Bosch Rexroth IndraControl XFE01.1-SY-01 Operating Instructions Manual page 16

Module
Hide thumbs Also See for Rexroth IndraControl XFE01.1-SY-01:
Table of Contents

Advertisement

10/45
Ambient conditions
Surge standard
Test acc. to DIN EN 61000-4-5
Surge
Increased noise level
HF coupling to lines
Test acc. to DIN EN 61000-4-6
HF coupling to lines
Increased noise level
Voltage dips, short interruptions and
voltage fluctuations at DC mains inputs
Test acc. to DIN EN 61000-4-29
Voltage dips, short interruptions and
voltage fluctuations at DC mains inputs
Increased requirements
Tab. 6-4: Electromagnetic operating conditions: Testing electromagnetic compatibility acc.
to EN 61000-6-2 as well as increased noise level acc. to EN 61326-3-1
NOTICE
Provide sufficient ventilation and cooling to ensure that the ambient
temperature of the control does not exceed 55°C.
Bosch Rexroth AG R911376654_Edition 03
IndraControl XFE01.1-SY-01 Safety Ex-
Asymmetric coupling:
0.5 kV (supply lines)
1 kV (signal/data lines)
Symmetric coupling:
0.5 kV (supply lines)
Asymmetric coupling:
2 kV (supply lines)
2 kV (signal and data lines)
Symmetric coupling:
1 kV (supply lines)
0.15 MHz to 80 MHz: 10 V
0.15 MHz to 80 MHz: 20 V
24 V DC supply voltage: 20 interruptions every 10 s,
interruption period of 10 ms
24 V DC supply voltage:
1. 40% UT (rated voltage) for 10 ms
2. 0% UT (rated voltage) for 20 ms
Voltage deviation of -15 % to +20 %
3 attempts, period of 10 s
In case of overheating, the Safety extension
module IndraControl XFE01.1-SY-01 goes into a
safe
tension Module
, criterion A
eff
, criterion FS
eff