5.1
External Control Operating Mode Selection
There are four modes when operating using signals from external equipment.
1. ON/OFF interlock ( the chosen function from either external signal or remote control switch has priority )
2. ON interlock
3. OFF interlock
4. External priority ON/OFF interlock
Operating Signal
Mode
When external signal is level signal.
External signal
ON/OFF
inter-
Remote controller
[ON/OFF] button pressed
lock
Operating
Operating
condition
Stopped
External signal
ON
inter-
Remote controller
lock
[ON/OFF] button pressed
Operating
Operating
condition
Stopped
External signal
OFF
inter-
Remote controller
lock
[ON/OFF] button pressed
Operating
condition
External
External signal
priority
ON/OFF
Remote controller
[ON/OFF] button pressed
inter-
lock
Operating
Operating
condition
Stopped
Setting Method
When PZ-41SLB-E is used, use the remote controller to set. (Refer to page C-91)
When PZ-41SLB-E is not used, use the DIP switch 5-7,8 to set. (Refer to page C-76)
Operating
Stopped
When external signal is pulse signal.
( Optional setting )
External signal
Remote controller
[ON/OFF] button pressed
Operating
Operating
condition
Stopped
External signal
Remote controller
[ON/OFF] button pressed
Operating
Operating
condition
Stopped
External signal
Remote controller
[ON/OFF] button pressed
Operating
Operating
condition
Stopped
This mode does not exist.