Line reactors for power modules pm330
Hide thumbs Also See for SINAMICS G120P:

Advertisement

General
Note
Length of connecting cables
The connection cables between line reactor and Power Module, as well as between line
reactor and line filter, must be kept as short as possible (max. 5 m).
You must use shielded connection cables, whose cable shields are attached at both ends.
Shielding can only be omitted if the following conditions are met:
• The cables do not exceed 1 m in length.
• The cables are laid flush with the rear metal wall of the control cabinet.
• The cables are laid in a way that keeps them physically separate from signal cables.
Do not route any cables near the line reactor. If this cannot be avoided, observe a minimum
distance of 200 mm.
Assignment of line reactor and Power Module
Table 2- 1
Assignment of line reactor and Power Module
Power Module
6SL3310-1PE33-0AA0
6SL3310-1PE33-7AA0
6SL3310-1PE34-6AA0
6SL3310-1PE35-8AA0
6SL3310-1PE36-6AA0
6SL3310-1PE37-4AA0
6SL3310-1PE38-4AA0
6SL3310-1PE38-8AA0
6SL3310-1PE41-0AA0
6SL3310-1PG35-8AA0
6SL3310-1PG36-5AA0
6SL3310-1PG37-2AA0
10
Unit rating of the Power Module
Line voltage 380 – 480 V 3 AC
160 kW
200 kW
250 kW
315 kW
355 kW
400 kW
450 kW
500 kW
560 kW
Line voltage 500 – 690 V 3 AC
500 kW
560 kW
630 kW
Suitable line reactor
6SL3000-0CE33-3AA0
6SL3000-0CE35-1AA0
6SL3000-0CE35-1AA0
6SL3000-0CE36-3AA0
6SL3000-0CE37-7AA0
6SL3000-0CE37-7AA0
6SL3000-0CE38-7AA0
6SL3000-0CE41-0AA0
6SL3000-0CE41-0AA0
6SL3000-0CH36-0AA0
6SL3000-0CH38-4AA0
6SL3000-0CH38-4AA0
Operating Instructions, 04/2016, A5E32845290B AC