Panasonic WH-MDC05J3E5 Service Manual

Panasonic WH-MDC05J3E5 Service Manual

Air-to-water heatpump
Hide thumbs Also See for WH-MDC05J3E5:
Table of Contents

Advertisement

This service information is designed for experienced repair technicians only and is not designed for use by the general public.
It does not contain warnings or cautions to advise non-technical individuals of potential dangers in attempting to service a product.
Products powered by electricity should be serviced or repaired only by experienced professional technicians. Any attempt to
service or repair the products dealt with in this service information by anyone else could result in serious injury or death.
R32 REFRIGERANT
– This Air Conditioner contains and operates with refrigerant R32.
THIS PRODUCT MUST ONLY BE INSTALLED OR SERVICED BY QUALIFIED PERSONNEL.
Refer to National, State, Territory and local legislation, regulations, codes, installation & operation manuals, before the installation,
maintenance and/or service of this product.
In order to avoid frostbite, be assured of no refrigerant leakage during the installation or repairing of refrigerant circuit.
WARNING
CAUTION
PRECAUTION OF LOW TEMPERATURE
Order No: PAPAMY2003034CE
Mono Bloc Unit
WH-MDC05J3E5
WH-MDC07J3E5
WH-MDC09J3E5
Destination
Europe
Turkey
© Panasonic Corporation 2020.

Advertisement

Table of Contents
loading

Summary of Contents for Panasonic WH-MDC05J3E5

  • Page 1 Refer to National, State, Territory and local legislation, regulations, codes, installation & operation manuals, before the installation, maintenance and/or service of this product. PRECAUTION OF LOW TEMPERATURE In order to avoid frostbite, be assured of no refrigerant leakage during the installation or repairing of refrigerant circuit. © Panasonic Corporation 2020.
  • Page 2: Table Of Contents

    11.2 Refrigerant System ........51 14.31 Flow Sensor ..........140 12. Installation Instruction ........52 15. Protection Control (WH-MDC05J3E5)..141 12.1 Mono Bloc Unit ..........52 15.1 Protection Control for All Operations ..141 12.2 Variation of system ........64 15.2 Protection Control for Heating...
  • Page 3 17.5 How To Adjust Pump Speed ..... 152 17.6 How To Unlock Cool Mode ......153 17.7 EEPROM Factory Default Data Setup Procedure ..........154 17.8 Dry Concrete Setup ........155 18. Maintenance Guide ........157 18.1 Maintenance Menu ........158 19.
  • Page 4: Safety Precautions

    1. Safety Precautions  Read the following “SAFETY PRECAUTIONS” carefully before installation of (Mono bloc) Air-to-Water Heatpump system (hereafter referred to as “Mono bloc unit”).  Electrical works and water installation works must be done by licensed electrician and licensed water system installer respectively.
  • Page 5 WARNING When installing electrical equipment at wooden building of metal lath or wire lath, in accordance with electrical facility standard, no electrical contact between equipment and building is allowed. Insulator must be installed in between. This installation may be subjected to building regulation approval applicable to respective country that may require to notify the local authority before installation.
  • Page 6: Precaution For Using R32 Refrigerant

    2. Precaution for Using R32 Refrigerant  The basic installation work procedures are the same as conventional refrigerant (R410A, R22) models. However, pay careful attention to the following points: WARNING Since the working pressure is higher than that of refrigerant R22 models, some of the piping and installation and service tools are special.
  • Page 7 CAUTION Installation (Space)  Must comply with national gas regulations, state municipal rules and legislation. Notify relevant authorities in accordance with all applicable regulations.  Must ensure mechanical connections be accessible for maintenance purposes.  In cases that require mechanical ventilation, ventilation openings shall be kept clear of obstruction. ...
  • Page 8 CAUTION Repairs to sealed components  During repairs to sealed components, all electrical supplies shall be disconnected from the equipment being worked upon prior to any removal of sealed covers, etc.  If it is absolutely necessary to have an electrical supply to equipment during servicing, then a permanently operating form of leak detection shall be located at the most critical point to warn of a potentially hazardous situation.
  • Page 9 CAUTION Decommissioning  Before carrying out this procedure, it is essential that the technician is completely familiar with the equipment and all its details.  It is recommended good practice that all refrigerants are recovered safely.  Prior to the task being carried out, an oil and refrigerant sample shall be taken in case analysis is required prior to re-use of reclaimed refrigerant.
  • Page 10: Specifications

    3. Specifications WH-MDC05J3E5 Item Unit Refrigerant System Performance Test Condition EN 14511 / EN14825 Condition A35W7 (Ambient/Water) 5.00 Cooling Capacity BTU/h 17100 kcal/h 4300 3.31 Cooling EER kcal/hW 2.85 Condition A7W35 A2W35 (Ambient/Water) 5.00 5.00 Heating Capacity BTU/h 17100 17100...
  • Page 11 Item Unit Refrigerant System Type Propeller Fan Material Motor Type DC Motor (8-poles) Input Power Output Power Cooling: 650 Fan Speed Heating: 520 Fin material Aluminium (Pre Coat) Fin Type Corrugated Fin Heat Exchanger Row × Stage × FPI 2 × 30 × 17 Size (W ×...
  • Page 12 Item Unit Water System Performance Test Condition EN 14511 / EN14825 Cooling: 10 ~ 43 Outdoor Ambient °C Heating: -20 ~ 35 Operation Range Cooling: 5 ~ 20 Water Outlet °C Heating: 20 ~ 55 ( Below Ambient -15°C) 20 ~ 60 (Above Ambient -10°C) Cooling: 12.0 Internal Pressure Differential Heating: 12.0...
  • Page 13: Wh-Mdc07J3E5

    WH-MDC07J3E5 Item Unit Refrigerant System Performance Test Condition EN 14511 / EN14825 Condition A35W7 (Ambient/Water) 7.00 Cooling Capacity BTU/h 23900 kcal/h 6020 3.06 Cooling EER kcal/hW 2.63 Condition A7W35 A2W35 (Ambient/Water) 7.00 7.00 Heating Capacity BTU/h 23900 23900 kcal/h 6020 6020 4.76 3.40...
  • Page 14 Item Unit Refrigerant System Type Propeller Fan Material Motor Type DC Motor (8-poles) Input Power Output Power Cooling: 670 Fan Speed Heating: 560 Fin material Aluminium (Pre Coat) Fin Type Corrugated Fin Heat Exchanger Row × Stage × FPI 2 × 30 × 17 Size (W ×...
  • Page 15 Item Unit Water System Performance Test Condition EN 14511 / EN14825 Cooling: 10 ~ 43 Outdoor Ambient °C Heating: -20 ~ 35 Operation Range Cooling: 5 ~ 20 Water Outlet °C Heating: 20 ~ 55 ( Below Ambient -15°C) 20 ~ 60 (Above Ambient -10°C) Cooling: 22.0 Internal Pressure Differential Heating: 22.0...
  • Page 16: Wh-Mdc09J3E5

    WH-MDC09J3E5 Item Unit Refrigerant System Performance Test Condition EN 14511 / EN14825 Condition A35W7 (Ambient/Water) 9.00 Cooling Capacity BTU/h 30700 kcal/h 7740 2.71 Cooling EER kcal/hW 2.33 Condition A7W35 A2W35 (Ambient/Water) 9.00 7.45 Heating Capacity BTU/h 30700 25400 kcal/h 7740 6410 4.48 3.13...
  • Page 17 Item Unit Refrigerant System Type Propeller Fan Material Motor Type DC Motor (8-poles) Input Power Output Power Cooling: 700 Fan Speed Heating: 670 Fin material Aluminium (Pre Coat) Fin Type Corrugated Fin Heat Exchanger Row × Stage × FPI 2 × 30 × 17 Size (W ×...
  • Page 18 Item Unit Water System Performance Test Condition EN 14511 / EN14825 Cooling: 10 ~ 43 Outdoor Ambient °C Heating: -20 ~ 35 Operation Range Cooling: 5 ~ 20 Water Outlet °C Heating: 20 ~ 55 ( Below Ambient -15°C) 20 ~ 60 (Above Ambient -10°C) Cooling: 32.0 Internal Pressure Differential Heating: 32.0...
  • Page 19: Features

    4. Features  Inverter Technology - Energy saving  High Efficiency  Compact Design  Environment Protection - Non-ozone depletion substances refrigerant (R410A)  Easy to use control panel  Weekly Timer setting  Quality Improvement - Random auto restart after power failure for safety restart operation - Gas leakage protection - Prevent compressor reverse cycle - Inner protector to protect compressor...
  • Page 20: Location Of Controls And Components

