WARNING: Disconnect an power from the starter and
overload relay
servicing.
installation, modification, ou entretien.
CAUTION: Before installing this product in a nuclear
application, determine if it is intended for such use.
ATTENTION: Avant d'installer le produit dans une
application nudeaire, verifier si cela est permis.
The ABB Solid State Overload Relay is shown in
Figure l.
The catalog
specifications are listed in Table 1.
The following instructions describe the installation
of a Solid State Overload Relay as a replacement for
an existing overload relay on a 300-Line starter.
1. Disconnect all sources of power to the starter.
2. Disconnect all control and power wiring from
the load side of the existing overload relay.
3. Remove and save the overload relay mounting
screw, located at the bottom right and upper left
corners of the overload relay housing.
4. Remove the overload relay from the starter
baseplate.
5. Reassemble the Solid State 9verload Relay from
this kit in the reverse order.
Catalog Number:
Starter Mount
Replacement
1
GEH-6432 User's Guide
Solid State Overload Relay
NEMA Sizes 5 & 6
AVERTISSEMENT:
Introduction
Replacement Installation
NOTE: Maximum fuse and breaker sizes are intended as guidelines. Refer to NEC and local codes for proper fuse and
breaker selection.
Table 1. Solid State Overload Relay, NEMA Sizes 5 & 6, catalog numbers and electrical specifications.
before installing,
modifying,
Couper
l'alimentation
numbers
and
NEMA
Size
CR324GXNS
5
CR324GXPS
5
CR324GXQS
5
CR324HXSS
6
CR324HXTS
6
or
avant
electrical
6. Check to see that the two wires
current transformer have been reconnected to
the top and bottom terminals on the same pole
of the Solid State Overload Relay as on the
overload relay that was replaced.
7. Torque the bottom terminal screws to 20 lb-in
and the top terminal screws to 1 2 lb-in.
8. Connect the control and power wiring to the
terminals on the load side of the Solid State
Overload Relay, shown in Figure 2.
9. Reconnect power sources to the starter.
10. Fully depress the blue reset button on the Solid
State Overload Relay to insure that it is in the
reset position. The yellow trip flag will be at its
right position, as illustrated in Figure 2.
Current
Max Fuse Size,
Range,
amps (Class
amps
32-68
250
500
65-135
130-270
800
130-270
800
260- 540
1600
Figure 1. Solid State Overload Relay (external current transformers
T,H�J,L,R,K)
Max Breaker
Use with
amps
Contactor
CR306G
250
400
CR306G
800
CR306G
CR306HH
800
1600
CR306HH
Rating,
ABB
not shown}.
from each

Advertisement

loading

Summary of Contents for GE GEH-6432

  • Page 1 CR306HH 130-270 CR324HXTS 260- 540 1600 1600 CR306HH Replacement Rating, GEH-6432 User's Guide Solid State Overload Relay NEMA Sizes 5 & 6 AVERTISSEMENT: Introduction Figure 1. Solid State Overload Relay (external current transformers not shown}. Replacement Installation T,H�J,L,R,K) NOTE: Maximum fuse and breaker sizes are intended as guidelines. Refer to NEC and local codes for proper fuse and breaker selection.
  • Page 2 tionai dust protection. To protect against unauthorized persons' tampering with the settings, insert a w i r e lock through the locking tabs. The Solid State Overioad Relay contains a trip function activated by an unbalance among the phase currents. The percent difference between the highest lowest phase current mav be set between 20% and 50%.
  • Page 3 60/75 C copper wire only. Tighten the terminal 3. Depress and release the reset button to insure screws to 12 lb-in. that the Solid State Overload Relay is reset. In this condition, there should be continuity between the terminals. 4. Slide the mechanical trip test lever from right to left to trip the Solid State Overload Relay.
  • Page 4 ABB Sales Office. — — — ABB Inc. GE is a trademark of GE. Manufactured We reserve the right to make technical We reserve all rights in this document and 305 Gregson Drive by ABB Inc. under license from GE.