The available energy capacity depends now on the criteria for the U
the actual DC link voltage supplied into common DC system. Selection of the
value for U
depends on common DC system configuration and its
dc,lim
general requirements.
Here are the major alternatives for the U
module DC voltage limits (see also the paragraph ACSM1 DC voltage
limits).
Absolute maximum limit is defined according to the DC overvoltage trip
limit including some safety margin.
U
840
V DC
dc
,lim
DC over voltage control is enabled, but not activated.
U
810
V DC
dc
,
lim
DC link voltage level, where the braking choppers are not yet
activated.
U
780
V DC
dc
,lim
To determine whether the energy capacity is adequate (i.e. the selected
U
voltage level is not reached) the following condition must be fulfilled
dc,lim
W
> E
dc
gen
Where E
is the regenerative energy to the DC link during the generating
gen
period:
=
E
P
dt
gen
gen
based on the ACSM1 drive
dc,lim
23
and
dc,lim