Page 1
AIR CONDITIONER Ceiling type DESIGN & TECHNICAL MANUAL SINGLE INDOOR AB A30LBT AB A36LBT OUTDOOR AO A30LBTL AO A30LFTL AO A36LBTL AO A36LFTL...
Page 2
1. INDOOR UNIT CEILING TYPE : AB A30LBT AB A36LBT D2D_AB025E/03 2011.11.07...
FEATURE MODEL INDOOR UNIT OUTDOOR UNIT AOA30LBTL ABA30LBT AOA30LFTL AOA36LBTL ABA36LBT AOA36LFTL FEATURES Energy saving rank A European energy ranking rank A achieved by all DCization and optimization of the refrigerant cycle. Quiet operation Air flow mode can be set in 4 steps and more detailed air flow setting is possible.
Page 5
Filter sign operating time (Standard/long/short/no display) Filter sign display time interval and filter sign no display can be selected. Fresh-air intake OUTDOOR INDOOR FUNCTION SETTING Ceiling height (standard/high ceiling) Air conditioner operation capacity (air flow) switching is possible as response to height of installation ceiling.
WIRELESS REMOTE CONTROLLER FEATURES Four kinds of timer setup (ON / OFF / PROGRAM / SLEEP) are possible. Four kinds of timers. Easy operation. Easy to change transmission code (4 patterns) by button operation. ...
Page 7
FUNCTIONS MODE button Selects the operating mode (AUTO, HEAT, FAN, COOL, DRY). / Start / end R.C. custom code change. (Max 4 types) Economy button SET TEMP. button ( Set remote controller custom code buttons. Sets the indoor temp./ Sets R.C. custom code. Filter reset button Sleep button Pressed to select sleep timer.
SPECIFICATIONS CEILING MODEL Type INVERTER HEATPUMP Indoor unit ABA30LBT ABA36LBT Model name Outdoor unit AOA30LBTL AOA30LFTL AOA36LBTL AOA36LFTL Power source 230V~ 50Hz Available voltage range 198-264V~ 50Hz Cooling European energy label Heating 8.50 9.40 Rated Btu/h 29000 32100 Cooling 2.80 -10.00 2.80 -11.20 Min.-Max.
DIMENSIONS MODEL : ABA30L, ABA36L (Unit : mm) Top view Side view Rear view Suspension bolt pitch 1,600 Dimensions (Space Required for Installation) INDOOR UNIT (Top view) Suspension bolt should extend INDOOR UNIT outward 30 to 75. Refrigerant piping flare connection (Gas) ...
Page 10
INSTALLATION PLACE (Unit : mm) Ceiling INDOOR UNIT 80 or more 150 or more Ceiling 10 or more Obstruction Floor Ceiling panel INDOOR UNIT Ceiling panel 80 or more 150 or more 10 or more Obstruction Floor - (01 - 07) -...
FAN PERFORMANCE AND AIR FLOW 7-1. AIR VELOCITY DISTRIBUTION MODEL : ABA30L Note: Condition Fan speed : High Unit : m/s Operation mode : FAN 0.25 Unit : m/s 10 11 12 13 14 15 16 17 TOP VIEW VERTICAL : UPWARD HORIZONTAL : CENTER 0.25...
Page 15
MODEL : ABA36L Note: Condition Fan speed : High Unit : m/s Operation mode : FAN 0.25 Unit : m/s 10 11 12 13 14 15 16 17 TOP VIEW VERTICAL : UPWARD HORIZONTAL : CENTER 0.25 Unit : m/s 10 11 12 13 14 SIDE VIEW FLAP : CENTER...
7-2. AIR FLOW MODEL : ABA30L COOLING Number of Fan speed rotations Air flow (r.p.m.) 1660 HIGH 1000 1500 1200 1000 QUIET HEATING Number of Fan speed rotations Air flow (r.p.m.) 1660 HIGH 1000 1500 1200 1000 QUIET - (01 - 13) -...
Page 17
MODEL : ABA36L COOLING Number of Fan speed rotations Air flow (r.p.m.) 1900 HIGH 1100 1118 1500 1200 1000 QUIET HEATING Number of Fan speed rotations Air flow (r.p.m.) 1900 HIGH 1100 1118 1500 1200 1000 QUIET - (01 - 14) -...
ELECTRIC CHARACTERISTICS Model name AB A30L AB A36L Voltage 230 ~ Power supply Frequency Max. operating current (Indoor unit) Connection cable 1.5 - 2.5 Wiring spec. Limited wiring length - (01 - 18) -...
SAFETY DEVICES Model Protection form AB A30L AB A36L Circuit protection Current fuse (PCB) 3.15A 250V Thermal protection 140±20°C OFF Fan motor protection program 110±20°C ON - (01 - 19) -...
EXTERNAL INPUT & OUTPUT Connector INPUT OUTPUT REMARKS Control input CN102 — (Operation/Stop) See external CN103 — Operation status output input/output settings for details. — Fresh air control output 11-1. EXTERNAL INPUT CONTROL INPUT (Operation/Stop) The air conditioner can be remotely operated by means of the following on-site work. Operation is started at the following contents by adding the contact input of a commercial ON/OFF switch to a connector on the external control PC board and turning it ON.
