Technical specifications
Article number
Output current
for signal "1" rated value
for signal "1" permissible range, max.
for signal "0" residual current, max.
Output delay with resistive load
"0" to "1", typ.
"0" to "1", max.
"1" to "0", typ.
"1" to "0", max.
Parallel switching of two outputs
for logic links
for uprating
for redundant control of a load
Switching frequency
with resistive load, max.
with inductive load, max.
on lamp load, max.
Total current of the outputs
Current per channel, max.
Current per group, max.
Current per module, max.
Cable length
shielded, max.
unshielded, max.
Isochronous mode
Isochronous operation (application synchro-
nized up to terminal)
Interrupts/diagnostics/status information
Diagnostics function
Substitute values connectable
Alarms
Diagnostic alarm
36
6ES7522-1BF00-0AB0
2 A
2.4 A; Note derating specification for PWM opera-
tion
0.5 mA
80 µs
100 µs
300 µs
500 µs
Yes
No
Yes
100 Hz; With PWM operation: 500 Hz
0.5 Hz; According to IEC 60947-5-1, DC-13; max.
500 Hz with PWM operation only with external
circuit; see additional description in the manual
10 Hz
2 A; see additional description in the manual
8 A; see additional description in the manual
16 A; see additional description in the manual
1 000 m
600 m
No
Yes
Yes
Yes
DQ 8x24VDC/2A HF Digital Output Module (6ES7522-1BF00-0AB0)