Interface For Compact Flash Card; Inline Bus - Bosch Rexroth IndraControl L45 Project Planning Manual

Hide thumbs Also See for Rexroth IndraControl L45:
Table of Contents

Advertisement

DOK-CONTRL-ICL45L65L85-PR01-EN-P
Rexroth IndraControl L45/L65/L85 Control
7.4.6

Interface for Compact Flash Card

Compact Flash card
7.5

Inline Bus

UL rating
Dropout time
Bounce time
Watchdog time (analog WD only)
Fig.7-28:
Characteristics of the ready contact
If it is in the release status, the ready contact is open. After powering up the
device, the contact is closed. The contact is opened again, if one of the states
listed below occurs:
The DC 24 V supply voltage falls below the permissible limit.
The internal 5 V and 3.3 V voltages fall below the permissible limit.
The ready watchdog is elapsing.
The reset button is pressed.
The LED arranged next to the ready contact is a red-green dual LED. The LED
can assume the following states:
LED "Ready"
Meaning
Off
Watchdog has not been started yet
or
Ready contact was opened by software (but the watchdog is still trig‐
gered internally)
Green
Ready contact is closed; watchdogs are still triggered.
Red
Ready error; at least one watchdog has responded.
Fig.7-29:
Ready LED
The IndraControl L45/L65/L85 is equipped with a slot for a Compact Flash card.
This slot can be used to insert the memory card containing the firmware (card
to be ordered separately). Additionally, data and programs are stored on this
card. Operation without Compact Flash card is not possible.
DANGER
Do not remove the Compact Flash card as long as the IndraControl L45/L65/
L85 is in operation!
To its right, the IndraControl L45/L65/L85 can be extended by additional
Rexroth Inline terminals. An I/O unit can be extended to up to 64 byte I/O by
using such terminals.
Max. 63 Rexroth Inline terminals can be connected.
For further information on the connection of Rexroth Inline termi‐
nals, please refer to the documentation "Automation Terminals of
the Rexroth Inline Product Range", parts number R911317021,
http://www.boschrexroth.com/various/utilities/mediadirectory/in‐
dex.jsp?publication=NET&objectlang_en-EN&edi‐
tion_enum=R911317021.
Bosch Rexroth AG
Connections and Interfaces
1 A, DC 60 V (resistive)
0.3 ms
None
50 ms ± 25 %
Uncontrolled movements caused by operation
without Compact Flash card!