4. TECHNICAL CHARACTERISTICS

4.1 MODEL LIST

Here is the information required to completely define the MLJ models. (See chart below):
MLJ 100 _ A010 _ 00 _
Communications
0 - No communications
5 - RS-485
6 - RS-485, 232, plastic optic fiber
7 - RS-485, 232, glass optic fiber
4.2 TECHNICAL CHARACTERISTICS
• FREQUENCY
50 and 60 Hz, programmable by user.
• NOMINAL VOLTAGE
63 to 220 Vac.
• AUXILIARY POWER
24 - 28 Vdc ± 20%
110 - 250 Vdc ± 20%
• MAXIMUM VOLTAGE ALLOWABLE
Continuous: 440 Vac.
• TEMPERATURE RANGES
Operating:
Storage:
Comply with IEC standard 255-6 (for the -25º to +55ºC interval) and ANSI C37.90 (specifying the -
25º to +55ºC interval).
• AMBIENT HUMIDITY
Up to 95% without condensation.
• CLOSURE ENABLE CONTACTS
Break capacity:
Maximum continuous voltage:
Maximum alternating voltage:
Carry continuously:
Make and carry:
GEK - 105560
Auxiliary and inputs voltage
F - 24/ 48 Vdc
H - 110/ 250 Vdc
-25ºC to +55ºC
-40ºC to +65ºC
4000 VA
300 Vdc
440 Vac
16 A
30 A