Siemens FDOOT271-O Technical Manual

Siemens FDOOT271-O Technical Manual

Radio fire detector
Hide thumbs Also See for FDOOT271-O:

Advertisement

Quick Links

FDOOT271-O
Radio fire detector
Technical Manual
Smart Infrastructure
A6V10425624_en--_h
2020-03-31

Advertisement

Table of Contents
loading

Summary of Contents for Siemens FDOOT271-O

  • Page 1 FDOOT271-O Radio fire detector Technical Manual Smart Infrastructure A6V10425624_en--_h 2020-03-31...
  • Page 2 All rights created by patent grant or registration of a utility model or design patent are reserved. Issued by: Siemens Switzerland Ltd. Smart Infrastructure Global Headquarters Theilerstrasse 1a CH-6300 Zug Tel. +41 58 724-2424 www.siemens.com/buildingtechnologies Edition: 2020-03-31 Document ID: A6V10425624_en--_h © Siemens Switzerland Ltd, 2014 2 | 50 A6V10425624_en--_h...
  • Page 3: Table Of Contents

    Detector locking device FDBZ293 ..........3.5.4 Designation plate FDBZ291............3.5.5 Detector dust cap FDZ291............Planning....................Ambient features ..................Parameter sets for FDOOT271-O ............4.2.1 Sensor mode 0 'Neural fire detector' .......... 4.2.1.1 Description ................ 4.2.1.2 Use..................4.2.1.3 Specification..............4.2.2 Sensor mode 1 'Heat detector' ...........
  • Page 4 Required space ..................Detector base FDB271 ................Mounting radio fire detector FDOOT271-O ..........Detector locking device FDBZ293 ............Designation plate FDBZ291 ..............Commissioning ..................Maintenance / Repair ................Status query ..................... Performance check................... Testing detectors ..................Confirming the detector position............... Establishing factory settings ..............
  • Page 5: About This Document

    Following the instructions consistently will ensure that the product can be used safely and without any problems. Intended use The radio fire detector FDOOT271-O may only be used in a fire detection system in a detector base FDB271 together with a radio gateway approved by the manufacturer.
  • Page 6 About this document A6Vxxxxxxxx_--AA_vv A6Vxxxxxxxx_aa--_vv A6Vxxxxxxxx_----_vv ID code Description A6Vxxxxxxxx STEP-ID generated by the STEP system Separator Language abbreviation in accordance with ISO 639-1 Country abbreviation in accordance with ISO-3166-1 Multilingual or international Document version, single or double digit: a, b, …z; aa, ab, …az; ba, bb, …bz; etc.
  • Page 7: Applicable Documents

    Document ID Title A6V10208552 Installation Detector locking device FDBZ293 A6V10425603 Planning Radio fire detection system OEM A6V10425629 Installation Radio fire detector FDOOT271-O, Detector base FDB271 A6V10425605 User Guide FXS2061-O Wireless diagnostic tool A6V10431682 Data sheet Radio fire detection system OEM A6V10367669...
  • Page 8: History Of Changes

    About this document History of changes 1.4 History of changes The reference document's version applies to all languages into which the reference document is translated. The first edition of a language version or a country variant may, for example, be version 'd' instead of 'a' if the reference document is already this version.
  • Page 9: Safety

    Safety Safety notes 2 Safety 2.1 Safety notes Comply with the following safety notes to protect life, limb, and property. The safety notes in the document include the following elements: ● Symbol for hazard ● Signal word ● Type and source of hazard ●...
  • Page 10 Safety Safety notes DEPICTION for possible damage to property Notes on possible damage to property is depicted as follows: NOTICE Type and source of hazard Consequences in the event the hazard occurs ● Measures/prohibitions to prevent the hazard 10 | 50 A6V10425624_en--_h...
  • Page 11: Safety Regulations For The Method Of Operation

