11 I/O MODULE TROUBLESHOOTING
Table 11.2 Output Circuit Problems and Corrective Actions (Continued)
Condition
When the
Erroneous output due to the stray capacitance (C) between
external power
collector and emitter of photocoupler.
supply turns
on, the load
turns on for a
moment.
(transistor
output)
(1) If the external power supply is turned on precipitously, Ic
(2) Ic current flows to the next stage of transistor Tr1 gate and
SW: External power
11 - 6
Cause
There is no erroneous output at normal load.
An erroneous output may occur at high sensitivity load
(such as solid state relay)
current flows due to the stray capacitance (C) between
collector and emitter of photocoupler.
Y0 output turns on by 100 s.
supply (24V) at On
Output Y0
(1) To turn on or off the external power supply,
check that the external power supply rising
edge must be 10ms or more, and switch the
SW1 to the primary side of external power
supply.
(2) When switching to the secondary side of the
external power supply is required, the
external power supply rising edge
connected a condenser and a resistor must
be slow, and measured 10ms or more.
Sink output
Source output
10ms or less
* The measures are ineffective in the following
modules due to the characteristic of the external
Approx.100 s
power supply circuit
 QY81P
 QY82P
R1: Several tens of ohms
Power capacity
C1: several hundreds of microfarads 50V
*1 Refer to current consumption of the external power
supply for modules used in this manual.
*2 Select the power capacity of resistance to be 3 to 5
times larger than the actual power consumption.
(Example)
R1=40Ω, C1=300 F
Use the below expression to calculate a time
constant
C1
R1=300
MELSEC-Q
Corrective action
(external power supply current
resistance value
(3 to 5)
*2
-6
10
40
-3
=12
10
s=12ms
(To the next page)