IEC 61000-4-8
IEC 61000-4-12
IEC 61000-4-16
IEC 61000-4-17
IEC 61000-4-29
IEC 60255-5
a
Siemens-specified severity levels.
EMC Immunity Type Tests for IEEE 1613
Note
The RUGGEDCOM RX1512 meets Class 2 requirements for an all-fiber
configuration and Class 1 requirements for copper ports. Class 1 allows for
temporary communication loss, while Class 2 requires error-free and interrupted
communications.
RUGGEDCOM RX1512
Installation Manual, 04/2021, C79000-G8976-1057-20
Test
Magnetic Field
Damped Oscillatory
Mains Frequency
Voltage
Ripple on DC
Power Supply
Voltage Dips
and Interrupts
Dielectric Strength
HV Impulse
Description
HV Impulse
Dielectric Strength
Fast Transient
Oscillatory
Radiated RFI
ESD
6.2 EMC and Environmental Type Tests
Description
Enclosure Ports
Signal ports
DC Power Ports
Signal ports
DC Power Ports
DC Power Ports
DC Power Ports
Signal ports
DC Power Ports
Signal ports
DC Power Ports
Signal ports
DC Power Ports
Signal ports
DC Power Ports
Signal ports
DC Power Ports
Earth ground ports
Signal ports
DC Power Ports
Enclosure ports
Enclosure Contact
Enclosure Air
Certification
Test Levels
100 A/m, continuous
1000 A/m for 1 s
1000 A/m for 1 s
2.5 kV common, 1 kV
differential mode @1 MHz
30 V Continuous
300 V for 1 s
10%
30% for 0.1 s
60% for 0.1 s
100% for 0.05 s
2 kV (Failsafe Relay output)
2 kV
5 kV (Failsafe Relay output)
5 kV
Test Levels
5 kV (Failsafe Relay Output)
5 kV
2 kV
2 kV
± 4 kV @ 2.5 kHz
± 4 kV
2.5 kV common mode @1MHz
2.5 kV common
1 kV differential mode @ 1 MHz
35 V/m
± 8 kV
± 15 kV
Severity
Levels
a
Note
5
3
4
3
 
 
41