Download Print this page

Panasonic PAW-FC-RC1 User Manual page 8

Fan coil-room controller

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 1
No.
Description
Controller mode
P008
0 = 2-pipe systems
1 = 4-pipe systems
Change-over mode, fan release function via heat pump
supply sensor at AI
4 = manual setting in the display via button
P009
5 = manual Heat
6 = manual Cool
7 = automatic via digital input DI
Temperature difference between the current room
P010
temperature and the water temperature (AI1) to release the
fan at Heat mode
Temperature difference between the current room
P011
temperature and the water temperature (AI1) to release the
fan at Cool mode
Operating mode for DI
0 = no contact connected
1-2 = not used
P012
3 = presence detector connected
(switches between Standby and Occupied state)
4 = change-over (heat pump in COOL mode)
Inactive delay
Delay for the display to dim down and enter Idle mode.
P044
If set to 0 (Basic) the display never dims down.
8
Basic Min
Max
0
0
1
4
0
7
3K
1
50
3K
1
50
0
0
4
0 s
0
600

Advertisement