Contact capacity
Note) For details, refer to JIS C 4601 (1993).
Voltage tripping type
DC110V 15A (L/R=0ms)
Making
DC220V 10A (L/R=0ms)
(Closing)
AC110V 10A (cosφ=0.1)
DC110V 0.3A (L/R=7ms)
Breaking
AC110V 5A (cosφ=0.1)
(Opening)
AC220V 1A (cosφ=0.1)
Breaking (Opening): AC110V 60A
The 2Ω (power factor = 0.5) loads in parallel to
the contacts
8
Current tripping type
JEP0-IL9555