    2.2 Safety regulations for the method of operation National standards, regulations and legislation Siemens products are developed and produced in compliance with the relevant European and international safety standards. Should additional national or local safety standards or legislation concerning the planning, mounting, installation,...
  • Page 12 Disregard of the safety regulations Before they are delivered, Siemens products are tested to ensure they function correctly when used properly. Siemens disclaims all liability for damage or injuries caused by the incorrect application of the instructions or the disregard of danger warnings contained in the documentation.
  • Page 13: Standards And Directives Complied With

    Safety Standards and directives complied with 2.3 Standards and directives complied with A list of the standards and directives complied with is available from your Siemens contact. 2.4 Release Notes Limitations to the configuration or use of devices in a fire detection installation with a particular firmware version are possible.
  • Page 14: Structure And Function

    Structure and function Overview 3 Structure and function 3.1 Overview Properties ● Radio communication with: – Radio gateway – Other radio devices ● Software can be used to set as: – Neural fire detector – Heat detector – Wide-spectrum smoke detector ●...
  • Page 15: Details For Ordering

    Overview 3.1.1 Details for ordering Type Order number Designation FDOOT271-O S54323-F312-A1 Radio fire detector The battery pack and detector base are not included in the scope of delivery. A battery pack and detector base are required for commissioning and operation.
  • Page 16: Sensory

    Structure and function Overview 3.1.3 Sensory The radio fire detector has optical and thermal sensors. The radio fire detector can be parameterized as a smoke detector or a heat detector. Figure 3: Fire detector structure 1 Heat sensors 3 Forward scatterer 2 Backward scatterer 4 Labyrinth The radio fire detector has a sophisticated opto-electronic measuring chamber with...
  • Page 17: Power Supply

    Structure and function Power supply 3.2 Power supply The battery pack BAT3.6-10 supplies the radio devices with power. The battery pack consists of lithium batteries plus a battery cable and a battery connector. Figure 4: Battery pack BAT3.6-10 Battery pack consisting of: ●...
  • Page 18: Function

    Structure and function Function 3.3 Function 3.3.1 Parameter sets The detection behavior of the detectors is influenced by the parameter sets, so that it can be specifically adjusted to the fire phenomena and environmental conditions to be expected in the environment to be monitored. The parameter sets for smoke and heat detection are programmed in the detectors.
  • Page 19: Internal Alarm Indicator

    1 Internal alarm indicator The table below describes the flashing behavior of the internal alarm indicator in the radio fire detector FDOOT271-O: Several flashing patterns are available for normal operation. The flashing pattern is selected using the panel configuration program.
  • Page 20 Structure and function Function Operating condition Flashing Graphic mode Commissioning The radio fire detector IAI flashes has not yet been red once logged on to a radio every two gateway seconds The radio fire detector is not mounted on a detector base.
  • Page 21 Structure and function Function Please also observe the documentation for your fire detection system. A6V10425624_en--_h 21 | 50...
  • Page 22: Renovation Mode

    Structure and function Function 3.3.5 Renovation mode Renovation mode is set using the control panel. Renovation mode can be used under the following conditions: ● If there is a large amount of dust in the air around the radio fire detector temporarily ●...
  • Page 23: Mechanical Setup

    Structure and function Mechanical setup 3.4 Mechanical setup A mounted detector base FDB271 is required to mount the detector. Once the detector is ready for use, twist it onto the detector base either manually or using the detector exchanger. Figure 5: Mechanical setup 1 Battery connector 5 Fixing screws 2 Battery pack...
  • Page 24: Accessories

    ● Compatible with: – Radio manual call point FDM273-O – Radio manual call point FDM275-O – Radio fire detector FDOOT271-O ● Order number: S54370-Z11-A1 3.5.2 Detector base FDB271 ● For installing radio fire detectors ● Directly attached to the mounting surface ●...
  • Page 25: Detector Locking Device Fdbz293

    Structure and function Accessories 3.5.3 Detector locking device FDBZ293 ● For protection against theft ● Compatible with: – Radio fire detector FDOOT271-O ● Order number: A5Q00005035 3.5.4 Designation plate FDBZ291 ● To identify the location ● Compatible with: – Detector base FDB271 ●...
  • Page 26: Planning