11-2. EXTERNAL OUTPUT OPERATION STATUS OUTPUT An air conditioner operation status signal can be output. Circuit diagram example Indoor Connected unit control PC board Connector Ex.)Relay unit Ex.)Display 24V DC Relay power supply *10 m Signal Field supply * Make the distance from the PC board to the connected unit within 10m.
Page 25
FRESH AIR CONTROL OUTPUT A signal linked to air conditioner indoor fan ON can be output. * However, signal becomes OFF during cold air prevention control operation. Circuit diagram example Indoor Connected unit control PC board Ex.) Fan Ex.) Relay unit 12 V Connector...
FUNCTION SETTING 12-1. INDOOR UNIT INDOOR UNIT DIP SW Forbidden Remote control unit signal code Jumper Wire Forbidden SWITCH POSITION MAIN PCB Indoor unit Printed circuit board JUMPER WIRE SETTING Remote control unit signal code Indoor unit setting (...
Page 27
FUNCTION SETTING • This procedure changes to the function settings used to control the indoor unit according to the installation conditions. Incor settings can cause the indoor unit malfunction. • After the power is turned on, perform the “FUNCTION SETTING” according to the installation conditions using the remote control unit. •...
SELECTING THE REMOTE CONTROL UNIT CODE Setting the Filter Sign When two or more air conditioners are installed in a room and the remote control unit is operating an air conditioner other than • The indoor unit has a sign to inform the user that it is time to the one you wish to set, change the signal code of the remote clean the filter.
OPTIONAL PARTS Exterior Parts name Model No. Summary Wired remote Unit control is performed by wired UTB- UD controller remote controller Optional drain lift-up mechanism Drain Pump unit UTR-DPB24T allows more flexible installation. Round flange is used when the fresh air duct is installed.
Page 30
2. OUTDOOR UNIT SINGLE TYPE : AO A30LBTL AO A36LBTL AO A30LFTL AO A36LFTL D2D_AO022E/03 2011.11.07...
SPECIFICATIONS Type INVERTER HEATPUMP Model name AO A30LBTL AO A36LBTL Power source 230V ~ 50Hz Available voltage range 198-264V ~ 50Hz Starting current 15.0 15.0 Cooling 3600 4000 Airflow rate Heating 3800 3800 Type × Q'ty Propeller × 1 Motor output Cooling Sound pressure level...
Page 33
Type INVERTER HEATPUMP Model name AO A30LFTL AO A36LFTL Power source 230V ~ 50Hz Available voltage range 198-264V ~ 50Hz Starting current 15.0 15.0 Cooling 3600 3800 Airflow rate Heating 3600 3800 Type × Q'ty Propeller × 1 Motor output Cooling Sound pressure level...
DIMENSIONS MODEL : AOA30LB, AOA36LB, AOA30LF, AOA36LF (Unit : mm) Top view Front view Side view Air flow Bottom view INSTALLATION PLACE When there are obstacles at the back, When there are obstacles at the back, When there are obstacles at the back side(s), and top.
CAPACITY COMPENSATION RATE FOR PIPE LENGTH AND HEIGHT DEFFERENCE This table is created using the maximum capacity. MODEL : AOA30LB, AOA30LF Pipe length (m) COOLING 0.908 0.894 0.876 0.935 0.923 0.909 0.891 1 Indoor unit is upper 0.968 0.951 0.938...
Page 41
This table is created using the maximum capacity. MODEL : AOA36LB, AOA36LF Pipe length (m) COOLING 0.908 0.894 0.876 0.935 0.923 0.909 0.891 1 Indoor unit is upper 0.968 0.951 0.938 0.924 0.906 than outdoor unit 0.982 0.972 0.954 0.942...
AIR FLOW MODEL : AOA30LB COOLING Number of rotations Air flow (r.p.m) 3600 1000 2119 HEATING Number of rotations Air flow (r.p.m) 3800 1056 2236 MODEL : AOA36LB COOLING Number of rotations Air flow (r.p.m) 4000 1111...
Page 44
MODEL : AOA30LF COOLING Number of rotations Air flow (r.p.m) 3600 1000 2119 HEATING Number of rotations Air flow (r.p.m) 3600 1000 2119 MODEL : AOA36LF COOLING Number of rotations Air flow (r.p.m) 3800 1056 2236...
ELECTRIC CHARACTERISTICS AO A30LB AO A36LB Model name AO A30LF AO A36LF Voltage 230 ~ Power supply Frequency *1) Max. operating current 17.0 20.0 Starting current 15.0 Main fuse (Circuit breaker) current *2) Wiring spec. Power cable 5.3 - 6.0 *3)Limited wiring length *1) The maximum current is the total current of indoor unit and outdoor unit.
SAFETY DEVICES Model Protection form AO A30LB AO A36LB AO A30LF AO A36LF Current fuse (NEAR THE TERMINAL) 25A 250V Circuit protection Current fuse (FILTER PRINTED CIRCUIT BOARD) 10A 250V Current fuse (MAIN PRINTED CIRCUIT BOARD) 3.15A 250V OFF : 140±20°C Fan motor protection...