    5. Location of Controls and Components Indoor Unit 5.1.1 Location of Control...
  • Page 21 Display Mode selection AUTO • Depending on the preset outdoor COOL • COOL operation is either turned temperature, the system selects ON or OFF. HEAT or * COOL operation • The unit provides cooling to the mode. system. Auto Heat Auto Cool AUTO •...
  • Page 22 5.1.2 Initialization Before starting to install the various menu settings, please initiate the Remote Controller by selecting the language of operation and installing the date and time correctly. When power is turned on for the rst time, it becomes the setting screen automatically. It can also be set from personal setting of the menu.
  • Page 23 5.1.4 Menus For user Select menus and determine settings according to the system available in the household. All initial settings must be done by an authorised dealer or a specialist. It is recommended that all alterations of the initial settings are also done by an authorised dealer or a specialist.
  • Page 24 t l u i t t i t t o i t 2 System check Energy monitor Present Present or historical chart of Select and retrieve energy consumption, generation or COP. Historical chart Select and retrieve • COP= Coef cient of Performance. •...
  • Page 25 t l u i t t i t t o i t Backlight Sets the duration of screen backlight. 1 min Backlight intensity Sets screen backlight brightness. Clock format Sets the type of clock display. Date & Time Sets the present date and time. Year / Month / Day / Hour / Min Language ENGLISH / FRANÇAIS / DEUTSCH /...
  • Page 26 5.1.5 Menus For installer t l u i t t i t t o i t 5 Installer setup System setup Optional PCB connectivity To connect to the external PCB required for servicing. • If the external PCB is connected (optional), the system will have following additional functions: Buffer tank connection and control over its function and temperature.
  • Page 27 t l u i t t i t t o i t Buffer tank connection To connect tank to the system and if selected YES, to set T temperature. • The optional PCB connectivity must be selected YES to enable the function. Set T for Buffer •...
  • Page 28 t l u i t t i t t o i t Yes Auto To select a bivalent connection to allow an additional heat source such as a boiler to heat- Set outdoor up the buffer tank and domestic temperature for -5 °C hot water tank when heatpump turn ON Bivalent...
  • Page 29 t l u i t t i t t o i t Delay timer to stop the bivalent heat 0:30 source (in hour and minutes). Control pattern Advanced parallel DHW Yes • DHW Tank is activated only after selecting “Yes”. Delay timer to start the bivalent heat 0:30...
  • Page 30 t l u i t t i t t o i t Yes After selecting the tank T ON temperature Set T OFF 5 °C temperature Yes After selecting the tank T ON temperature T OFF temperature Set Antifreeze 5 °C temperature Yes After selecting the tank T ON temperature...
  • Page 31 t l u i t t i t t o i t Heat-Cool SW 5.19 Force heater 5.20 To turn on Force heater either manually (by default) or automatically. Manual Force defrost 5.21 If auto selection is set, the unit will start defrost operation Manual if long heating hour operate during low outdoor temperature.
  • Page 32 t l u i t t i t t o i t Water temp. for heating ON Compensation curve Input the 4 temperature points X axis: -5 °C, 15 °C (2 on horizontal X Y axis: 55 °C, 35 °C axis, 2 on vertical Y axis).
  • Page 33 t l u i t t i t t o i t Heater ON/OFF Delay time for heater ON Delay time for heater 0:30 min to turn on Heater ON/OFF Water temperature for heater ON Setting of water temperature to turn -4 °C on from water set temperature.
  • Page 34 t l u i t t i t t o i t Water temp. for cooling ON Direct Set temperature for 10 °C Cooling ON • If 2 zone system is selected, temperature set point must input for Zone 2. •...
  • Page 35 t l u i t t i t t o i t Tank heat up time (max) Maximum time for 1:00 heating the tank (in hours and minutes) Tank re-heat temp. Set temperature to -8 °C perform reboil of tank water.
  • Page 36 t l u i t t i t t o i t Pump down Pump down operation To set the pump down operation. Dry concrete Edit to set the temperature of dry concrete. To dry the concrete ( oor, walls, etc.) during construction.
  • Page 37 5.1.6 Main Components DETAIL A Component name 1 PCB 0 Overload Protector (2 pieces) Connector name Single phase RCCB (Main Power) a Pressure Relief Valve Water inlet Single phase RCCB (Backup Heater) b Air Purge Valve Water outlet 3 Heat Exchanger c Magnetic Water Filter Set 4 Water Pressure Gauge d Plug (2 pieces)
  • Page 38: Dimensions

    6. Dimensions Mono Bloc Unit <Top View> <Front View> <Side View> 1284 <Side View> <Back View> Unit: mm...
  • Page 39: Refrigeration And Water Cycle Diagram

    7. Refrigeration and Water Cycle Diagram Outdoo r Side Mono bloc Unit Water Pressure Gauge Liquid Side Expansion (3-Way Valve) Strainer Valve Strainer Shut Shut Valve Valve Water Inlet Filter Water Pump Receiver Water Inlet Ref Pipe Temp. Temp. Sensor Sensor Pipe Temp.
  • Page 40: Standard System (Optional Pcb Not Connected)

    Standard System (Optional PCB not connected) Room Thermo (4 option) Mono Bloc Unit Water System External Internal Thermostat Thermostat Fan Coil Unit Air purge valve (Heating / Cooling) Expansion Vessel (10L) Water External Nothing Inlet Pressure Thermistor Gauge Panel Heater Unit (Heating) OLP ×...
  • Page 41: Block Diagram

    8. Block Diagram WH-MDC05J3E5...
  • Page 42: Wh-Mdc07J3E5 Wh-Mdc09J3E5

    WH-MDC07J3E5 WH-MDC09J3E5...
  • Page 43: Wiring Connection Diagram

    9. Wiring Connection Diagram Water System EXTERNAL COMP. SW HEAT/COOL SWITCH SG SIGNAL SOLAR TEMP. SENSOR DEMAND SIGNAL WATER TEMP. ZONE 1 WATER TEMP. ZONE 2 POOL TEMP. SENSOR BUFFER TANK SENSOR ROOM TEMP. ZONE 1 ROOM TEMP. ZONE 2...
  • Page 44: Refrigerant System

    Refrigerant System 9.2.1 WH-MDC05J3E5...
  • Page 45 9.2.2 WH-MDC07J3E5 WH-MDC09J3E5...
  • Page 46: Electronic Circuit Diagram

    10. Electronic Circuit Diagram 10.1 Water System EXTERNAL COMP. SW HEAT/COOL SWITCH SG SIGNAL SOLAR TEMP. SENSOR DEMAND SIGNAL WATER TEMP. ZONE 1 WATER TEMP. ZONE 2 POOL TEMP. SENSOR BUFFER TANK SENSOR ROOM TEMP. ZONE 1 ROOM TEMP. ZONE 2...
  • Page 47: Refrigerant System

    10.2 Refrigerant System 10.2.1 WH-MDC05J3E5 ELECTRONIC CONTROLLER FG202 FG201 (CAPACITOR) L1-IN ACL201 (GREEN) (GREEN) REACTOR (GRAY) (BLACK) DCP-OUT (WHITE) CN-BLK (BLACK) CAPACITOR NOISE FILTER CIRCUIT CN-DC DCN-IN CIRCUIT (WHITE) (BLACK) ACN201 (WHITE) AC-C CN-WHT (BLUE) DCN-OUT (WHITE) (BLACK) ELECTRONIC CONTROLLER (SUB)
  • Page 48 10.2.2 WH-MDC07J3E5 WH-MDC09J3E5 ELECTRONIC CONTROLLER REACTOR REACTOR (CAPACITOR) FG1 (GREEN) FG2 (GREEN) CN-BLK CN-ACL RELAY (BLACK) DCP-OUT (BLACK) (WHITE) CAPACITOR NOISEFILTER CIRCUIT AC-BLK DCN-IN (BLACK) CIRCUIT (BLACK) CN-ACN (WHITE) AC-C (BLUE) DCN-OUT CN-WHT (BLACK) (WHITE) ELECTRONIC CONTROLLER (SUB) AC-L AC-C DCN2 AC-BLK01 CN-WHT...
  • Page 49: Printed Circuit Board

    11. Printed Circuit Board 11.1 Water System 11.1.1 Main Printed Circuit Board AC2-N2 CN-OLP1 HT1-L3 AC2-L3 CN-PWR CN-PWR2 CN-PWR3 DATA AC1-N AC1-L3 CN-PUMP1 CN-PWR4 CN-FLWSEN CN-TH1 CN-TH3 ACL3 CN-CNT...
  • Page 50 11.1.2 Optional Printed Circuit Board...
  • Page 51: Refrigerant System

    11.2 Refrigerant System 11.2.1 Main Printed Circuit Board CN-FM1 DCN1 CN-WHT AC-L CURRENT TRANSFORMER POWER (CT) TRANSISTOR (IPM) COM3 AC-WHT02 AC-C AC-BLK02 AC-BLK01 CN-HT1 CN-HT2 CN-HOT CN-PSW1 CN-RY1 CN-TANK CN-HPS CN-TH3 CN-EV CN-DIS CN-TH1...
  • Page 52: Installation Instruction

    12. Installation Instruction 12.1 Mono Bloc Unit 12.1.2 Mono Bloc Unit Installation Mono bloc unit will become heavy when filled with 12.1.1 Select the Best Location water. Please install the unit on a strong concrete floor and consider the weight of the unit and water. ...
  • Page 53 12.1.3 Piping Installation WARNING This section is for authorized and licensed electrician / water system installer only. Work behind the front plate secured by screws must only be carried out under supervision of qualified contractor, installation engineer or service person. 12.1.3.1 Typical Piping Installation Temporary connection to be...
  • Page 54 Power Supply Cord Cable Size Isolating Devices Recommended RCD 3 x min 1.5 mm 15/16A 30mA, 2P, type A WH-MDC05J3E5 3 x min 1.5 mm 15/16A 30mA, 2P, type AC 3 x min 2.5 mm 30mA, 2P, type A WH-MDC07J3E5 and WH-MDC09J3E5 3 x min 1.5 mm...
  • Page 55 12.1.4.5 Connecting Requirement For WH-MDC05J3E5  The equipment’s Power Supply 1 complies with IEC/EN 61000-3-2.  The equipment’s Power Supply 1 complies with IEC/EN 61000-3-3 and can be connected to current supply network.  The equipment’s Power Supply 2 complies with IEC/EN 61000-3-2.
  • Page 56 10 Outdoor air sensor cable shall be (2 x min 0.3 mm ) double insulation layer of PVC-sheathed or rubber- sheathed. 11 Tank OLP cable must be (2 x min 0.5 mm ), double insulation layer of PVC-sheathed or rubber-sheathed cable.
  • Page 57 Room thermostat zone 1 and zone 2 cable shall be (4 x min 0.5 mm ), of type designation 60245 IEC 57 or heavier. Mixing valve zone 1 and zone 2 cable shall be (3 x min 1.5 mm ), of type designation 60245 IEC 57 or heavier.
  • Page 58 How to guide optional cables to control board Guide cables through Guide cables through this hole to bushing e this hole to bushing e Bind optional cables with this band How to guide optional cables (view without internal wiring) Terminal screw on PCB Maximum tightening torque cN•m {kgf•cm} 50 {5.1} 120 {12.24}...
  • Page 59 12.1.5.3 Mounting The Remote Controller For exposed type Preparation: Make 2 holes for screws using a driver. Mount the top case. Mount the bottom case to • the wall. Align the claws of the top case and then align the claws of the bottom case.
  • Page 60 For embedded type Preparation: Make 2 holes for screws using a driver. Mount the bottom case to the wall. Mount the top case. • Pass the wire through the hole • Align the claws of the top in the centre of the bottom case. case and then align the claws of the bottom case.
  • Page 61 12.1.6 Installation of Network Adaptor and Base Pan Heater 12.1.6.1 Network Adaptor and Installation (Optional) 1. Open the Cabinet Front Plate and Cabinet Top 3. On the wall near the Mono bloc unit, attach the Plate, then connect the Network Adaptor Cable adaptor by screwing screws through the holes to the CN-CNT connector on the printed circuit in the back cover.
  • Page 62 12.1.7 Charging the Water 12.1.8.2 Check Pressure Relief Valve   Make sure all the piping installations are properly Check for correct operation of Pressure Relief done before carry out below steps. Valve by turning on the lever to become horizontal. ...
  • Page 63 12.1.8.4 Check RCCB 12.1.9.2 Reset Overload Protector Ensure the RCCB set to “ON” condition before check Overload Protector serves the safety purpose to RCCB 2. prevent the water over heating. When the Overload Turn on the power supply to the Mono bloc unit. Protector trip at high water temperature, take below This testing could only be done when power is steps to reset it.
  • Page 64: Variation Of System

    12.2 Variation of system This section introduces variation of various systems using Air-To-Water Heatpump and actual setting method. 12.2.1 Introduce application related to temperature setting. 12.2.1.1 Temperature setting variation for heating 1. Remote Controller Mono bloc Setting of remote controller Installer setting System setup Optional PCB connectivity - No...
  • Page 65 Floor heating Connect floor heating or radiator directly to Mono bloc. Install separate external room thermistor (specified by Panasonic) in the room where floor heating is installed. This is an application that uses external room thermistor. There are 2 kinds of circulation water temperature setting method.
  • Page 66 Connect floor heating to 2 circuits through buffer tank as shown in the figure. Install mixing valves, pumps and thermistors (specified by Panasonic) on both circuits. Install the remote controller in one of the circuit and use it as Room Thermostat.
  • Page 67 Connects pool heat exchanger directly to Mono bloc without using buffer tank. Install pool pump and pool sensor (specified by Panasonic) at secondary side of the pool heat exchanger. Install the remote controller in room where floor heating is installed.
  • Page 68 Built-in pump from Mono bloc served as a pump in zone 1. Install mixing valve, pump and thermistor (specified by Panasonic) on zone 2 circuit. Please be sure to assign high temperature side to zone 1 as temperature of zone 1 cannot be adjusted.
  • Page 69 This is an application that connects the DHW tank to the Mono bloc through 3-way valve before connect the solar water heater to heat up the tank. DHW tank’s temperature is detected by tank thermistor (specified by Panasonic). Solar panel’s temperature is detected by solar thermistor (specified by Panasonic).
  • Page 70 (It must connect to buffer tank especially when selecting Advanced Parallel setting.) WARNING Panasonic is NOT responsible for incorrect or unsafe situation of the boiler system. CAUTION Make sure the boiler and its integration in the system complies with applicable legislation.
  • Page 71: How To Fix External Device

    Solar pump Outdoor air AW-A2W-TSOD (Total cable length shall be 30m or Pool pump sensor less) Pump Tank sensor Please use Panasonic specified part Boiler contact / Defrost signal External control 12.3.1.2 Connection of Optional PCB Tank sensor (CZ-NS4P) Room sensor...
  • Page 72 Solar sensor: PAW-A2W-TSSO  This section explains about the external devices Use for measurement of the solar panel (optional) recommended by Panasonic. Please temperature. always ensure to use the correct external device Insert the sensor into the sensor pocket and during system installation.
  • Page 73   For optional pump. For optional mixing valve. Power supply: AC230V/50Hz, <500W Power supply: AC230V/50Hz (input open/output Recommended part: Yonos 25/6: made by Wilo close) Operating time: 30s~120s Recommended part: 167032: made by Caleffi...
  • Page 74: System Installation

    12.4 System Installation 12.4.1 Remote Controller Outline Name Function Main screen Display information Menu Open/Close main menu Triangle (Move) Select or change item Operate Start/Stop operation Back Back to previous item Quick Menu Open/Close Quick menu Confirm 10:34am, Mon Name Function 12:00am,Mon 1: Function icon...
  • Page 75 First time of power ON (Start of installation) Date & time 12:00am,Mon Initialization 12:00am,Mon Year/Month/Day Hour : Min When power YY/MM/DD/Time is ON, fi rstly setup screen initialization 12 : 00 2015 / 01 / 01 appears Initializing. screen appears (10 sec) Select Confi...
  • Page 76 12.4.2 Installer Setup System setup Optional PCB connectivity Yes/No Only when the selection for Optional PCB is Yes Zone & Sensor 1 Zone system / 2 Zone system Zone settings Heater capacity Capacity select Anti freezing Yes/No Tank connection Yes/No DHW Capacity Variable/Standard Only when the selection for Optional PCB is Yes...
  • Page 77 Operation setup Heat Water temp. for heating ON Compensation curve Compensation curve setup Direct Direct temp. setup Heating OFF Temp. setup Outdoor temp. for heating OFF T for heating ON T for heating setup Heater ON/OFF O/D temp for heater ON setup Heater ON Delay Time T of target temperature for Heater ON T of target temperature for Heater OFF...
  • Page 78 12.4.3 System Setup 12:00am,Mon System setup 1. Optional PCB connectivity Initial setting: No Optional PCB connectivity If function below is necessary, please purchase and install optional PCB. Zone & Sensor Please select Yes after installing optional PCB. Heater capacity • •...
  • Page 79 System setup 12:00am,Mon 6. DHW Capacity Initial setting: Variable Zone & Sensor Variable DHW capacity setting normally run with effi cient boiling which is energy saving Heater capacity heating. But while hot water usage high and tank water temperature low, variable DHW mode Anti freezing will run with fast heat up which heat up the tank with high heating capacity.
  • Page 80 System setup 12:00am,Mon 11. Bivalent connection Initial setting: No Tank heater Set if heat pump linked with boiler operation. Base pan heater Connect the start signal of the boiler in boiler contact terminal (main PCB). Alternative outdoor sensor Set Bivalent connection to YES. After that, please begin setting according to remote controller instruction.
  • Page 81 System setup 12:00am,Mon 13. Solar connection Initial setting: No Alternative outdoor sensor Set when solar water heater is installed. Bivalent connection Setting include items below. External SW 1 Set either buffer tank or DHW tank for connection with solar water heater. 2 Set temperature difference between solar panel thermistor and buffer tank or DHW tank Solar connection thermistor to operate the solar pump.
  • Page 82 System setup 12:00am,Mon 17. External Compressor SW Initial setting: No External Error signal Set when external compressor SW is connected. Demand control SW is connected to external devices to control power consumption, Open Signal will stop SG ready compressor’s operation. (Heating operation etc. are not cancelled). External compressor SW (NOTE) Does not display if there is no Optional PCB.
  • Page 83 12.4.4 Operation Setup Heat 55°C 24. Water temp. for heating ON Initial setting: compensation curve Decide temperature of 4 points as shown Hot water temperature Set target water temperature to operate heating operation. in diagram Compensation curve: Target water temperature change in conjunction with outdoor 35°C ambient temperature change.
  • Page 84 Auto Heat Outdoor temp. rising 30. Outdoor temp. for (Heat to Cool) Initial setting: 15°C Set outdoor temp that switches from heating to cooling by Auto setting. Cool Setting range is 5°C ~ 25°C 15°C Timing of judgement is every 1 hour Heat Outdoor temp.
  • Page 85: Service And Maintenance

    12.5 Service and maintenance Custom menu If forget Password and cannot operate remote controller Setting method of Custom menu Press for 5 sec. Password unlock screen appears, press Confi rm and it shall reset. Custom menu 12:00am,Mon Password will become 0000. Please reset it again. Cool mode (NOTE) Only display when it is locked by password.
  • Page 86: Installation And Servicing Air Conditioner Using R32

    13. Installation and Servicing Air Conditioner using R32 13.1 About R32 Refrigerant For air conditioning refrigerants such as R410A, the refrigerants were collected back in order to prevent their air dissipation, to curbe the global warming impact, in case they were released into the atmosphere. In the “4th Environmental Basic Plan”, 80% reduction of greenhouse gas emissions by 2050 is required, and due to this requirement, further reduction in the emission of high greenhouse effect gas, such as CFCs, is required.
  • Page 87 2. Characteristic of Pressure As shown in Table 2, R32 does not have much difference in vapor pressure at the same refrigerant temperature comparing to R410A, but comparing to R22, it is higher at 1.6 times more. Thus, the same as in case of R410A, it is necessary to do installation and service using high-pressure tools and components.
  • Page 88: Refrigerant Piping Installation • Tools Used In Services

    13.3 Refrigerant piping installation • Tools used in services 13.3.1 Required Tools R32 refrigerant air conditioners use the common parts as R410A air conditioners for two-way valves and three-way valves (diameters of service ports); thus, they maintain commonality in the maintenance of the compressive strength, the size of pipe flaring, and the size of flare nuts as R410A.
  • Page 89 3. Torque wrenches (diameters 1/2, 5/8) Manifold gauges / Charging hoses In order to strengthen the compressive strength, the diameters of wrenches change depending on the flare nut sizes. Torque wrenches Differences in charging hoses Differences in torque wrenches (common R410A) Normal 5.1 MPa 3.4 MPa...
  • Page 90 7. HFC refrigerant_Electric gas leakage tester 9. Refrigerant cylinders R32 refrigerant is often used for other mixed Refrigerant cylinders for R410A are painted in pink, refrigerant (R410A, R404A, R407C etc.). Therefore, and the ones for R32 are painted in other colors that the usage of existing HFC detectors is possible, but in might subject to change according to the international order to detect more accurately, we recommend to...
  • Page 91 11. Tools used for refrigerant piping installations and services Tools for R410A Common with R32 Possibility of usage for R22 ○ ○ Pipe cutters, reamers or scrapers ○ ○ Flare tools (clutch type) ○ ○ Torque wrench (1/4, 3/8) ○ ×...
  • Page 92: New Installation, Relocation, Repairing Of Refrigerant Cycle System The Procedures

    13.4 New installation, Relocation, Repairing of Refrigerant Cycle System The Procedures Relocation Repairing refrigerant cycle Installation Indoor / outdoor units and piping Pump down Refrigerant recovery • Displacing pipes and wires, and displacing indoor / outdoor units Prevention of impurity •...
  • Page 93: Piping Installation Of R32

    13.5 Piping installation of R32 13.5.1 Pipe materials used and flaring Copper pipes are used for refrigerant piping. Pipes Pipe thickness which comply with JIS Regulations need to be used. Room air conditioners which use R410A and R32 O and OL materials Thickness (mm) have higher pressure;...
  • Page 94: Installation, Relocation, And Service

    13.6 Installation, Relocation, and Service 13.6.1 Air purge and gas leak test for new installation (using new refrigerant pipes) using vacuum pump (From the point of view of global environment protection, do not release CFCs into the atmosphere during installation work) 1.
  • Page 95 13.6.2 Process of refrigerant recovery 1. Connect the center charging hose of manifold gauge to the in-let side of recovery device. 2. Connect the valves of the discharge side of recovery device and liquid side of refrigerant cylinder with red hose (charging hose).
  • Page 96 13.6.3 Relocation 1. Removing the air conditioning unit a) Recovery of outdoor unit refrigerant by pumping down Press “forced cooling button” (as a general rule, since 1998 the name of cooling testing button is changed, and this name is unified within the air conditioning industry), and then you are able to start cooling operation in which the room temperature is low, and you can recover the refrigerant from the outdoor unit.
  • Page 97 13.6.6 Re-insertion of refrigerant in service When re-insertion is needed, follow the procedures to ensure the insertion of new refrigerant at correct amount. 1. Attach charging hose (blue) to the service port of the outdoor unit. 2. Attach charging hose (red) to the vacuum pump. Fully open the 2-way and 3-way valves. 3.
  • Page 98: Repairing Of Refrigerant Cycle / Brazing Point

    13.7 Repairing of refrigerant cycle / Brazing point 13.7.1 Preparation for repairing of refrigerant cycle / brazing Brazing which is a technique needed for repairing refrigerant cycle requires advanced technique and experience, and this brazing procedure can only be performed by the workers who completed “Gas Welding Skill Training” regulated by the Occupational Safety and Health Act, and went through the training programs of refrigerant operations.
  • Page 99 2. Cylinder without adjustment valve side gauge pressure is adjusted by the adjuster. Check the both side valves of the torch and open the cylinder valve to check the remaining refrigerant in the cylinder. Caution: Do not attach oil component on the connection port of the adjuster. Especially, use an oxygen cylinder adjuster which is no oil substance type.
  • Page 100 13.7.5 Types of flame Types of flame change based on the proportion of propane and oxygen. [Neutral Flame] Perform brazing with this flame (This is a flame when oxygen and propane are mixed at proper proportion, and has lesser effect on the brazed metals) White core flame 10 ~ 15 mm...
  • Page 101 13.7.7 Selection of brazing material Use BAg brazing material (silver solder) to increase the welding performance. Tensile strength Composition of ingredients (%) Temperature (°C) Characteristics (Reference) Category Standard Brazing Base Number Solidus Liquidus Kgf•cm applications temp material Liquidity is good at low temperature, 49.0 14.5...
  • Page 102 13.7.10 Checking of brazing (insert) points 1. No impurity on the brazing point Gap 0.025 ~ 0.05 mm If dirt or oil is attached on the brazing point, the brazing filler metal does not reach to junction, and Inner diameter ø6.45 it may cause poor welding.
  • Page 103 (Reference) Melting temperature of copper • • • • • • • Approx. 1083°C Maximum temperature obtained in propane and oxygen • • • • • • • Approx. 1083°C The important point is to heat the bonding part uniformly within a short period of time until reaching to the brazing temperature in the following manner.
  • Page 104: Reference> Analysis Method For No Error Code, No Cooling / No Warming

    13.8 <Reference> Analysis method for no error code, no cooling / no warming 13.8.1 Preparation for appropriate diagnosis In order to obtain appropriate operation characteristics, minimum 15 minutes or more operation time [testing operation (rated operation)] is required. 1. Method of rated operation (rated operation) For the models which have two buttons of “emergency operation and forced cooling operation”, press forced cooling button once.
  • Page 105 1. Measuring temperature 1) Indoor unit suction temperature, release temperature, temperature difference, → Measure by thermometer 2) 2-way valve pipe temperature in cooling mode is low temperature (benchmark:5 ~ 10°C), in heating mode is medium temperature (benchmark:25 ~ 35°C). 3) 3-way valve pipe temperature in cooling mode is low temperature (benchmark:7 ~ 15°C) in heating mode is high temperature (benchmark:38 ~ 50°C).
  • Page 106: Operation And Control

    14. Operation and Control 14.1 Basic Function Inverter control, which equipped with a microcomputer in determining the most suitable operating mode as time passes, automatically adjusts output power for maximum comfort always. In order to achieve the suitable operating mode, the microcomputer maintains the set temperature by measuring the temperature of the environment and performing temperature shifting.
  • Page 107 14.1.4 Target Water Temperature Setting 14.1.4.1 Target Water Temperature Control of Standard System (Optional PCB not connected) There are 2 types of temperature control selection which are Compensation and Direct.  Temperature control type selection by installer: Compensation : Wlo, WHi, ODLo, ODHi can be set at installer menu. Direct : Direct Water Temperature Set ...
  • Page 108  Outdoor ambient is updated every 30 minutes when operation ON.  Setting water outlet temperature always follow W or W whenever is higher if outdoor ambient sensor or (LO) (HI) indoor comminication error happen. However, when powerful mode is requested by remote control during heating mode, the higher value of HLo or Whi will be used for A calculation.
  • Page 109 14.1.6 Target Zone Water Temperature Control Purpose:- To control zone mixing and zone pump according to the zone sensor temperature 14.1.6.1 Target Zone 1 water temperature setting control  Start condition Heating zone 1 is ON by remote control or Timer or Auto Mode OR Cooling zone 1 is ON by remote control or Timer or Auto Mode.
  • Page 110 14.1.6.2 Target Zone 2 water temperature setting control  Start condition Heating zone 2 is ON by remote control or Timer or Auto Mode OR Cooling zone 2 is ON by remote control or Timer or Auto Mode.  Cancel condition Heating zone 2 is OFF by remote control or Timer or Auto mode AND Cooling zone 2 is OFF by remote control or Timer or Auto mode.
  • Page 111 14.1.6.3 Zone Temperature Control Contents  During Standard System (Optional PCB not connected) Only 1 zone temperature control is available This zone room temperature is control by either one of the 4 room sensor (Room Th, Int/Ext Room Thermostat, Water temperature) Target Zone Water Temperature is calculated based on selected temperature control type (Compensation or Direct) and selected room sensor.
  • Page 112 14.1.7 Auto Mode Operation COOL MODE Heat To Cool Setting Temp. Cool To Heat Setting Temp. HEAT MODE Outdoor Ambient  Control details: To enable the unit to operate either heat or cool mode automatically, heat to cool set temperature and cool to heat set temperature can be set by control panel.
  • Page 113  Case 2: Tank Heater OFF OR External Heater is select When heat pump OFF due to water thermos & Tank temperature > Tank water set temperature for continuously 20 seconds. OR Tank temperature > Tank set temperature + 1°C for continuously 20 seconds. Tank Thermo ON Case 1: Tank Heater ON (Internal Tank Heater) Tank temperature <...
  • Page 114 Heat pump OFF condition at Tank Mode Tank temperature > tank water set temperature continuously for 20 seconds after heat pump thermos OFF due to water thermo. (Heat pump turn OFF but water pump continue ON and room heater turn ON to achieve tank set temperature) OR Tank temperature >...
  • Page 115 Tank heater control: During heating heat-up interval  Internal tank heater will not function under heating heat-up interval. During tank heat-up interval  Internal tank heater will turn ON after heat pump thermo off to boil tank temperature to tank set temperature.
  • Page 116: Water Pump

    14.1.12 Outdoor Fan Motor Operation Outdoor fan motor is adjusted according to operation condition. It starts when compressor starts operation and it stops 30 seconds after compressor stops operation. Compressor: Fan Speed Outdoor Fan: 30 sec 14.2 Water Pump 14.2.1 Water Pump Control ...
  • Page 117 1) P-Q graph for different pump HEX duty P-Q (WH-ADC0309J3E5) Max Duty: C5 Duty: 6E Min Duty: 50 Water Flow Rate, Q (L/min) 14.2.2 Zone Water Pump Control Purpose:  Water pump install at each zone to circulate the water inside each zone during buffer tank connection selected “YES”...
  • Page 118  Pool water pump stop condition Pool zone: Zone room request OFF OR Pool function is cancel * Zone 1 & Zone 2 water pump need to turn OFF when antifreeze deice pump stop control activate and turn ON back after the antifreeze deice pump stop control end under setting of "NO" buffer tank connection. Zone Pump Prohibit ON control: ...
  • Page 119: Indoor Unit Safety

    14.3 Indoor Unit Safety 14.3.1 Indoor Unit Safety Control When water pump is ON, the system will start checking flow switch status (ON/OFF). If the flow switch ON for 10 seconds, the system will check on the water inlet temperature for 10 seconds. If the water inlet temperature not exceeds 80°C, the water pump shall be continuously running with normal mode.
  • Page 120: Indoor Back-Up Heater Control

    14.6 Indoor Back-Up Heater Control 14.6.1 Indoor Electric Heater Control Normal Heating Mode Heater On condition: a. Heater switch is ON b. After Heatpump thermo ON for Remote Control Set Delay Time mins c. After water pump operate [3] mins d.
  • Page 121: Tank Heater Control

    14.7 Tank Heater Control 14.7.1 Tank Heater Remote Control Setting Tank heater selection: External: - Booster Heater use to heat up tank when select external Internal: - Backup Heater use to heat up tank when select internal * When select External Tank Heater, Heater Delay ON Timer need to set. (range 20 min ~ 3 hrs) Tank Heater ON/OFF selection by user.
  • Page 122: Base Pan Heater Control (Optional)

    Tank Temp. 65°C Tank Water Set Temp. Backup Heater Operation Heat Pump Operation Time 14.8 Base Pan Heater Control (Optional)  To enable the base pan heater function, control panel initial setting has to be manually adjusted by activating Base Pan Heater menu. ...
  • Page 123: Force Heater Mode

    14.9 Force Heater Mode Purpose of Force Heater Mode As a backup heat source when heat pump error. Force heater Mode control backup heater to heat up the room circuit, and turn ON back up heater or booster heater to boil up tank water base on the tank heater selection (internal or external) Force Heater Control start condition: Force heater request ON by user during error OR auto turn ON by remote controller during error AND (Force...
  • Page 124: Powerful Operation

    Backup Heater Stop condition:  Force mode off OR  Operation off OR  When water outlet temperature > water set temperature + Remote Control Heater OFF Setting for continuous 15 secs OR * ON/OFF follow normal heater sequence. Tank side (Tank mode): ...
  • Page 125: Quiet Operation

     Start condition Powerful function is select by remote control.  End Condition OFF/ON button is pressed. Powerful function is OFF by remote control. 14.11 Quiet Operation Quiet mode is use to reduce the noise of outdoor unit by reducing the frequency or fan speed. Quiet level There are 3 level (Level 1, Level 2, Level 3) to set by quick menu function on remote control.
  • Page 126: Outdoor Ambient Thermo Off Control

    14.13 Outdoor Ambient Thermo OFF Control  Purpose Stop provides heating to room side during high outdoor ambient condition. Outdoor thermo off set temperature +3°C Outdoor thermo off set temperature +1°C  Control content Heating outdoor ambient thermos OFF control only applicable when heat pump operate in heat mode. (This control will not activate when running in tank side) Heat pump and water pump will turn OFF when outdoor ambient is higher than outdoor thermo OFF set temperature.
  • Page 127: Force Dhw Mode

    14.16 SMART DHW mode Panasonic All In One model provide the option to choose STANDARD DHW Mode or SMART DHW Mode for Tank Heat Up according to requirement. SMART DHW mode comparatively consume lower tank heat up power but longer re-heat time than STANDARD DHW Mode.
  • Page 128: Dhw Capacity Setting