    Planning Ambient features 4 Planning 4.1 Ambient features In selecting the optimum parameter set, the following factors must be taken into account: ● Risk of damage to persons ● Value concentration ● Room geometry ● Deceptive phenomena ● Risk of fire ●...
  • Page 27: Parameter Sets For Fdoot271-O

    Planning Parameter sets for FDOOT271-O 4.2 Parameter sets for FDOOT271-O 4.2.1 Sensor mode 0 'Neural fire detector' 4.2.1.1 Description (Parameter set numbers in brackets) Robust (0)/(2): The priority of the 'Robust' parameter set is to a robust response. It is thus particularly suited to application in rooms where deceptive phenomena such as cigarette smoke or dust can be expected.
  • Page 28: Specification

    Planning Parameter sets for FDOOT271-O 4.2.1.3 Specification The following table displays the properties and fields of application of the parameter sets of radio fire detector FDOOT271-O in sensor mode 0. Name Optical Thermal Typ. Response Sensitivity, Sensitivity, Static Differential activation...
  • Page 29: Sensor Mode 1 'Heat Detector

    Parameter sets for FDOOT271-O 4.2.2 Sensor mode 1 'Heat detector' 4.2.2.1 Description This sensor mode is especially suited for applications where the detector should only react thermally. The heat detector FDOOT271-O has the following parameter sets: ● A1R (1) ● A1S (3) Notes on A1 designations ●...
  • Page 30: Sensor Mode 2 'Smoke Detector

    'Sensitive'. Robust (2): This parameter set responds to aerosols in a similar way as the neural fire detector FDOOT271-O in sensor mode 0 with the 'Robust' parameter set, without taking into account the temperature. Sensitive (3): With regard to aerosols, this parameter set reacts in a way that is comparable to 'Fast Response' in sensor mode 0 without temperature influence.
  • Page 31: Application Examples

    Planning Application examples 4.3 Application examples Please contact your system manufacturer for application recommendations, such as choosing the detector type and its settings for various applications. A6V10425624_en--_h 31 | 50...
  • Page 32: Mounting / Installation

    Mounting / Installation Required space 5 Mounting / Installation 5.1 Required space ● Upon insertion of the detector, the detector base is stressed by compression, tension and torsion. The fixing must thus be designed accordingly. ● Detector bases must be placed flat on the ceiling. ●...
  • Page 33: Mounting Radio Fire Detector Fdoot271-O

    Mounting / Installation Mounting radio fire detector FDOOT271-O 5.3 Mounting radio fire detector FDOOT271-O The action of inserting the radio fire detector into the detector base activates it; the detector then logs on to other radio devices immediately. Therefore, start from the radio gateway and work outwards to install the individual radio fire detectors.
  • Page 34 Mounting / Installation Mounting radio fire detector FDOOT271-O 5. Make sure that the holder (3) latches into place correctly. When the battery connector is connected, the internal alarm indicator lights up red for 5 seconds. After a further 10 seconds, the radio fire detector signals that it is not installed on the detector base and the internal alarm indicator flashes.
  • Page 35: Detector Locking Device Fdbz293

    Mounting / Installation Detector locking device FDBZ293 5.4 Detector locking device FDBZ293 The detector can be protected against theft with the detector locking device FDBZ293. Figure 8: Mounting of detector locking device FDBZ293 1 Detector base 4 Detector 2 Set screw with a hexagon socket 5 Allen key 3 Hole 1.
  • Page 36: Designation Plate Fdbz291

    Mounting / Installation Designation plate FDBZ291 5.5 Designation plate FDBZ291 Designation plate FDBZ291 is used to assign a location address to the detector. 1. Label the designation plate. 2. Slide the designation plate into the detector base from the side. FDBZ291 FDB271 Figure 9: Installing the designation plate 1 Designation plate 2 Detector base 36 | 50...
  • Page 37: Commissioning

    Commissioning 6 Commissioning When the battery connector is connected, the radio fire detector FDOOT271-O is activated. Once inserted into the detector base, the radio fire detector automatically looks for radio devices within range in the vicinity and automatically integrates itself into the radio network.
  • Page 38: Maintenance / Repair

