Table of Contents About this document ..................5 Revision history ....................5 Reference documents ..................5 Accessories ..................... 5 Before you start ....................5 1.4.1 Symbols and abbreviations .............. 5 1.4.2 Trademarks ..................6 1.4.3 Copyright ..................6 1.4.4 Quality assurance ................6 1.4.5 Document use / request to the reader ..........
About this document Revision history 1 About this document 1.1 Revision history Version Date Changes Section Pages 2020-10-15 Highlighted the product size Cover page, 1, 8 of 7-inch. 2018-11-13 First version. 1.2 Reference documents The following documents contain further information on the products described in this document.
This document may be duplicated and distributed only with the expressed permission of Siemens, and may be provided only to authorized persons or companies with the requisite technical knowledge. Siemens reserves the right to make any modification to this document without prior notice. 1.4.4 Quality assurance This document was prepared with great care.
Siemens assumes no liability to the extent allowed under the law for any losses resulting from a failure to comply with the aforementioned points or for the improper compliance of the same.
Overview Product overview 2 Overview 2.1 Product overview The Climatix touch panel is based on Android, featuring a user-friendly interface, good user experience and more advanced functions. The GUI application supports multiple languages and offers transparent, cascading, fading and other special effects.
Page 9
Overview Topology With Climatix POL6XX controller Climatix POL6XX communication concept (here C600) With Climatix POL4XX controller Climatix POL4XX communication concept (here POL42X) A6V11521026_en--_b 9 | 31...
Overview Product design 2.3 Product design The following is the mechanical design of the Climatix capacitive touch panel POL8T2.70. Description Description Display / touch screen USB-B port Recesses for a mounting USB-A port clip RS485 communication Label port and power supply Ethernet communication port and power supply 10 | 31...
Safety instructions Residential applications 3 Safety instructions 3.1 Residential applications The Climatix touch panel is designed for applications in most residential environments. The technical design specification ensures that the product works stably at temperatures of -10 °C…+50 °C (+14 °F − +122 °F). Maximum Ambient Temperature is 50 °C (122 °F).
Check the package content for visible signs of transport damage and for completeness. Note: Do not install parts damaged during shipment. Contact your Siemens representative in the event of damaged parts. Note the information in the following sections of these operating instructions before...
Mounting and connecting Mount the Climatix touch panel w 210 mm 114 mm 4.2 Mount the Climatix touch panel Note: ● The material in the area of the mounting cutout must be sufficiently strong to ensure lasting and safe mounting of the Climatix touch panel. ●...
Mounting and connecting Connect the Climatix touch panel 1. Connect the power supply. 2. Connect the configuration PC. 3. Connect the controller. Field Wiring Terminal Markings- Field wiring terminals shall be marked to show a range of values or a normal value of tightening torque in pound-inches per the terminal block manufacturer.
Mounting and connecting Connect the Climatix touch panel Do not connect Climatix touch panel pin (0 V) directly to Ground of electrical panel to avoid equalizing currents. Note: Ensure that the wires are connected to the correct polarities. 4.3.2 Connect configuration PC A configuration PC can: ●...
Mounting and connecting Switch on the Climatix touch panel RS485 Connection Use the RS485 port to connect to a Climatix controller. 1. Shut down the Climatix touch panel. 2. Connect an RJ45 connector (side B, without power branch) on the communication cable in the product package to the RS485 port of the Climatix touch panel.
Page 18
Mounting and connecting Switch on the Climatix touch panel If the screen does not light up in two seconds after powering up, immediately switch off the power supply. You have probably crossed the cables on the power supply terminal. Check the connected cables and change them as needed. Climatix touch panel has a DEMO application in order to show main functionalities and features.
Operating the Climatix touch panel Operate the touch screen 5 Operating the Climatix touch panel Use the touch screen to operate and use the function keys to trigger associated configured functions within a project. Caution: ● Do not use pointed or sharp objects because they can damage the plastic surface of the touch screen.
Upgrade the firmware of the Climatix touch panel using a USB stick. The Climatix touch panel is delivered with the latest firmware version, uploaded in the Siemens factory. Proceed with the following instructions only if required by Siemens representative. The following table lists the upgrade file name for the touch panel.
Operating the Climatix touch panel Upgrade GUI application 1. When the upgrading process is finished, the Climatix touch panel restarts automatically. It displays introduction screen for a few minutes. Afterwards the touch panel enters into Android mode. 2. Shut down the Climatix touch panel and switch it on again. The upgraded firmware is available on the Climatix touch panel.
Configuring the Climatix touch panel Set screen brightness 6 Configuring the Climatix touch panel You can configure the following Climatix touch panel settings: ● Screen brightness ● System date and time ● Network configuration ● Serial port test ● Language To access the Settings mode: 1.
Configuring the Climatix touch panel Configure the network 6.3 Configure the network To configure the network setting of the Climatix touch panel: 1. Press Network. 2. Choose either automatic address assignment via DHCP, or a Static IP for the Climatix touch panel. –...
Configuring the Climatix touch panel Set the language 5. In the setting mode, enter test data (for example, 1234) in the Send characters textbox and press Senddata. 6. If the monitor software receives the same data (1234, in this example), the test is successful.
Maintenance and care 7 Maintenance and care The Climatix touch panel is designed for maintenance-free operation. Keep the touch screen and keyboard membrane clean. Proceed as follows: 1. Shut down the Climatix touch panel. 2. Spray the cleaning solution onto a cleaning cloth. Do not spray directly onto the Climatix touch panel.
Technical specifications Technical data 8 Technical specifications 8.1 Technical data Power supply Rated voltage (range) DC 24 V (±15%) Consumption Withstand voltage test AC 1000 V, 1 minute Interfaces USB port USB type A, USB type B Ethernet port Serial interface RS485 Memory Application memory...
Technical specifications Interface description FCC compatibility In accordance with FCC Part 15, Class B Listings UL916 Environmental The product environmental declaration (A5W90006122) contains data on environmentally compatibility compatible product design and assessments (RoHS compliance, materials composition, packaging, environmental benefit, disposal). General data Dimensions (mm) 225 ×...
Page 28
Technical specifications Interface description Figure RS485 Pin on controller RS485 A+ RS485 A+ (for RS485 connection) RS485 B- (for RS485 B- RS485 connection) 24 V 24 V IP interface Figure Pin on controller 24 V 24 V Note: RS485 and LAN ports can also supply power. If one port is powered with DC 24 V, the other port will not be output as DC 24 V if no external power supply is connected.
Technical specifications DIP switches Communication cable The following is an example of RS485 connection. (POL0C1.80/STD) Note: Accessories POL0C1.80/STD and POL0C1.75/STD (touch panel-controller communication cables) have an RJ45 connector. To connect the touch panel with the Climatix controller RS485 port, cut off the plug and then connect two wires as shown above.