Mitsubishi Electric FR-F806-E Hardware Instruction Manual page 65

Inverter for fans and pumps, ip55/ul type 12
Table of Contents

Advertisement

Electro-magnetic interference (EMI) and leakage currents
3.1.3
Built-in EMC filter
This inverter is equipped with a built-in EMC filter (capacitive filter) and a common mode choke.
These filters are effective in reducing air-propagated noise on the input side of the inverter.
To enable the EMC filter, fit the EMC filter ON/OFF connector to the ON position.The EMC filter is initially set to the "enabled"
(ON) position.
The input side common mode choke, which is built in the inverter, is always enabled regardless of the EMC filter ON/OFF
connector setting.
NOTE
• Do not change the initially set ON (enabled) position of the EMC filter ON/OFF connector. The Class C2 compatibility
condition is not satisfied with the EMC filter OFF.
• The FR-F846-00250(11K)-L2 to FR-F846-00470(22K)-L2 are not provided with the EMC filter ON/OFF connector. The EMC
filter is always ON.
FR-F846-00023(0.75K) to
00170(7.5K)
FR-F846-00023(0.75K) to 00170(7.5K)
EMC filter ON
Warning
 While power is ON or when the inverter is running, do not open the front cover. Otherwise you may
get an electric shock.
64
PRECAUTIONS FOR USE OF THE INVERTER
FR-F846-00250(11K) to
00470(22K)
FR-F846-00250(11K) to 01160(55K)
FR-F846-00620(30K) to
01160(55K)
OFF ON
EMC filter ON
FR-F846-01800(75K) to
03610(160K)
FR-F846-01800(75K) to 03610(160K)
ON
OFF
EMC filter ON
EMC filter
ON/OFF connector

Hide quick links: