Installation
3. Secure the operator terminal in position, using all the fastening holes and the
provided brackets and screws:
4. Connect the cables in the specified order.
A
Caution
Ensure that the operator terminal and the controller system have the
same electrical grounding (reference voltage level), otherwise errors
in communication may occur.
B
Use an M5 screw and a grounding conductor (as short as possible)
with a cross-section of minimum 2.5 mm
C
Caution
- Use only shielded communication cables.
- Separate high voltage cables from signal and supply cables.
D
Caution
- The operator terminal must be brought to ambient temperature
before it is started up. If condensation forms, ensure that the
operator terminal is dry before connecting it to the power outlet.
- Ensure that the voltage and polarity of the power source is correct.
RS422/
RS485
RS232
C
Ethernet
5. Carefully remove the laminated film over the operator terminal display, to avoid
static electricity that could damage the terminal.
8
x 4
B
Power
Controller
24V DC
D
A
0.5 - 1.0 Nm
2
.
24V DC
Mitsubishi Electric, MA00815