    Maintenance / Repair Status query 7 Maintenance / Repair Check the detector on a regular basis, but at least once a year. To do this, look for/check the following and resolve any problems you identify: ● Mechanical damage ● Soiling ● Correct fastening ● Detector function by means of test activation 7.1 Status query The query is issued from the control panel, via the radio gateway.
  • Page 39: Testing Detectors

    Maintenance / Repair Testing detectors 7.3 Testing detectors Depending on the sensor mode, testing may be performed with one or more of the following tools: ● Test gas ● Hot air The following table shows which mode may be tested with which test aid. Mode Test gas Hot air...
  • Page 40: Establishing Factory Settings

    Maintenance / Repair Establishing factory settings 7.5 Establishing factory settings All existing settings are deleted and reset to the factory settings. Figure 10: Establishing factory settings 1 Internal alarm indicator 2 'new' opening with button To create the factory settings on the radio fire detector, proceed as follows: The radio fire detector is being supplied with power.
  • Page 41: Basic Principles For Replacing The Battery Pack

    Maintenance / Repair Basic principles for replacing the battery pack 7.6 Basic principles for replacing the battery pack WARNING Risk of explosion due to fire or short-circuit, even with a discharged battery pack Injury due to flying parts ● Isolate the connections and attach the battery cable to the battery pack to avoid a short-circuit of the connection wires.
  • Page 42: Replacing The Battery Pack

    Maintenance / Repair Replacing the battery pack 7.7 Replacing the battery pack ● Do not interrupt the power supply for longer than 2 minutes. ● Do not interrupt the power supply to multiple radio devices simultaneously. Replace the battery pack for one radio device as described below before replacing the battery pack for the next radio device.
  • Page 43 Maintenance / Repair Replacing the battery pack 8. Insert the new battery pack, paying attention to the position of the battery cable (arrows at 5). 9. Make sure that the holder (4) latches into place correctly. When the battery connector is connected, the internal alarm indicator lights up red for 5 seconds (flashing pattern number 1 Internal alarm indicator).
  • Page 44: Specifications

    Specifications Technical data 8 Specifications 8.1 Technical data You will find information on approvals, CE marking, and the relevant EU directives for this device (these devices) in the following document(s); see 'Applicable documents' chapter: ● Document A6V10431682 Device characteristics Response sensitivity 2.3…12 %/m Compensation speed ≤1/45 voltage increase for detection/h...
  • Page 45 Specifications Technical data Standards European standards ● EN 54-5 ● EN 54-7 ● EN 54-25 ● EN 54-29 ● EN 300220-2 ● EN 301489-3 ● EN 60950-1 A6V10425624_en--_h 45 | 50...
  • Page 46: Dimensions

    Specifications Dimensions 8.2 Dimensions Radio fire detector FDOOT271-O with detector base FDB271 8.3 Environmental compatibility and disposal This equipment is manufactured using materials and procedures which comply with current environmental protection standards as best as possible. More specifically, the following measures have been undertaken: ●...
  • Page 47: Glossary

    Glossary Factory setting Basic settings present at the time of delivery Radio device Any device that the radio gateway monitors Radio network Within a radio cell, bidirectional radio connections are established between the radio devices. Together with the radio gateway connections, these create a radio network. A6V10425624_en--_h 47 | 50...
  • Page 48: Index

    Index Index Approvals ............ 44 Packaging label Product version ........... 15 Parameter set Battery pack Detection behavior of the detector .... 18 Description .......... 24 Product label Replacing ............ 42 Product version ........... 15 Replacing the battery pack...... 41 Recycling............ 46 CE marking............ 44 Control panel ............ 37 Signal processing of the detector Danger level .......... 18 Danger level Source language .......... 5...
  • Page 49 A6V10425624_en--_h 49 | 50...
  • Page 50 © Siemens Switzerland Ltd, 2014 Issued by Siemens Switzerland Ltd Technical specifications and availability subject to change without notice. Smart Infrastructure Global Headquarters Theilerstrasse 1a CH-6300 Zug +41 58 724 2424 www.siemens.com/buildingtechnologies A6V10425624_en--_h...

Table of Contents