adjustment / Display Range
0 = Disabled, or
5 - 30% imbalance
1 - 20 seconds
0 = Disabled, or
100 - 300% of motor FLA
1 - 20 seconds
0 = Disabled, or
10 - 90% of motor FLA
1 - 60 seconds
0 = Disabled, or
5 - 90% of CT ratio from Fn 74
1 - 60 seconds
Adjustment / Display Range
0 = Disabled, or 1 - 60 minutes
0 = Disabled, or 1 – 10 starts
0 = Disabled, or 1 - 60 minutes
1 – 127
See" F051 Definition Table"
Fault Preferences 1 – 12
See Table 5.6.7:
"Auto-Reset Selected Faults"
0 = Disabled, or 1-10 attempts
0-999 Minutes
1-3600 Seconds
1-3600 Seconds
1-10 Starts
1-3600 Seconds
0-100 % Thermal Capacity
Setting
Factory
Section
Increments
Setting
0
1%
Disabled
2
1 second
seconds
0
1%
Disabled
1 second
1 second
5.6.7
0
1%
Disabled
2
1 second
seconds
0
1%
Disabled
2
1 second
seconds
Setting
Factory
Section
Increments
Setting
0
1 minute
Disabled
0
1
5.6.8
Disabled
0
1 minute
Disabled
1
126
5.6.8.a
4,
1
Phase
Loss only
5.6.8.b
0
1
Disabled
1
0
1
0
1
0
5.6.8.c
1
0
1
0
1
0