Remote device net Ver.1 mode
The following table lists the maximum number of connectable modules for a system configured in the remote device net Ver.1
mode. For the modes, refer to the following.
Page 23 Modes
For one master station, 64 modules of a remote I/O station and remote device station can be connected in total. Note,
however, that the following conditions must be satisfied.
Item
{(1 a) + (2 b) + (3 c) + (4 d)} 64
Condition 1
Remote device net Ver.2 mode
The following table lists the maximum number of connectable modules for a system configured in the remote device net Ver.2
mode. For the modes, refer to the following.
Page 23 Modes
For one master station, 64 modules of a remote I/O station and remote device station can be connected in total. Note,
however, that the following conditions must be satisfied.
Item
Condition 1
{(a + a2 + a4 + a8)
+ (b + b2 + b4 + b8) 2
+ (c + c2 + c4 + c8) 3
+ (d + d2 + d4 + d8) 4} 64
[{(a 32) + (a2 32) + (a4 64) + (a8 128)}
Condition 2
+ {(b 64) + (b2 96) + (b4 192) + (b8 384)}
+ {(c 96) + (c2 160) + (c4 320) + (c8 640)}
+ {(d 128) + (d2 224) + (d4 448) + (d8 896)}] 8192
[{(a 4) + (a2 8) + (a4 16) + (a8 32)}
Condition 3
+ {(b 8) + (b2 16) + (b4 32) + (b8 64)}
+ {(c 12) + (c2 24) + (c4 48) + (c8 96)}
+ {(d 16) + (d2 32) + (d4 64) + (d8 128)}] 2048
Remote I/O net mode
The maximum number of connectable modules for a system configured in the remote I/O net mode is 64 stations. For the
modes, refer to the following.
Page 23 Modes
Number of modules
a: Number of modules occupying 1 station
b: Number of modules occupying 2 stations
c: Number of modules occupying 3 stations
d: Number of modules occupying 4 stations
Number of modules
a: Total number of Ver.1-compatible remote stations occupying 1 station
and Ver.2-compatible remote device stations occupying 1 station
(extended cyclic setting: single)
b: Total number of Ver.1-compatible remote stations occupying 2 stations
and Ver.2-compatible remote device stations occupying 2 stations
(extended cyclic setting: single)
c: Total number of Ver.1-compatible remote stations occupying 3 stations
and Ver.2-compatible remote device stations occupying 3 stations
(extended cyclic setting: single)
d: Total number of Ver.1-compatible remote stations occupying 4 stations
and Ver.2-compatible remote device stations occupying 4 stations
(extended cyclic setting: single)
a2: Number of Ver.2-compatible remote device stations occupying 1 station
(extended cyclic setting: double)
b2: Number of Ver.2-compatible remote device stations occupying 2
stations (extended cyclic setting: double)
c2: Number of Ver.2-compatible remote device stations occupying 3
stations (extended cyclic setting: double)
d2: Number of Ver.2-compatible remote device stations occupying 4
stations (extended cyclic setting: double)
a4: Number of Ver.2-compatible remote device stations occupying 1 station
(extended cyclic setting: quadruple)
b4: Number of Ver.2-compatible remote device stations occupying 2
stations (extended cyclic setting: quadruple)
c4: Number of Ver.2-compatible remote device stations occupying 3
stations (extended cyclic setting: quadruple)
d4: Number of Ver.2-compatible remote device stations occupying 4
stations (extended cyclic setting: quadruple)
a8: Number of Ver.2-compatible remote device stations occupying 1 station
(extended cyclic setting: octuple)
b8: Number of Ver.2-compatible remote device stations occupying 2
stations (extended cyclic setting: octuple)
c8: Number of Ver.2-compatible remote device stations occupying 3
stations (extended cyclic setting: octuple)
d8: Number of Ver.2-compatible remote device stations occupying 4
stations (extended cyclic setting: octuple)
2.2 Maximum Number of Connectable Modules
2 SPECIFICATIONS
21