General
CAUTION
The line filters listed conduct a high leakage current via the PE conductor. A permanent PE
connection for the line filter or control cabinet is required due to the high leakage current of
the line filters.
According to EN 61800-5-1, Section 6.3.6.7, the minimum cross-section of the protective
ground conductor must conform to the local safety regulations for protective ground
conductors for equipment with a high leakage current.
Note
If a high-voltage test is conducted with alternating voltage in the system, the line filter must
be disconnected to obtain correct measurement results.
CAUTION
Using line filters not approved by SIEMENS for SINAMICS can lead to line-side harmonics
that can interfere with or damage other loads powered from the network.
CAUTION
Provisions for component cooling must be made at the installation site. Power loss data are
given in the technical specifications.