    14.17 DHW Capacity Setting DHW Capacity is heat pump heating capacity output control during tank boiling operation. There are two DHW capacity setting (VARIABLE & STANDARD) which can be set in remote control. VARIABLE DHW Capacity:  Heat pump operate with efficient (Low) Capacity to boil tank temperature during re-heat process. And heat pump regulated to operate with high capacity to boil tank temperature when tank temperature drop below 25°C.
  • Page 129: Solar Operation (Optional)

    14.18.1 Zone Anti-Freeze Control  If buffer tank selection is “NO” and Anti- Freeze function select “NO” from remote control, this control cannot activate. Start condition:  After [5] min from previous Zone pump off. AND  Outdoor air temp < [3] °C OR Outdoor sensor is abnormal. AND ...
  • Page 130  Solar remote control setting Solar Setting can only be set when the optional PCB connection is select "YES" By remote controller, Setting as below list can be set for solar function operation (Installer Menu) Solar Function ("YES" or "NO) Tank Connection Direction ("DHW TANK"...
  • Page 131: Boiler Bivalent Control

    14.20 Boiler Bivalent Control  Boiler is an additional or alternative heat source to heat up the room when necessary.  Purpose of this control is to turn ON and turn OFF the Boiler output signal when boiler heating capacity needed in the system.
  • Page 132 Control detail: During operation ON at Heat Mode Boiler signal turns ON when  Outdoor ambient < Outdoor Ambient Set AND  Buffer tank temperature < Target Buffer Tank Temperature + [START_TEMP] for [START_TIMER]  Heat pump operate at room side AND Connection of Boiler to Heating Select "YES"...
  • Page 133: External Room Thermostat Control (Optional)

    14.21 External Room Thermostat Control (Optional) Purpose: Better room temperature control to fulfill different temperature request by external room thermostat. Recommended external room thermostat: Maker Characteristic Siemen (REV200) Touch panel Siemen (RAA20) Analog Connection of external room thermostat: Wire Connection and thermo characteristic of Siemen REV200: Setting L/L1 (H) Heat Thermo...
  • Page 134: Three Ways Valve Control

    14.22 Three Ways Valve Control Purpose: - 3 ways valve is used to change flow direction of hot water from heat pump between heating side and tank side. Control contents: 3 ways valve switch Off: During 3 ways valve switch Off time, the hot water will provide heat capacity to heating side. 3 ways valve switch On: During 3 ways valve switch On time, the hot water will provide heat capacity to tank side.
  • Page 135: External Off/On Control

    14.24 External OFF/ON Control  Communication circuit between indoor unit and external controller is as per below. External Controller mico Panasonic CN-THERMO  Maximum length of communication cable is 50 meter.  Control content: External Control Switch Control Panel OFF/ON...
  • Page 136: External Compressor Switch (Optional Pcb)

    14.25 External Compressor Switch (Optional PCB) External compressor switch port can have two purpose of control as below:  Heat source ON/OFF function (Dip switch Pin 3 on PCB "OFF")  Heater ON/OFF function (Dip switch Pin 3 on PCB "ON") ...
  • Page 137: Heat/Cool Switch (Optional Pcb)

    14.26 Heat/Cool Switch (Optional PCB) Purpose:  User can switch the running mode from heat to cool or cool to heat through external installed Heat/Cool switch. This kind of heat / cool switch may built in inside the field supply room remocon as well. Control contents: ...
  • Page 138 Control contents: If SG control on remote control = "Yes", then following control only activate by digital input.  While Digital input is " 00 " (Normal operation) Normal operation. Once detect '00' system will operate back to normal condition. (All the target set temperature for heating side and DHW side will return back to previous set temperature when digital signal change from "10' or"11"...
  • Page 139: Demand Control (Optional Pcb)

    If Buffer selection is “NO” Room side New Target Zone Water Temperature = Current Target Zone Water Temperature * Remote Control Setting (*Capacity 2) % (Zone 1 and Zone 2 will change according to it's own target zone water temperature.) (Max regulation depend on the temperature control type select) DHW Tank side New Tank Set Temperature = Tank Set Temperature * Remote Control setting for DHW ("Capacity 2) %...
  • Page 140: Dry Concrete

    14.30 Dry Concrete  Purpose: Provide heat to floor heating panel and dry the wet concrete during installation.  Setting condition: Dry concrete parameter can be set through remote control under system setup. Parameters are possible to set up to 99 days with different target set temperature. ...
  • Page 141: Protection Control (Wh-Mdc05J3E5)

    15. Protection Control (WH-MDC05J3E5) 15.1 Protection Control for All Operations 15.1.1 Time Delay Safety Control The compressor will not start for three minutes after stop of operation. 15.1.2 30 Seconds Forced Operation Once the compressor starts operation, it will not stop its operation for 30 seconds.
  • Page 142 15.1.5 High Pressure Sensor Control  Purpose: - To protect the system operation.  Detection period: - After compressor on for 1 minute.  Detection conditions: - When abnormal high voltage detection, 5 V or when open circuit detection 0V for 5 seconds continuously. ...
  • Page 143: Protection Control For Heating Operation

    15.2 Protection Control for Heating Operation 15.2.1 Outdoor Air Temperature Control The maximum current value is regulated when the outdoor air temperature rises above 14°C in order to avoid compressor overloading. 15.2.2 Deice Operation When outdoor pipe temperature and outdoor air temperature is low, deice operation start where outdoor fan motor stop.
  • Page 144: Protection Control For Cooling Operation

    15.3 Protection Control for Cooling Operation 15.3.1 Outdoor Air Temperature Control  The Compressor operating frequency is regulated in accordance to the outdoor air temperature as shown in the diagram below.  This control will begin 1 minute after the compressor starts. ...
  • Page 145: Protection Control (Wh-Mdc07J3E5 Wh-Mdc09J3E5)

    16. Protection Control (WH-MDC07J3E5 WH-MDC09J3E5) 16.1 Protection Control for All Operations 16.1.1 Time Delay Safety Control The compressor will not start for three minutes after stop of operation. 16.1.2 30 Seconds Forced Operation Once the compressor starts operation, it will not stop its operation for 30 seconds. However, it can be stopped using control panel at indoor unit.
  • Page 146 16.1.5 High Pressure Sensor Control  Purpose: - To protect the system operation.  Detection period: - After compressor on for 1 minute.  Detection conditions: - When abnormal high voltage detection, 5 V or when open circuit detection 0V for 5 seconds continuously. ...
  • Page 147: Protection Control For Heating Operation

    16.2 Protection Control for Heating Operation 16.2.1 Outdoor Air Temperature Control The maximum current value is regulated when the outdoor air temperature rises above 14°C in order to avoid compressor overloading. 16.2.2 Deice Operation When outdoor pipe temperature and outdoor air temperature is low, deice operation start where outdoor fan motor stop.
  • Page 148: Protection Control For Cooling Operation

    16.3 Protection Control for Cooling Operation 16.3.1 Outdoor Air Temperature Control  The Compressor operating frequency is regulated in accordance to the outdoor air temperature as shown in the diagram below.  This control will begin 1 minute after the compressor starts. ...
  • Page 149: Servicing Mode

    17. Servicing Mode 17.1 Expansion Vessel Pre 17.2 Maintenance Pressure Checking  In order to ensure optimal performance of the unit, seasonal inspections on the unit, functional check [Upper limit water volume of the system] of RCCB, field wiring and piping have to be The Mono bloc unit has a build-in Expansion Vessel carried out at regular intervals.
  • Page 150: Pump Down Procedures

    17.3 Pump Down Procedures Refer below steps for proper pump down procedure. Press Press SW & scroll to “Pump down” [Screen 4]...
  • Page 151: How To Adjust Pump Speed

    17.4 How To Adjust Pump Speed 11 : 00am, M on Press & scroll to “Installer setup” [Screen 4] - Press SW to select & confirm maximum duty. (Range: 0 x40~0xFF) [Screen 5] - Range (0.1~99.9)L/min [Screen 6] Press SW to select & confirm operation...
  • Page 152: How To Adjust Pump Speed

    17.5 How To Adjust Pump Speed 11 : 00am, M on Press & scroll to “Installer setup” [Screen 4] - Press SW to select & confirm maximum duty. (Range: 0 x40~0xFF) [Screen 5] - Range (0.1~99.9)L/min [Screen 6] Press SW to select & confirm operation NOTE: 1.
  • Page 153: How To Unlock Cool Mode

    17.6 How To Unlock Cool Mode Operation must be OFF Press ( ) SW’s continuously for 5secs Display latest status retrieved from EEPROM...
  • Page 154: Eeprom Factory Default Data Setup Procedure

    17.7 EEPROM Factory Default Data Setup Procedure - EEPROM default data setup is only possible during initialization process. - Press simultaneously for 5secs continuously, initialization process will stop & EEPROM default data setup process will start. During EEPROM default data setup process, display should be as shown below. 0.2s Later 0.2s...
  • Page 155: Dry Concrete Setup

    17.8 Dry Concrete Setup 11 : 00am, M on Press & scroll to “Installer setup” [Screen 4] [Screen 5] [Screen 6] Once ‘ON’ is confirm, stage 1 setup will start Every day stage will increment with its respective setup Next Page...
  • Page 156 - Press button to select no. of stages. - Press to store latest status. - Press button, display will return to [Screen 6]. - If suppose to select 10 stages, then setup will start from stage 1/10. - Press button to select set temperature. - Press button to store latest status.
  • Page 157: Maintenance Guide

    18. Maintenance Guide In order to ensure safety and optimal performance of the unit, seasonal inspections on the unit, functional check of RCCB/ELCB, field wiring and piping have to be carried out at regular intervals. This maintenance should be carried out by authorized dealer.
  • Page 158: Maintenance Menu

    Reset overload protector Overload Protector a serves the safety purpose to prevent the water over heating. When the Overload Protector a trip at high water temperature, take below steps to reset it. a. Take out the cover. b. Use a test pen to push the centre button gently in order to reset the Overload Protector. c.
  • Page 159 18.1.3 Custom menu Setting method of Custom menu Custom menu 17:26, Wed Cool mode Back-up heater Reset energy monitor Select Confirm Please press for 10 sec. Items that can be set  Cool mode (Set With/Without Cooling function) Default is without (CAUTION) As with/without Cool mode may affect electricity application, please be careful and do not simply...
  • Page 160: Troubleshooting Guide

