Installation Manual for Outdoor Unit
No. 0150543934
• Please read this manual carefully before using.
• Keep this operation manual for future reference.
Original instructions
AU08NFKERA
AU10NFKERA
AU12NFKERA

Advertisement

loading

Summary of Contents for Haier MRV5

  • Page 1 Installation Manual for Outdoor Unit AU08NFKERA AU10NFKERA AU12NFKERA No. 0150543934 • Please read this manual carefully before using. • Keep this operation manual for future reference. Original instructions...
  • Page 2: Table Of Contents

    User Manual MRV S adopts "simultaneous control" type, Contents all indoors should be heating or cooling simultaneously. Safety ............1 Installation instruction ........3 To protect compressor, before startup, the unit should be electrified for over 12 hours. Installation procedure ........6 If the unit is not used for a long time, please Electric wiring and the application .....
  • Page 3: Safety

    Safety • his manual should always be accessible and close to this air condition equipment. • here are two types of indications, " WARNING" and " CAUTION". The indication preventing from death or heavy injury is listed as " WARNING". Even the indication listed as "...
  • Page 4 Safety CAUTION • rounding wire should be connected with the grounding bar. The grounding wire can not be connected to the gas pipe, water pipe, lightening rod or the telephone grounding wire. Improper grounding may cause electric shock. • nits installed on roof should have appropriate access and handrail. •...
  • Page 5: Installation Instruction

    Installation instruction For installation, please review the items below: • Is the connected units quantity and the total capacity in the allowable range? • Is the refrigerant pipe length in the limited range? • Is the pipe size proper? And if the pipe installed horizontally? •...
  • Page 6 Installation instruction (2) Installation place selection Air-conditioner can't be The unit should be installed The unit should be installed at installed in the place with at the place with good the strong enough place. Or it will inflammable gas. Or it will ventilation.
  • Page 7 Installation instruction (3) Transportation and hoisting Hoisting • Please remove the outdoor unit to the installation location as far as possible near place befor open the packaging. • Forbid on the equipments to place anything, need to use 2 ropes while promoting outdoor. •...
  • Page 8: Installation Procedure

    Installation procedure Outdoor Installation Installation location • Outdoor unit should be placed in well ventilated and dry place. • Outdoor noise and exhaust should not affect neighbors and around the ventilation. • Ensure the ground steadily reliable. • Do not install the outdoor unit on high oil,salt spray or harmful gases. •...
  • Page 9 Installation procedure Multi Outdoor Min300mm Inlet Outlet Min300mm...
  • Page 10 Installation procedure Case 2: stumbling block on the inlet and top side Single Outdoor Max300mm Max300mm Min360mm Min360mm Multi Outdoor...
  • Page 11 Installation procedure Case 3:stumbling block on the outlet, both right and left side Single Outdoor Min360mm Min1000mm Min300mm Min150mm...
  • Page 12 Installation procedure Multi Outdoor If h>H, please set the outdoor on the foundation to make sure H≥h. H=The height of outdoor and foundation 0<h≤1/2H Over 600 1/2H<h≤H Over 1400 Note: Avoid making air short cycle in any case.
  • Page 13 Installation procedure Multi Row Outdoor Note: Make sure the distance at least 300mm between two neighbor units and no stumbling block. 0<h≤1/2H Over 600 1/2H<h≤H Over 1400...
  • Page 14 R410A, if the pipe over 19.05 is 0-type, the pressure preservation will be bad, thus it must be 1/2H type and over the min. thickness. 3. The branch pipe and the gather pipe must be from Haier. 4. When installing the stop valve, refer to the relative operation instruction.
  • Page 15 Installation procedure Anti-fouling measures First, clean the pipe. Position Installation period Measures More than 1 month Flat the pipe end Outdoor Less than 1 month Flat the pipe end or seal with adhesive tape Indoor Nothing to do with period Pipe specification: The first branch pipe 1.
  • Page 16 Installation procedure 3. Pipe "c" diameter (main pipe, between outdoor gather pipe and the first branch pipe) Main pipe Enlarged main pipe Model Gas pipe (mm) Liquid pipe (mm) Gas pipe (mm) Liquid pipe (mm) AU08NFKERA Ø19.05 Ø9.52 Ø22.22 Ø12.7 AU10NFKERA Ø22.22 Ø9.52...
  • Page 17 Installation procedure B. Indoor unit Gas pipe side Liquid pipe side Model Capacity Connecting Connecting Diameter (mm) Diameter (mm) method method Ø9.52 Ø6.35 Ø9.52 Ø6.35 Ø12.7 Ø6.35 Ø12.7 Ø6.35 Ø12.7 Ø6.35 Ø15.88 Ø9.52 Braze Flared Ø15.88 Ø9.52 Ø15.88 Ø9.52 Ø15.88 Ø9.52 Ø15.88 Ø9.52...
  • Page 18 Installation procedure Adhesive side Seal the connection and wrap the heat insulator with adhesive tape Prepare on field Cut off pipe with the cutter Horizontal Floor Cut off at the middle Floor Right Wrong Pipe installation When doing the piping connection, please do the following: •...
  • Page 19 Installation procedure Operation procedure • Brazing the pipe at the same time charge the nitrogen. Or it will cause a number of impurity (a film of oxidation) to clog the capillary and the expansion valve, further cause the deadly failure. Seal the pipe end with adhesive tape or the stopper to increase the resistance, fill up the pipe with nitrogen.
  • Page 20 Installation procedure B. Leakage test 1. The outdoor unit has been executed the leakage test in the factory. The pipe should be executed leakage test individually and forbidden to test after connecting with stop valve. 2. Refer to the below figure to charge the nitrogen into the unit to take a test. Never use the chlorin, oxygen, flammable gas in the leakage test.
  • Page 21 Installation procedure Because the unit is with refrigerant R410A, the below issues should be paid attention: • To prevent the different oil into the pipe, please use the special tool for R410A, especially for gauge manifold and charging hose. • To prevent the compressor oil into the refrigerant cycle, please use the anti-counter-flow adapter.
  • Page 22 Installation procedure L1: Total length of 22.22 liquid pipe; L2: Total length of 19.05 liquid pipe; L3: Total length of 15.88 liquid pipe; L4: Total length of 12.7 liquid pipe; L5: Total length of 9.52 liquid pipe; L6: Total length of 6.35 liquid pipe; Total refrigerant volume charging on site during installation=W2+W3 W: Total refrigerant volume charging on site for maintenance.
  • Page 23: Electric Wiring And The Application

    Electric wiring and the application Communication wiring figure Outdoor 1 Control wire for wired controller with polarity Indoor 1 Indoor 2 Indoor 3 Indoor 4 Indoor 5 Wired controller Indoor 6 Indoor 7 Indoor 8 Indoor 9 Indoor 10 Wired Wired Wired Wired...
  • Page 24 Electric wiring and the application Power wiring figure Please make sure that when the unit is running, the input voltage is no less than 380V; if it is lower than 380V,the unit may run abnormal. power source: 3N~, 380-415V, 50/60Hz power source: 1PH, 220-240V~, 50/60Hz power source: 1PH, 220-240V~, 50/60Hz power source: 1PH, 220-240V~, 50/60Hz...
  • Page 25 Electric wiring and the application Indoor power source and communication wiring Rated Rated current of residual Communication wire Item Power section Wire current of circuit breaker(A) Indoor cable length overcurrent Ground fault Outdoor/ Indoor/ total section breaker interruptor(mA) indoor indoor current (A) response time(S) <10...
  • Page 26 Installation and debugging Search indoor units In the following table, 1 is ON, 0 is OFF. Begin to search indoor Indoor searching BM1_1 after startup Stop searching indoor and lock the quantity Note: The number of indoor units must be locked by the BM1_1(OFF to ON) before running the outdoor.
  • Page 27: Failure Code

    Failure code Failure code The outdoor unit failure code table Failure code display on Failure code the outdoor Failure code definition Remarks definition digital display board Defrosting temp. Continuous disconnect for 60 seconds or 20-0 Resumable sensor (Te) failure short circuit, failure alarm Ambient temp.
  • Page 28 Failure code Failure code display on Failure code the outdoor Failure code definition Remarks definition digital display board (1)Cooling: Ps≤0.05 MPa or Ps≤0.1MPa for 5 consecutive minutes, failure alarm. Ps≥0.25MPa, failure removed. Once failure Suction pressure (2)Heating: Ps≤0.03Mpa or Ps≤0.05MPa 39-0 locked, un- (Ps) too low...
  • Page 29 Failure code Failure code display on Failure code the outdoor Failure code definition Remarks definition digital display board Tliqsc temp. sensor Continuous disconnect for 60 seconds or Resumable failure short circuit, failure alarm. When the CT current exceeds the specified value for 5 consecutive seconds, failure Once failure CT value too high...
  • Page 30 Failure code Failure code display on Failure code the outdoor Failure code definition Remarks definition digital display board During start-up or operation, the rotor position cannot be detected for 6 consecutive Compressor out of times, failure alarm. The inverter PCB will be control automatic recovery after compressor stops for 5 seconds.
  • Page 31 Failure code In case of no failure, if the starting conditions of the system are not met, the digital tube of the outdoor unit will display the standby code of the air conditioner: Standby state of capacity over- The ratio of indoor capacity to out- 555.0 matched door capacity is over 130%.
  • Page 32: Trial Operation And The Performance

    Trial operation and the performance 5-minute delay function • If starting up the unit after being powered off, the compressor will run about 5 minutes later against being damaged. Cooling/heating operation • Indoor units can be controlled individually, but cannot run in cool and heat mode at the same time.
  • Page 33 Trial operation and the performance Heating capacity • The heating mode adopts the heat pump type that absorbs outdoor heat energy and releases into indoor. So if outdoor temperature goes down, the heating capacity will decrease. Trial operation • Before trial operation: Before being energized, measure the resistor between power terminal block (live wire and neutral wire) and the grounded point with a multimeter, and check if it is over 1M * .
  • Page 34: Move And Scrap The Air Conditioning

    Move and scrap the air conditioning • When moving, to disassemble and re-install the air conditioning, please contact your dealer for technical support. • In the composition material of air conditioning, the content of lead, mercury, hexavalent chromium, polybrominated biphenyls and polybrominated diphenyl ethers are not more than 0.1% (mass fraction) and cadmium is not more than 0.01% (mass fraction).
  • Page 36 Qingdao Haier Air Conditioner Electric Co.,Ltd. Haier Industrial Park,Qianwangang Road,Eco-Tech Development Zone, Qingdao 266555,Shandong,P.R.C.