RTU Combination
No
Connection Condition
1 Only RTU installation
Mixture Installation with standard i
2
ndoor units and RTUs
CAUTION : Failure to comply with the above connection conditions for installation,
it can cause cooling & heating capacity down.
Connection of the Outdoor Unit
<Mixture Install>
Outdoor : 20 Ton
<Wrong Install>
Outdoor : 20 Ton
▶ The total capacity of indoor units exceed 100% of outdoor unit.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG" is a registered trademark of LG Corp.
1) The total capacity of RTU should be 50~110% of outdoor unit.
1) The total capacity of indoor units (standard Indoor Unit + RTU) should be 5
0~100% of outdoor unit.
2) The total capacity of RTUs should be less than 60% the total capacity of ind
oor units.
RTU
6 Ton
RTU
6 Ton
Due to our policy of continuous product innovation, some specifications may change without notification.
Combination
RTU
Standard
6 Ton
4 Ton
RTU
Standard
6 Ton
4 Ton