    19. Troubleshooting Guide 19.1 Refrigeration Cycle System In order to diagnose malfunctions, make sure that there are no electrical problems before inspecting the refrigeration cycle. Such problems include insufficient insulation, problem with the power source, malfunction of a compressor and a fan.
  • Page 161: Relationship Between The Condition Of The Air-To-Water Heatpump Indoor And Outdoor Units And Pressure And Electric Current

    19.2 Relationship between the Condition of the Air-to-Water Heatpump Indoor and Outdoor Units and Pressure and Electric Current Heating Mode Cooling Mode Condition of the Air-to-Water Heatpump Low Pressure High Pressure Electric current Low Pressure High Pressure Electric current indoor and during operation during operation outdoor units...
  • Page 162: Breakdown Self Diagnosis Function

    19.3 Breakdown Self Diagnosis Function 19.3.1 Self Diagnosis Function (Three Digits Alphanumeric Code)  When abnormality occur during operation, the system will stop operation, and OFF/ON control panel LED will blink and error code will display on the control panel. ...
  • Page 163 Press button and select “System Check” Press SW to select [Screen 4] “Error history” Display last 4 error retrieved from EEPROM...
  • Page 164: Error Codes Table

    19.4 Error Codes Table Diagnosis display Abnormality/Protection control Abnormality judgement Primary location to verify No abnormality detected — —  Indoor/outdoor connection wire  Indoor/outdoor PCB Indoor/Outdoor capacity unmatched 90s after power supply  Specification and combination table in catalogue ...
  • Page 165 Diagnosis display Abnormality/Protection control Abnormality judgement Primary location to verify  Compressor tank temperature sensor  Clogged expansion valve or strainer Outdoor compressor overheating 4 times occurrence within 30  Insufficient refrigerant protection minutes  Outdoor PCB  Compressor  Improper heat exchange IPM (power transistor) overheating 3 times occurrence within 30 ...
  • Page 166: Self-Diagnosis Method

    19.5 Self-diagnosis Method 19.5.1 Connection Capability Rank Abnormality (H12) Malfunction Decision Conditions: During startup operation of cooling and heating, the capability rank of indoor checked by the outdoor is used to determine connection capability rank abnormality. Malfunction Caused: Wrong model interconnected. Wrong indoor unit or outdoor unit PCB (main) used.
  • Page 167 19.5.2 Compressor Tank Temperature Sensor Abnormality (H15) Malfunction Decision Conditions: During startup and operation of cooling and heating, the temperatures detected by the compressor tank temperature sensor are used to determine sensor error. Malfunction Caused: Faulty connector connection. Faulty sensor. Faulty outdoor unit PCB (main).
  • Page 168 19.5.3 Water Pump Abnormality (H20) Malfunction Decision Conditions: During startup and operation of cooling and heating, the rotation speed detected by the IPM of water pump motor during water pump operation is used to determine abnormal water pump (feedback of rotation > 6,000rpm or < 1,000rpm).
  • Page 169 19.5.4 Indoor Refrigerant Liquid Temperature Sensor Abnormality (H23) Malfunction Decision Conditions: During startup and operation of cooling and heating, the temperatures detected by the indoor refrigerant liquid temperature sensor are used to determine sensor error. Malfunction Caused: Faulty connector connection. Faulty sensor.
  • Page 170 19.5.5 Service Valve Error (H27) Malfunction Decision Conditions: During cooling operation, when:- [a] Indoor refrigerant pipe temperature at compressor startup - present indoor refrigerant pipe temperature < 2°C [b] Present high pressure - high pressure at compressor startup < 5kg/cm **Judgment only for first time cooling operation and not during pump down operation.
  • Page 171 19.5.6 Abnormal Solar Sensor (H28) Malfunction Caused: Faulty connector connection. Faulty solar sensor. Faulty indoor sub PCB. Abnormality Judgment: Continue for 5 seconds. For safety reason and to prevent Abnormal solar sensor component breakdown, always switch Caution off the power before remove and connect the component.
  • Page 172 19.5.7 Abnormal Swimming Pool Sensor (H31) Malfunction Caused: Faulty connector connection. Faulty swimming pool sensor. Faulty indoor sub PCB. Abnormality Judgment: Continue for 5 seconds. For safety reason and to prevent Abnormal swimming pool sensor component breakdown, always switch Caution off the power before remove and connect the component.
  • Page 173 19.5.8 Abnormal Buffer Tank Sensor (H36) Malfunction Caused: Faulty connector connection. Faulty buffer tank sensor. Faulty indoor sub PCB. Abnormality Judgment: Continue for 5 seconds. For safety reason and to prevent Abnormal buffer tank sensor component breakdown, always switch Caution off the power before remove and connect the component.
  • Page 174 Brand code not match component breakdown, always switch Caution off the power before remove and connect the component. ● Use only Panasonic units. Check the brand of indoor and outdoor unit both Panasonic? ● Change to Panasonic unit. Change PCB outdoor...
  • Page 175 19.5.10 Compressor Low Pressure Protection (H42) Malfunction Decision Conditions: During operation of heating and after 5 minutes compressor ON, when outdoor pipe temperature below -29°C or above 26°C is detected by the outdoor pipe temperature sensor. Malfunction Caused: Dust accumulation on the outdoor unit heat exchanger. Air short circuit at outdoor unit.
  • Page 176 19.5.11 Abnormal Zone 1 Sensor (H43) Malfunction Caused: Faulty connector connection. Faulty buffer tank sensor. Faulty indoor sub PCB. Abnormality Judgment: Continue for 5 seconds. For safety reason and to prevent Abnormal zone 1 sensor component breakdown, always switch Caution off the power before remove and connect the component.
  • Page 177 19.5.12 Abnormal Zone 2 Sensor (H44) Malfunction Caused: Faulty connector connection. Faulty buffer tank sensor. Faulty indoor sub PCB. Abnormality Judgment: Continue for 5 seconds. For safety reason and to prevent Abnormal zone 2 sensor component breakdown, always switch Caution off the power before remove and connect the component.
  • Page 178 19.5.13 Water Flow Switch Abnormality (H62) Malfunction Decision Conditions: During operation of cooling and heating, the water flow detected by the indoor water flow switch is used to determine water flow error. Malfunction Caused: Faulty water pump. Water leak in system. Faulty connector connection.
  • Page 179 19.5.14 Outdoor High Pressure Abnormality (H64) Malfunction Decision Conditions: During operation of cooling and heating, when the outdoor high pressure sensor output signal is 0 Vdc or 5 Vdc. Malfunction Caused: Faulty connector connection. Faulty sensor. Faulty outdoor unit PCB (main). Abnormality Judgment: Continue 4 times in 20 minutes.
  • Page 180 19.5.15 Deice Circulation Error (H65) Malfunction Decision Conditions: During startup and operation of deice (mode 2), the water flow (> 10l/min) detected by the water flow switch is used to determine deice circulation error. Malfunction Caused: Water flow in air-to-water heatpump indoor unit circuitry. Faulty indoor unit water flow switch.
  • Page 181 19.5.16 Abnoraml External Thermistor 1 (H67) Malfunction Caused: Faulty connector connection. Faulty room temperature zone 1 sensor. Faulty indoor sub PCB. Abnormality Judgment: Continue for 5 seconds. For safety reason and to prevent Abnormal external thermistor 1 component breakdown, always switch Caution off the power before remove and connect the component.
  • Page 182 19.5.17 Abnoraml External Thermistor 2 (H68) Malfunction Caused: Faulty connector connection. Faulty room temperature zone 2 sensor. Faulty indoor sub PCB. Abnormality Judgment: Continue for 5 seconds. For safety reason and to prevent Abnormal external thermistor 2 component breakdown, always switch Caution off the power before remove and connect the component.
  • Page 183 19.5.18 Indoor Backup Heater OLP Abnormality (H70) Malfunction Decision Conditions: During operation of indoor backup heater, when no power supplies to indoor backup heater or OLP open circuit. Malfunction Caused: Faulty power supply connector connection. Faulty connector connection. Faulty indoor backup heater overload protector (OLP). Faulty indoor unit PCB (main).
  • Page 184 19.5.19 Tank Temperature Sensor Abnormality (H72) Malfunction Decision Conditions: When tank connection is set to ON, the temperatures detected by the tank temperature sensor are used to determine sensor error. Malfunction Caused: Faulty connector connection. Faulty sensor. Faulty indoor unit PCB (main). Abnormality Judgment: Continue for 5 seconds.
  • Page 185 19.5.20 PCB Communication Error (H74) Malfunction Decision Conditions: When External PCB connection is select “YES” and no communication with External PCB micon for 10 seconds and above. Malfunction Caused: Faulty connector connection. Faulty indoor PCB. Faulty indoor sub PCB. Abnormality Judgment: After 1 minute operation started.
  • Page 186 19.5.21 Indoor-Control Panel Communication Abnormality (H76) Malfunction Decision Conditions: During standby and operation of cooling and heating, indoor-control panel error occur. Malfunction Caused: Faulty connector connection. Faulty control panel. Faulty indoor unit PCB (main).
  • Page 187 19.5.22 Indoor/Outdoor Abnormal Communication (H90) Malfunction Decision Conditions: During operation of cooling and heating, the data received from outdoor unit in indoor unit signal transmission is checked whether it is normal. Malfunction Caused: Faulty outdoor unit PCB (main). Faulty indoor unit PCB (main). Indoor-outdoor signal transmission error due to wrong wiring.
  • Page 188 19.5.23 Tank Booster Heater OLP Abnormality (H91) Malfunction Decision Conditions: During operation of tank booster heater, and tank booster heater OLP open circuit. Malfunction Caused: Faulty connector connection. Faulty tank booster heater overload protector (OLP). Faulty indoor unit PCB (main). Abnormality Judgment: Continue for 60 seconds.
  • Page 189 19.5.24 Unspecified Voltage between Indoor and Outdoor (H95) Malfunction Decision Conditions: The supply power is detected for its requirement by the indoor/outdoor transmission. Malfunction Caused: Insufficient power supply. Faulty outdoor unit PCB (noise filter/main).
  • Page 190 19.5.25 Outdoor High Pressure Protection (H98) Malfunction Decision Conditions: During operation of heating, when pressure 4.0 MPa and above is detected by outdoor high pressure sensor. Malfunction Caused: Faulty water pump. Insufficient water flow rate in system. Water leak in system. 2/3 way closed.
  • Page 191 19.5.26 Indoor Freeze-up Protection (H99) Malfunction Decision Conditions: During anti-freezing control in cooling operation, when the indoor refrigerant liquid temperature < 0°C. Malfunction Caused: Faulty water pump. Insufficient water flow rate in system. Water leak in system. 2 way valve partially closed. Clogged expansion valve or strainer.
  • Page 192 19.5.27 Outdoor High Pressure Switch Activate (F12) Malfunction Decision Conditions: During operation of cooling and heating, when pressure 4.5 MPa and above is detected by outdoor high pressure switch. Malfunction Caused: Dust accumulation on the outdoor unit heat exchanger. Air short circuit at outdoor unit. Faulty water pump.
  • Page 193 19.5.28 Compressor Rotation Failure (F14) Malfunction Decision Conditions: A compressor rotation failure is detected by checking the compressor running condition through the position detection circuit. Malfunction Caused: Compressor terminal disconnect. Faulty outdoor unit PCB (main). Faulty compressor. Abnormality Judgment: Continue 4 times in 20 minutes.
  • Page 194 19.5.29 Outdoor Fan Motor (DC Motor) Mechanism Locked (F15) Malfunction Decision Conditions: The rotation speed detected by the Hall IC of the fan motor during fan motor operation is used to determine abnormal fan motor (feedback of rotation > 2550 rpm or < 50 rpm). Malfunction Caused: Operation stop due to short circuit inside the fan motor winding.
  • Page 195 19.5.30 Input Over Current Detection (F16) Malfunction Decision Conditions: During operation of cooling and heating, when outdoor current above 24.1 A (Heating) and 16.4 A (Cooling) [UD07FE5)] and 28.1 A (Heating) and 18.1 A (Cooling) [UD09FE5)] is detected by the current transformer (CT) in the outdoor unit PCB.
  • Page 196 19.5.31 Compressor Overheating (F20) Malfunction Decision Conditions: During operation of cooling and heating, when temperature above 112°C is detected by the compressor tank temperature sensor. Malfunction Caused: Faulty compressor tank temperature sensor. 2/3 way valve closed. Refrigerant shortage (refrigerant leakage). Clogged expansion valve or strainer.
  • Page 197 19.5.32 IPM Overheating (F22) Malfunction Decision Conditions: During operation of cooling and heating, when temperature 95°C is detected by the outdoor IPM temperature sensor. Malfunction Caused: Faulty outdoor unit fan motor. Faulty outdoor unit PCB (main). Abnormality Judgment: Continue 3 times in 30 minutes.
  • Page 198 19.5.33 Output Over Current Detection (F23) Malfunction Decision Conditions: During operation of cooling and heating, when outdoor DC current is above 34 A is detected by the IPM DC Peak sensing circuitry in the outdoor unit PCB (main). Malfunction Caused: Faulty outdoor unit PCB (main).
  • Page 199 19.5.34 Refrigeration Cycle Abnormality (F24) (WH-UD03HE5-1 and WH-UD05HE-1) Malfunction Decision Conditions: During operation of cooling and heating, compressor frequency > Frated. During operation of cooling and heating, running current: 0.65 A < I < 1.65 A. During operation of cooling, water inlet temperature - indoor refrigerant liquid temperature < 5°C. During operation of heating, indoor refrigerant liquid temperature - water inlet temperature <...
  • Page 200 19.5.35 Refrigeration Cycle Abnormality (F24) (WH-UD07HE5-1 and WH-UD09HE-1) Malfunction Decision Conditions: During operation running (heating / cooling) for more than 10 minutes expect deice, pumpdown and test mode. During heating / cooling, water outlet and water inlet difference is less than 1°C. During heating / cooling, high pressure <...
  • Page 201 19.5.36 Four Way Valve Abnormality (F25) Malfunction Decision Conditions: During heating operation, when the indoor pipe temperature of thermostat ON indoor unit < 0°C. During cooling operation, when the indoor pipe temperature of thermostat ON indoor unit > 45°C. Malfunction Caused: Faulty sensor.
  • Page 202 19.5.37 Outdoor High Pressure Switch Abnormal (F27) Malfunction Decision Conditions: During compressor stop, and outdoor high pressure switch is remain opened. Malfunction Caused: Faulty connector connection. Faulty switch. Faulty outdoor unit PCB (main). Abnormality Judgment: Continue for 1 minute.
  • Page 203 19.5.38 Low Discharge Superheat (F29) Malfunction Decision Conditions: During startup and operation of cooling and heating, the temperatures detected by the outdoor pipe temperature sensor are used to determine sensor error. Malfunction Caused: Faulty connector connection. Faulty sensor. Faulty outdoor unit PCB (main). Faulty High Pressure Switch Refrigerant shortage (refrigerant leakage).
  • Page 204 19.5.39 Indoor Water Outlet Temperature Sensor 2 Abnormality (F30) Malfunction Decision Conditions: During startup and operation of cooling and heating, the temperatures detected by the indoor water outlet temperature sensor 2 are used to determine sensor error. Malfunction Caused: Faulty connector connection. Faulty sensor.
  • Page 205 19.5.40 Outdoor Air Temperature Sensor Abnormality (F36) Malfunction Decision Conditions: During startup and operation of cooling and heating, the temperatures detected by the outdoor air temperature sensor are used to determine sensor error. Malfunction Caused: Faulty connector connection. Faulty sensor. Faulty outdoor unit PCB (main).
  • Page 206 19.5.41 Indoor Water Inlet Temperature Sensor Abnormality (F37) Malfunction Decision Conditions: During startup and operation of cooling and heating, the temperatures detected by the indoor water inlet temperature sensor are used to determine sensor error. Malfunction Caused: Faulty connector connection. Faulty sensor.
  • Page 207 19.5.42 Outdoor Discharge Pipe Temperature Sensor Abnormality (F40) Malfunction Decision Conditions: During startup and operation of cooling and heating, the temperatures detected by the outdoor discharge pipe temperature sensor are used to determine sensor error. Malfunction Caused: Faulty connector connection. Faulty sensor.
  • Page 208 19.5.43 Power Factor Correction (PFC) Abnormality (F41) Malfunction Decision Conditions: During operation of cooling and heating, when the PFC protection circuitry in the outdoor unit PCB (main) senses abnormal high DC voltage level. Malfunction Caused: Power supply surge. Compressor windings not uniform. Faulty outdoor unit PCB (main).
  • Page 209 19.5.44 Outdoor Pipe Temperature Sensor Abnormality (F42) Malfunction Decision Conditions: During startup and operation of cooling and heating, the temperatures detected by the outdoor pipe temperature sensor are used to determine sensor error. Malfunction Caused: Faulty connector connection. Faulty sensor. Faulty outdoor unit PCB (main).
  • Page 210 19.5.45 Outdoor Defrost Temperature Sensor Abnormality (F43) Malfunction Decision Conditions: During startup and operation of cooling and heating, the temperatures detected by the outdoor defrost temperature sensor are used to determine sensor error. Malfunction Caused: Faulty connector connection. Faulty sensor. Faulty outdoor unit PCB (main).
  • Page 211 19.5.46 Indoor Water Outlet Temperature Sensor Abnormality (F45) Malfunction Decision Conditions: During startup and operation of cooling and heating, the temperatures detected by the indoor water outlet temperature sensor are used to determine sensor errors. Malfunction Caused: Faulty connector connection. Faulty sensor.
  • Page 212 19.5.47 Outdoor Current Transformer Open Circuit (F46) Malfunction Decision Conditions: A current transformer (CT) open circuit is detected by checking the compressor running frequency ( rated frequency) and CT detected input current (< 0.65 A) for continuously 20 seconds. Malfunction Caused: CT defective.
  • Page 213 19.5.48 Cooling High Pressure Overload Protection (F95) Malfunction Decision Conditions: During operation of cooling, when pressure 4.0 MPa and above is detected by outdoor high pressure sensor. Malfunction Caused: Dust accumulation in the outdoor unit heat exchanger. Air short circuit at outdoor unit. 2 way valve closed.
  • Page 214: Disassembly And Assembly Instructions

