Technical specifications
Article number
Output current
for signal "1" rated value
•
for signal "1" permissible range, max.
•
for signal "0" residual current, max.
•
Output delay with resistive load
"0" to "1", typ.
•
"0" to "1", max.
•
"1" to "0", typ.
•
"1" to "0", max.
•
Parallel switching of two outputs
for logic links
•
for uprating
•
for redundant control of a load
•
Switching frequency
with resistive load, max.
•
with inductive load, max.
•
on lamp load, max.
•
Total current of the outputs
Current per channel, max.
•
Current per group, max.
•
Current per module, max.
•
Cable length
shielded, max.
•
unshielded, max.
•
Isochronous mode
Isochronous operation (application synchro-
nized up to terminal)
Interrupts/diagnostics/status information
Diagnostics function
Substitute values connectable
Alarms
Diagnostic alarm
•
36
6ES7522-1BF00-0AB0
2 A
2.4 A; Note derating specification for PWM opera-
tion
0.5 mA
80 µs
100 µs
300 µs
500 µs
Yes
No
Yes
100 Hz; With PWM operation: 500 Hz
0.5 Hz; According to IEC 60947-5-1, DC-13; max.
500 Hz with PWM operation only with external
circuit; see additional description in the manual
10 Hz
2 A; see additional description in the manual
8 A; see additional description in the manual
16 A; see additional description in the manual
1 000 m
600 m
No
Yes
Yes
Yes
DQ 8x24VDC/2A HF Digital Output Module (6ES7522-1BF00-0AB0)
Manual, 06/2018, A5E03485650-AF