Wiring Requirements for SLC Device
When using T-taps, the total length of all taps and the main bus must not exceed 40,000 feet. This requirement must be met in addition to the
maximum distance requirements for the various wire gauges.
4.3.2 Wiring SLC Devices in (Class A) Configuration
Figure 4.3 illustrates how to wire the SLC loop for Class A installations. .
Model SK-FFT Manual — P/N 54711:B2 12/18/2020
Figure 4.2 Calculating Wire Run Length for a T-tap
Figure 4.3 Class A SLC Configuration
SLC Device Installation