    20. Disassembly and Assembly Instructions WARNING High Voltage are generated in the electrical parts area by the capacitor. Ensure that the capacitor has discharged sufficiently before proceeding with repair work. Failure to heed this caution may result in electric shocks. WARNING Be sure to switch off all the power supply before performing each of the below action.
  • Page 215: To Remove The Cabinet Rear Plate

    20.3 To Remove The Cabinet Rear Plate 4. Slide the cabinet rear plate downward to release the pawls. 3. Remove 3 mounting screws. Then pull it out to remove it. 1. Remove 4 mounting screws. 2. Remove 5 mounting screws. 20.4 To Remove Pressure Gauge 2.
  • Page 216: To Remove Rccb

    20.5 To Remove RCCB 2. Disconnect 2 lead wires (Black and White) 1. Disconnect 2 lead wires (Black and White) 3. Remove screws to remove RCCB. RCCB 20.6 To Remove Reactor 1. Remove 2 screws to remove Reactor. Reac tor...
  • Page 217: To Remove Water System Electronic Controller Board

    20.7 To Remove Water System Electronic Controller Board CN-OLP1 1. Remove all the connectors from the Electronic Controller. CN-HT CN-PUMP1 CN-FLWSEN CN-TH1 CN-TH3 Electronic Controller Board 2. Disconnect all lead wires of G01 (Green), G02 (Green), G03 (Green) AC2-N2 (White), HT1-L3 (Red) & AC2-L3 (Black), Data (Red), AC1-N (White) AC1-L3 (Black) and ACL3 (Black)
  • Page 218: To Remove Refrigerant Side Control Board Complete

    20.8 To Remove Refrigerant Side Control Board Complete 3. Remove 2 screws to remove the Control Board Complete 1. Remove all lead wire FG1 (Green) AC-L (Grey), DCP (Red) , DCN2 (Black), DCN (Black), AC-C (Blue), AC-BLK01 (Black), AC-BLK02 (Black), COM3 (Red) , AC-WHT02 (White) and U (Red) V (Blue) W (Yellow) conne ctor.
  • Page 219: To Remove Pressure Relief Valve And Air Purge Valve

    20.9 To Remove Pressure Relief Valve and Air Purge Valve During reinstall Air Purge Valve. Air Purge Valve Make sure plug is fully close in clockwise direction. 1. Turn the Air Purge Valve anti-clockwise, then relea se Packing the retaining ring and pull out the air purge valve .
  • Page 220: To Remove Water Pump

    20.11 To Remove Water Pump 1. Disconnect CN-PUMP1 connector from Electronic Controller Board. 2. Remo ve 2 screw from Pump Bracket. If pump is repla ce, please follow below instruction. Hose Band Make sure bag opening facing down (To prevent water accumulate) 1.
  • Page 221: To Remove Heater

    20.12 To Remove Heater BLUE 2. Remove terminal cover by relea sing BLUE BLACK 1 screw , then remo ve the Overloa d P rotector (OLP) lead wire (Blue) BLACK and (Black). LEAD WIRE FIXING FOR OLP 1. Remove 2 lead wire, HT-L3 (Red) and AC2-N2 (White) from below the Heater.
  • Page 222: To Remove Filter

