Environmental; Type Tests & Certifications - GE Multilin MIB Instruction Manual

High impedance bus differential relay
Table of Contents

Advertisement

2.11 TECHNICAL SPECIFICATIONS FOR HID MODULE
NOMINAL VOLTAGE
Latching relay LO
Latching relay HI
Operation range
2
Consumption
Pickup value
OPERATING TIME (at nominal voltage)
Close time (N.O. contact)
Open time (N.C. contact)
CONTACTS
Continuous current
Make and carry
Breaking
DIELECTRIC WITHSTAND
Between independent circuits
Between circuits and ground
Between open contact
terminals
Mechanical life
Operating temperatures
Ambient storage temperatures
Maximum relative humidity
Altitude
Pollution degree
The MIB system complies with the following standards, which include the standards required by Community Directive 89/
336 for the CE marking, in line with European standards. It also complies with the European directive requirements for low
voltage, and the environmental and operating requirements established in ANSI standards C37.90, IEC 255-5, IEC 255-6
and IEC 68.
Test
Insulation Test Voltage:
Surge Test Voltage:
1 MHz Interference:
2-22
48 VDC
125 VDC
80 % to 150 % of nominal voltage
8 W at nominal voltage
60% of nominal voltage
< 25 ms.
< 20 ms.
10 A continious
20 A during 1 minute
200 A during 1 second
30 A
5000 VA non inductive at 250 Vac
375 W inductive at 125 Vdc.
250 W inductive at 250 Vdc.
2500 Vac one minute
2500 Vac one minute
1800 Vac one minute
More than 10 million operations
-20ºC to +60ºC
-40ºC to +80ºC
95%
2000 m. max
2
Standard
IEC 60255-5
IEC 60255-5
IEC 60255-22-1
MIB High Impedance Bus Differntial Relay
2 PRODUCT DESCRIPTION
2.11.2 LATCHING RELAY

2.11.3 ENVIRONMENTAL

2.11.4 TYPE TESTS & CERTIFICATIONS
Class
2kV, 50/60 Hz 1 min
5 kV, 0.5 J. (3 positive
pulses and 3 negative.)
III
GEK-106426B