Control/Circuit Terminal Block - GE Fuji Electric AF-300 MICRO-SAVER II Instructions Manual

1/4 - 5 horsepower
Hide thumbs Also See for Fuji Electric AF-300 MICRO-SAVER II:
Table of Contents

Advertisement

Table 4:
Wire Size Recommendations
& Circuit Protection Ratings
240V – Single Phase and 230V Three Phase
Model
PH
HP
NEMA 1
NEMA 4
Const
Carrier Frequency
Input
TRQ
6KM$221F25N1A1 6KM$221F25X4A1
1
1/4
6KM$221F50N1A1 6KM$221F50X4A1
1
1/2
6KM$221001N1A1 6KM$221001X4A1
1
1
6KM$221002N1A1 6KM$221002X4A1
1
2
6KM$221003N1A1 6KM$221003X4A1
1
3
6KM$223F25N1A1 6KM$223F25X4A1
3
1/4
6KM$223F50N1A1 6KM$223F50X4A1
3
1/2
6KM$223001N1A1 6KM$223001X4A1
3
1
6KM$223002N1A1 6KM$223002X4A1
3
2
6KM$223003N1A1 6KM$223003X4A1
3
3
6KM$223005N1A1 6KM$223005X4A1
3
5
480V – Three Phase
Model
PH
HP
NEMA 1
NEMA 4
Const
Carrier Frequency
Input
TRQ
6KM$243F50N1A1 6KM$243F50X4A1
3
1/2
6KM$243001N1A1 6KM$243001X4A1
3
1
6KM$243002N1A1 6KM$243002X4A1
3
2
6KM$243003N1A1 6KM$243003X4A1
3
3
6KM$243005N1A1 6KM$243005X4A1
3
5
WARNING - Device ratings such as system coordination, short-circuit
rating and type must be carefully reviewed by the user.
NOTE: Wire size from NEC table 310-16. Copper wire rated 60° C for 100 amps or less,
75° C for over 100 amps in 30° C ambient and 1.25 times Drive rated amps. These
are minimum wire sizes; consult and conform to local and national codes.
* NOTE: AC input fuses are required to validate the drive's UL and CSA approvals.
The fuse should be Class J type such as Bussman, JKS or equivalent. Circuit breaker
ratings are shown for reference, but UL and CSA approval can only be validated by
the use of Class J fuses.
** Optional Item.
DB
Incoming Power
Output Current
Power
Resistor**
AC – Line Devices
Wire
Wire
Circuit
Low
High
AWG
AWG
Fuses*
Breaker
1.5
1.3
16
-
6
3
2.5
16
16
10
5
4
14
14
15
8
7
12
12
20
11
10
10
10
30
1.5
1.3
16
-
6
3
2.5
16
16
10
5
4
16
16
15
8
7
14
14
20
11
10
14
14
30
17
16.5
10
10
40
DB
Incoming Power
Output Current
Power
Resistor**
AC – Line Devices
Wire
Wire
Circuit
Low
High
AWG
AWG
Fuses*
Breaker
1.6
1.4
16
14
6
2.5
2.1
16
14
6
3.7
3.7
16
14
15
5.5
5.3
16
14
15
9.0
8.7
14
14
20
4-4
30A 30B Y1 FMA PLC BX RST C1 13 12 11
5
10
15
20
30
5
5
10
15
20
30
5
5
10
15
15
* Not available on 6KM$221F25X1A1, 6KM$221F25A4A1, 6KM$223F25X1A1, 6KM$223F25A4A1.
Figure 4-5.
30C FMP X1
X2
X3
X4 REV FWD THR CM
*
* Factory installed jumper
CONTROL CIRCUIT TERMINAL BLOCK LAYOUT
#1 CAUTION:
Remove jumper from between terminals THR and CM when
a motor overload or a motor temperature switch is used.
Wire the device thermal switch in series with the THR and
CM terminals.
#2 NOTE:
FWD to CM jumper required for operation using keypad
RUN-STOP.
Figure 4-4.
L1 L2 L3 P1 P(+) DB* U V W
DB
E(G)
RESISTOR
DYNAMIC BRAKING RESISTOR CONNECTIONS
4-5
* #1
#2