3.6: Troubleshooting Guidelines in case any incoming
supply fault is present before switching ON the Starter
Table: 17 DOL Controller operating sequence in fault condition
8A
8B
8C
3
LMR-A
Rocker
main
Mode
switch
supply
Manual
ON
ON
Auto
ON
ON
Bypass
ON
ON*
#: Phase loss
, Phase reversal
1
NA – Starter is unprotected from incoming power supply faults,only protection from load side faults. In this mode, amber LED
will continously ON if incoming power supply is healthy and will blink if the incoming power supply is unhealthy– Refer 3.8
Starter Fault conditon:
1) LMR-A: Manual mode
8A : Check the mode of LMR-A, if it is manual mode.
8B : Switches ON the 3-Phase incoming main supply.
8C : Switch ON the rocker switch
8D : Amber LED will start blinking
8E : Amber LED will blink for a duration of min.30sec.
8F : After the ON delay duration, amber LED remains blinking indicating that the 3phase incoming supply is unhealthy.
8G : - Check the rated operational voltage of the starter in incoming terminal block (TB1) between L1- L2 , L2-L3, L1-L3
1
with suitable equipment e.g. multimeter.
- Check for the phase loss in any phase (L1,L2,L3) with suitable equipment e.g. multimeter.
8H : - After resuming incoming main supply to normal condition,
1
- Repeat the steps from 8A to 8F and then go to step no.8I
If fault still exists, then
8G : - Check the phase sequence of all the phases of incoming main supply.
2
- Identify the wrong sequence of phase connected in any of the incoming terminal.
8H : - Connect the phase sequence of all the phases correctly (R phase to L1 , Y phase to L2, B phase
2
to L3) to the incoming main supply terminals of Terminal block TB1.
- Repeat the steps from 8A to 8F and then go to step no.8I
13
8D
8E
Amber
LMR-A
Amber
LED
On-Delay
Blink
(On-delay
0.5-5min
duration)
Blink
(On-delay
0.5-5min
duration)
Blink
(On-delay
0.5-5min
duration)
, Under voltage
, Over voltage
2
3
8F
8G
8H
Possible
Corrective
causes
LED
action
of fault
Blink
#
1)
Blink
#
2)
Blink
NA
NA
ON operation
, Phase unbalance
4
5
8I
8J
8K
Amber
'ON' Push
Starter
LED
button
Operation
ON
ON
ON
ON
NA
ON
ON
ON
ON
8L
Green
LED
ON
ON
ON