    20.13 To Remove Filter 1. Remove the access cover by removing 2 screws. 1. Set 2 valve for the Water Filter Set to “CLOSE”. Water Filter 2. Pull up the Water Filter set. 3. Remove the retaining ring, then remove the the Water Filter.
  • Page 223: Technical Data

    21. Technical Data 21.1 Operation Characteristics 21.1.1 WH-MDC05J3E5 Heating Characteristics at Different Outdoor Air Temperature Condition Outdoor air temperature : 7°C (DBT), 6°C (WBT) Indoor water inlet temperature : 30°C Indoor water outlet temperature : 35°C 5.200 5.000 4.800 4.600 4.400...
  • Page 224 Cooling Characteristics at Different Outdoor Air Temperature Condition Outdoor air temperature : 35°C (DBT), -°C (WBT) Indoor water inlet temperature : 12°C Indoor water outlet temperature : 7°C 5.400 5.200 5.000 4.800 4.600 4.400 4.200 4.000 Outdoor Air Temperature (°C) 2.000 1.800 1.600...
  • Page 225 Cooling Characteristics at Different Outdoor Air Temperature Condition Outdoor air temperature : 35°C (DBT), -°C (WBT) Indoor water inlet temperature : 19°C Indoor water outlet temperature : 14°C 6.800 6.600 6.400 6.200 6.000 5.800 5.600 5.400 5.200 Outdoor Air Temperature (°C) 2.000 1.800 1.600...
  • Page 226 Cooling Characteristics at Different Outdoor Air Temperature Condition Outdoor air temperature : 35°C (DBT), -°C (WBT) Indoor water inlet temperature : 23°C Indoor water outlet temperature : 18°C 5.800 5.600 5.400 5.200 5.000 4.800 4.600 4.400 4.200 Outdoor Air Temperature (°C) 1.300 1.200 1.100...
  • Page 227 21.1.2 WH-MDC07J3E5 Heating Characteristics at Different Outdoor Air Temperature Condition Outdoor air temperature : 7°C (DBT), 6°C (WBT) Indoor water inlet temperature : 30°C Indoor water outlet temperature : 35°C 7.500 7.000 6.500 6.000 5.500 5.000 4.500 -20 -18 -16 -14 -12 -10 -8 -6 -4 -2 0 8 10 12 14 16 18 20 22 24 26 Outdoor Air Temperature (°C) 2.600...
  • Page 228 Cooling Characteristics at Different Outdoor Air Temperature Condition Outdoor air temperature : 35°C (DBT), -°C (WBT) Indoor water inlet temperature : 12°C Indoor water outlet temperature : 7°C 7.500 7.000 6.500 6.000 5.500 5.000 Outdoor Air Temperature (°C) 2.600 2.400 2.200 2.000 1.800...
  • Page 229 Cooling Characteristics at Different Outdoor Air Temperature Condition Outdoor air temperature : 35°C (DBT), -°C (WBT) Indoor water inlet temperature : 19°C Indoor water outlet temperature : 14°C 9.500 9.000 8.500 8.000 7.500 7.000 6.500 Outdoor Air Temperature (°C) 2.600 2.400 2.200 2.000...
  • Page 230 Cooling Characteristics at Different Outdoor Air Temperature Condition Outdoor air temperature : 35°C (DBT), -°C (WBT) Indoor water inlet temperature : 23°C Indoor water outlet temperature : 18°C 7.800 7.600 7.400 7.200 7.000 6.800 6.600 6.400 6.200 6.000 Outdoor Air Temperature (°C) 2.000 1.800 1.600...
  • Page 231 21.1.3 WH-MDC09J3E5 Heating Characteristics at Different Outdoor Air Temperature Condition Outdoor air temperature : 7°C (DBT), 6°C (WBT) Indoor water inlet temperature : 30°C Indoor water outlet temperature : 35°C 9.000 8.500 8.000 7.500 7.000 6.500 6.000 -20 -18 -16 -14 -12 -10 -8 -6 -4 -2 0 8 10 12 14 16 18 20 22 24 26 Outdoor Air Temperature (°C) 4.000...
  • Page 232 Cooling Characteristics at Different Outdoor Air Temperature Condition Outdoor air temperature : 35°C (DBT), -°C (WBT) Indoor water inlet temperature : 12°C Indoor water outlet temperature : 7°C 10.000 9.500 9.000 8.500 8.000 7.500 7.000 6.500 6.000 5.500 5.000 Outdoor Air Temperature (°C) 3.500 3.000 2.500...
  • Page 233 Cooling Characteristics at Different Outdoor Air Temperature Condition Outdoor air temperature : 35°C (DBT), -°C (WBT) Indoor water inlet temperature : 19°C Indoor water outlet temperature : 14°C 12.000 11.500 11.000 10.500 10.000 9.500 9.000 8.500 8.000 7.500 7.000 6.500 Outdoor Air Temperature (°C) 4.000 3.500...
  • Page 234 Cooling Characteristics at Different Outdoor Air Temperature Condition Outdoor air temperature : 35°C (DBT), -°C (WBT) Indoor water inlet temperature : 23°C Indoor water outlet temperature : 18°C 10.000 9.500 9.000 8.500 8.000 7.500 7.000 Outdoor Air Temperature (°C) 2.600 2.400 2.200 2.000...
  • Page 235: Heating Capacity Table

    21.2 Heating Capacity Table 21.2.1 WH-MDC05J3E5 Water Out 25ºC 35ºC 45ºC 55ºC 60ºC Outdoor Air Capacity Input Capacity Input Capacity Input Capacity Input Capacity Input (°C) Power (W) Power (W) Power (W) Power (W) Power (W) 4370 1730 4160 2030...
  • Page 236: Cooling Capacity Table

    21.3 Cooling Capacity Table 21.3.1 WH-MDC05J3E5 Water Out 7ºC Water Out 14ºC Water Out 18ºC 5180 6170 5780 5380 1220 6640 1250 5550 5000 1540 5860 1610 5000 4190 1850 5360 1920 4370 1300 21.3.2 WH-MDC07J3E5 Water Out 7ºC Water Out 14ºC Water Out 18ºC...
  • Page 237: Exploded View And Replacement Parts List

    22. Exploded View and Replacement Parts List 22.1 Water System WH-MDC05J3E5 11 1 11 1 (MDC07/09J3E5 Only) WH-MDC07J3E5 11 6 11 6 WH-MDC09J3E5 11 6 11 6 Note: The above exploded view is for the purpose of parts disassembly and replacement.
  • Page 238: Refrigerant System

    22.2 Refrigerant System Note: The above exploded view is for the purpose of parts disassembly and replacement. The non-numbered parts are not kept as standard service parts.
  • Page 239 Note: The above exploded view is for the purpose of parts disassembly and replacement. The non-numbered parts are not kept as standard service parts.
  • Page 240 Note: The above exploded view is for the purpose of parts disassembly and replacement. The non-numbered parts are not kept as standard service parts.
  • Page 241 <Model: WH-MDC05J3E5> SAFETY REF. NO. DESCRIPTION & NAME QTY. WH-MDC05J3E5 REMARK BASE PAN ASS’Y (1) CWD52K1282 BASE PAN ASS’Y (2) ACXD52K03580 COMPRESSOR 9KD240XBD21 LEADWIRE COMPRESSOR CWA68C1810 BUSHING - COMPRESSOR MOUNT CWH50055 NUT-COMPRESSOR MOUNT CWH561049 GASKET FOR TERMINAL COVER CWB811017 CONDENSER CO.
  • Page 242 SAFETY REF. NO. DESCRIPTION & NAME QTY. WH-MDC05J3E5 REMARK ACCESSORY CO.(RUBBER CAP) CWH82C1839 ACCESSORY CO.(DRAIN ELBOW) CWG87C900 RECEIVER ACXB14-00670 SENSOR-COMPLETE CWA50C3379 BASE PAN HEATER CWA341071 HOT WATER COIL-COMPLETE ACXB90C00960 FILTER COMPLETE ACXB51C00100 HEATER ASS'Y ACXA34K00240 THERMOSTAT CWA151074 TERMINAL COVER CWH171051...
  • Page 243 SAFETY REF. NO. DESCRIPTION & NAME QTY. WH-MDC05J3E5 REMARK HOLDER COUPLING ACXH35-01880A CWG861483 SHOCK ABSORBER CWG713660 SHOCK ABSORBER CWG713661 SHOCK ABSORBER CWG713662 BASE BOARD-COMPLETE ACXG62C02080 C.C.CASE ACXG50-55100 MODEL LABEL ACXF85-31560 Note:  All parts are supplied from PAPAMY, Malaysia (Vendor Code: 00029488).
  • Page 244 <Model: WH-MDC07J3E5 WH-MDC09J3E5> SAFETY REF. NO. DESCRIPTION & NAME QTY. WH-MDC07J3E5 WH-MDC09J3E5 REMARK BASE PAN ASS’Y (1) CWD52K1282 ← BASE PAN ASS’Y (2) ACXD52K03580 ← COMPRESSOR 9KD240XBD21 ← LEADWIRE COMPRESSOR CWA68C1810 ← BUSHING - COMPRESSOR MOUNT CWH50055 ← NUT-COMPRESSOR MOUNT CWH561049 ←...
  • Page 245 OPERATING INSTRUCTION ACXF55-26700 ← OPERATING INSTRUCTION ACXF55-26710 ← OPERATING INSTRUCTION ACXF55-27620 ← INSTALLATION INSTRUCTION ACXF60-38370 ← INSTALLATION INSTRUCTION ACXF60-38380 ← PANASONIC BADGE CWE373439 ← INVERTER BADGE CWE373441 ← PACKING-L.TUBE CWB81012 ← CONNECTING BAR CWE261213A ← CONNECTING BAR CWE261214A ← GASKET FOR TERMINAL COVER CWB811177 ←...
  • Page 246 SAFETY REF. NO. DESCRIPTION & NAME QTY. WH-MDC07J3E5 WH-MDC09J3E5 REMARK CWG861483 ← SHOCK ABSORBER CWG713660 ← SHOCK ABSORBER CWG713661 ← SHOCK ABSORBER CWG713662 ← BASE BOARD-COMPLETE ACXG62C02080 ← C.C.CASE ACXG50-55100 ← MODEL LABEL ACXF85-31570 ACXF85-31580 Note:  All parts are supplied from PAPAMY, Malaysia (Vendor Code: 00029488). ...

This manual is also suitable for:

Wh-mdc07j3e5Wh-mdc09j3e5

Table of Contents