7.4. Function setting

• FUNCTION SETTING can be performed with the wired or wireless remote controller.
(The remote controller is optional equipment)
• Refer to the wired or wireless remote controller manual for detailed setting information.
• Refer to "7.1. Setting the address" for indoor unit address and refrigerant circuit address
settings.
• Turn the power of the indoor unit ON before starting the setting.
* Turning on the power to the indoor units initializes EEV, so make sure the piping air tight
test and vacuuming have been conducted before turning on the power.
* Also check again to make sure no wiring mistakes were made before turning on the
power.
Function details
Function
Function
Setting number
number
00 Standard
01 Longer
Filter indica-
11
tor interval
02 Shorter
00 Enable
01 Disable
Filter indica-
13
Display only on
tor action
02
central remote
controller
(Forbidden)
20
00
(Forbidden)
23
00
(Forbidden)
24
00
Static pres-
26
Refer to 7.3. Static pressure mode
sure
00 Standard
Cool air
01 Adjust (1)
temperature
30
trigger
02 Adjust (2)
00 Standard
01 Adjust (1)
Heat air
02 Adjust (2)
temperature
31
trigger
03 Adjust (3)
00 Enable
Auto restart
40
(*1)
01 Disable
00 Super low
Follow the
Cool Air
43
setting on
Prevention
01
the remote
controller
00 Start/Stop
Emergency
01
stop
External
46
control
02 Forced stop
00 All
Display only
Error report
47
on central
target
01
remote con-
troller
Follow the
Fan set-
setting on
ting when
00
the remote
cooling
49
controller
thermostat
OFF
01 Stop
00 Mode 0
Switching
01 Mode 1
functions
02 Mode 2
for external
03 Mode 3
inputs and
60
04 Mode 4
external
05 Mode 5
outputs
06 Mode 6
terminals
07 Mode 7
(*2)
08 Mode 8
En-13
Details
Default
Adjust the filter cleaning interval
notification. If the notification is too
early, change to setting 01. If the
notification is too late, change to
setting 02.
Enable or disable the filter indica-
tor. Setting 02 is for use with a
central remote controller.
Adjust the cool air trigger
temperature. To lower the trigger
temperature, use setting 01. To
raise the trigger temperature, use
setting 02.
Adjust the heat air trigger
temperature. To lower the trigger
temperature by 6 degrees C, use
setting 01. To lower the trigger
temperature by 4 degrees C, use
setting 02. To raise the trigger
temperature, use setting 03.
Enable or disable automatic sys-
tem restart after a power outage.
Restrain the cold airflow with mak-
ing the airflow lower when starting
heating operation. To correspond
to the ventilation, set to 01.
Allow an external controller to start
or stop the system, or to perform
an emergency stop.
* If an emergency stop is
performed from an external
controller, all refrigerant systems
will be disabled.
* If forced stop is set, indoor unit
stops by the input to the external
input terminals, and Start/
Stop by a remote controller is
restricted.
Change the target for reporting er-
rors. Errors can either be reported
in all locations, or only on the
central remote controller.
When set to 01, the fan stops
when the thermostat is OFF in
cooling operation. Connection of
the wired remote controller (2-wire
type) and switching its thermistor
are necessary.
• Set this function when connecting
the VRF system to a ventilator,
economizer, humidifier, or other
external device.
• The connection terminal func-
tions can be changed depending
on the type of external device.
For details of the connection ter-
minal functions, see the Design
& Technical Manual.
Function
Function
Setting number
number
Auxiliary
00
heater con-
trol 1
Auxiliary
01
heater con-
trol 2
Heat pump
02
prohibition
control
Heater selec-
tion control
03
using outdoor
temperature 1
Heater selec-
tion control
04
using outdoor
Control
temperature 2
switching
61
Auxiliary
of external
heater control
heaters
05
by outdoor
temperature 3
Auxiliary heat
06
pump control
Auxiliary heat
pump control
07
by outdoor
temperature 1
Auxiliary heat
pump control
08
by outdoor
temperature 2
Auxiliary heat
pump control
09
by outdoor
temperature 3
00 Setting 0
01 Setting 1
02 Setting 2
03 Setting 3
04 Setting 4
05 Setting 5
06 Setting 6
Operating
07 Setting 7
temperature
08 Setting 8
switching
62
09 Setting 9
of external
10 Setting 10
heaters
11 Setting 11
12 Setting 12
13 Setting 13
14 Setting 14
15 Setting 15
16 Setting 16
17 Setting 17
Single setpoint
auto mode
00
(traditional)
Auto mode
68
type (*3)
Dual setpoint
01
auto mode
00 0°F (0°C)
01 1°F (0.5°C)
02 2°F (1.0°C)
03 3°F (1.5°C)
Deadband
04 4°F (2.0°C)
69
value (*3)
05 5°F (2.5°C)
06 6°F (3.0°C)
07 7°F (3.5°C)
08 8°F (4.0°C)
09 9°F (4.5°C)
(Forbidden)
70
00
Details
Default
Sets the control method for the
external heater being used. For
details of the control method, see
the Design & Technical Manual.
• Sets the temperature conditions
when the external heater is ON.
• For the temperature conditions,
see "Temperature conditions
when the external heater is ON".
For a more detailed explana-
tion, see the Design & Technical
Manual.
Switch the setting method of
auto mode to single or dual
(cooling/heating).
For heat pump systems, it is
necessary to set the master
indoor unit (by wired remote
controller).
Choose the minimum temperature
between cooling and heating
settings (deadband) for Dual
setpoint auto mode (set in No. 68).