Specification - Philips Dynalite DLE1210 Installation Manual

12 x 10a leading edge dimmer
Table of Contents

Advertisement

Notes
Check the following list. If you are still unable to rectify the situation, contact your nearest Dynalite office. A complete list
of distributors worldwide can be found on the Internet at:
www.philips.com/dynalite
Please ensure that you have completed the following prior to calling our technical support department.
Check all symptoms in the Troubleshooting list
Check for any deviations between the installation and the installation instructions
Make a list of the model numbers of all devices used in the system
SYMPTOM
Dimmer does not operate at all. No Service LED
activity. Power supply indicator LED on PCB not
lit.
Power supply indicator LED lit, but no Service
LED activity.
Dimmer will not respond to control panel push
buttons.
Dimmer operates properly but circuit breakers
keep tripping.
Fluorescent lights won't dim.

specification

Protection:
Regulating Device:
Interference Suppression:
Control Inputs:
User Controls:
DyNet DC Supply +VE:
Preset Scenes:
Cable Entry:
Diagnostic Functions:
Compliance:
Operating Environment:
Construction:
Dimensions:
DLE1210 Installation Manual Rev G.doc Specifications and design subject to change without notice.
Dynalite Manufactured by WMGD Pty Ltd (ABN 33 097 246 921). All rights reserved. Dynalite, Dimtek, DyNet and DLight and associated logos are the
registered trademarks of Dynalite Intelligent Light Pty Ltd. Not to be reproduced without permission.
Unit 6, 691 Gardeners Road Mascot NSW 2020 Australia Tel: +61 2 8338 9899 Fax: +61 2 8338 9333
8
DLE1210 Installation Manual Rev G.docx
PROBABLE CAUSE
Incorrect connection of mains supply or no
power available.
Supply voltage too low, short circuit on
network. Control PCB faulty.
Control panel incorrectly wired or incorrect
configuration.
Instant tripping: - short circuit on load.
Delayed tripping: - Dimmer overloaded.
Wrong type of ballast or ballast incorrectly
wired.
Supply:
230V ±14% 50/60Hz 3-Phase Y 40A per phase
Outputs:
12 x leading edge dimmed outputs at 10A per channel
10A 6KA thermal magnetic breaker on each channel
DLE1210 - Triac 600V 40A nom. 400A surge
DLE1210-S - Dual SCRs – 800V, 55A nom., 550A surge
Iron powder toroidal chokes
Rise time: 400μS at 110V supply, 200μS at 230V supply
1 x RS485 serial port – DyNet & DMX512
1 x programmable dry contact AUX input
Service Switch Diagnostic LED
3 x Phase LED's
Bypass switch for each channel (optional)
200mA (supply for approx. 10 Smart
Panels)
170
Mains - 5 x 25mm2 knockouts on a 105mm x 145mm removable gland plate
Data - 1 x 25mm2 dia. knockout
Device Online/Offline status
Circuit breaker trip reporting (optional)
Circuit run time tracking
Network Watchdog
CE, C-Tick
0C - 40C max 0% - 90% RH non condensing
Alloy/Steel wall mount case with epoxy finish
H 600mm x W 345mm x D 187mm (excluding wall brackets)
Weight:
30 kg
E-mail:
dynalite.info@philips.com
Check power supply to dimmer. Check Line
and Neutral input connections.
Check supply voltage is at least 75% of rated
voltage. Check 5V & 12V terminal voltages.
5V supply must be present.
network bus and restore power.
control PCB.
Check operation of LEDs on control panel.
Push button on panel and study response of
service LED.
Check load wiring for short circuits.
Verify dimmer loading with current tester
(don't forget to de-rate for low power-factor
loads and transformer losses). Check that the
breaker terminals are tight.
Check ballast type.
against ballast manufacturer's diagram.
Web: Philips.com/dynalite
ACTION
Disconnect
Replace
Check actual wiring