Mitsubishi Electric PUHZ-ZRP35VKA2 Service Manual page 74

Hide thumbs Also See for PUHZ-ZRP35VKA2:
Table of Contents

Advertisement

SW2 setting
LEV-C opening pulse 0 to 480
ON
1
2 3 4 5 6
Indoor room temperature (TH1) on error
occurring
8 to 39
ON
1
2 3 4 5 6
Indoor pipe temperature / Liquid (TH2)
on error occurring
−39 to 88
ON
1
2 3 4 5 6
Indoor pipe temperature / Cond./ Eva.
(TH5) on error occurring
−39 to 88
ON
1
2 3 4 5 6
Outdoor pipe temperature / 2-phase
(TH6) on error occurring
−39 to 88
ON
1
2 3 4 5 6
Outdoor ambient temperature (TH7) on
error occurring
−39 to 88
ON
1
2 3 4 5 6
Outdoor heatsink temperature (TH8) on
error occurring
−40 to 200
ON
1
2 3 4 5 6
OCH635A
Display detail
The black square ( ) indicates a switch position.
Explanation for display
0 to 480
(When it is 100 pulse or more, hundreds digit, tens
digit and ones digit are displayed by turns.)
(Example) When 130 pulse;
0.5 s
8 to 39
−39 to 88
(When the temperature is 0°C or less, "–" and
temperature are displayed by turns.)
(Example) When -15°C;
0.5 s
−39 to 88
(When the temperature is 0°C or less, "–" and
temperature are displayed by turns.)
(Example) When −15°C;
0.5 s
−39 to 88
(When the temperature is 0°C or less, "–" and
temperature are displayed by turns.)
(Example) When −15°C;
0.5 s
−39 to 88
(When the temperature is 0°C or less, "–" and
temperature are displayed by turns.)
(Example) When -15°C;
0.5 s
−40 to 200
(When the temperature is 0°C or less, "–" and
temperature are displayed by turns.)
(When the temperature is 100°C or more, hundreds
digit, tens digit and ones digit are displayed by
turns.)
74
0.5 s
2 s
1
30
0.5 s
2 s
15
0.5 s
2 s
15
0.5 s
2 s
15
0.5 s
2 s
15
Unit
Pulse
:
:
:
:
:
: