LG SPLIT COMPACT DEDICATED OUTDOOR AIR SYSTEM (DOAS) INSTALLATION MANUAL Variable Refrigerant Flow Split Compact DOAS ARND***DCR4 Series (1,500 and 2,000 CFM)
2. Rotate the fan wheel(s) by hand to ensure parts are not in contact with one another and are causing friction / damage. Assemblies • Blower - One plenum-type fans (LG 3D Plug). All units are equipped with a plenum fan for supply air. • Coils - Evaporator Coil and Reheat Coil.
LG offers, free of charge, LG Air Conditioner Technical Solution (LATS) software—a total design solution for LG air conditioning systems. To reduce the risk of designing an improper applied system or one that will not operate correctly, LG requires that LATS software be used on all projects.
• Remove the smallest space from the system and serve it with a smaller mini-split system. Selecting Field-Supplied Copper Piping For DOAS Units LG prefers the use of hard drawn copper in pipe segments connecting a Dedicated Outdoor Air System (DOAS) product and a heat recovery outdoor unit.
REFRIGERANT PIPING SYSTEM INSTALLATION DOAS Layout Example / Selecting the Piping Size erant system rules, review the information in this entire piping section, see the LG Split Compact DOAS Engineering Manual, and follow the LATS diagram. Example: Triple-Frame Multi V 5 Heat Recovery System with Three (3) DOAS Units Connected Figure 11: DOAS Layout Example / Pipe Sizing.
PVC, aluminum vapor barrier, or alternatively placed in a weather-resistant enclosure such as a pipe rack with a top cover; and meet local codes. LG-provided Y-branches are shipped from the factory with pre-formed peel-and-stick foam insulation jackets, with a 1.84 lb./ft3 density, 1/2 inch thickness, and meet UL94 MF-1 flammability.
• Do not apply power to the units sections of the piping system, making the leak test inconclusive. Contact your LG Applied Rep or service technician for the procedure to if the power has been applied. • For multi-frame outdoor units, connect the nitrogen cylinder regulator to the gauge manifold, then connect the gauge manifold to the Schrader port on the service port of only one outdoor unit, preferably the Sub outdoor unit that is farthest away from the refrigerant piping system and connected indoor units / heat recovery units.
Do not open the outdoor unit service valves and release the factory refrigerant charge until the LG trained commissioner authorizes to do so. The system must be left in vacuum until the LG trained commissioner verifies the quality of the evacuation.
Page 45
DOAS Unit Address Settings LG DOAS can be connected up to a maximum of four (4) units on a Multi V 5 heat recovery outdoor unit system. If more than two (2) DOAS units are installed, the DOAS / heat recovery unit (integral part of the Split Compact DOAS) addresses must match. Factory set value is 0.