Download Print this page
ABB Stanilite Standard Installation Manual

ABB Stanilite Standard Installation Manual

Weatherproof cool-room led exit (remote body)

Advertisement

Quick Links

Troubleshooting guide
If you have installed and connected the fitting as per the instructions listed earlier and it does
not function correctly, use the following table as a guide to fixing the problem. Look up the
type of fault in the left column and check the possible causes from the right column.
If the fitting still does not work after checking these possible causes, contact ABB customer
service in Australia on 1800 60 20 20.
No. Fault
1
LED lamp and indicator LED not lit
2
LED lamp not lit but red indicator LED is lit
3
LED lamp not lit but indicator LED is flashing green
4
LED lamp is lit but red indicator LED not lit
5
The LED lamp does not switch to emergency mode
when the test button is pressed
6
Indicator LED is constant green
7
Indicator LED not red after commissioning
8
The LED lamp works momentarily on emergency
when the test button is pressed or tested by
command from the Nexus system
ABB Australia Pty Limited
For enquiries
ABB contact centre: 1800 60 20 20
E-mail: AU-ABB-Stanilite@abb.com
www.stanilite.com.au
Possible causes
AC supply not connected; or
AC supply turned off; or
Test switch damaged
LED lamp damaged; or
LED lamp plug incorrectly inserted in the mother board
LED lamp damaged; or
LED lamp plug incorrectly inserted in the mother board
LED damaged; or
Check battery connection
Test switch damaged
Test switch damaged; or
Self check fail - return to factory
Check battery connection and battery plug polarity
Battery not yet charged (allow up to 24 hours)
© Copyright 2020 ABB. All rights reserved.
I N S TA L L AT I O N M A N U A L
Stanilite®
Weatherproof cool-room LED exit (remote body)
Standard, Nexus® LX, Nexus RF
Thank you for choosing ABB product
Please read this document thoroughly before
commencing installation and retain for future
reference. Contact ABB customer service in
Australia on 1800 60 20 20 if you need any
assistance. The installation instructions were
correct at the time of print. To reflect changes in
technology and Australian standards; ABB
reserves the right to amend the instructions
without notice. Updated document can be found
on the Stanilite website.
Safety warning
In Australia and New Zealand, only licensed
electricians are permitted by law to work with
240 volt electrical installations.
Do not attempt to install or connect this product
unless you are a licensed electrician.
Turn off and isolate the electrical supply before
connecting this fitting to the building wires.
Do not touch the terminals of the terminal block
when the light fitting is energised.
The only user-serviceable part is the battery
pack. LED light source is not user-serviceable.
Do not attempt to service other parts of the
fitting as this will void the warranty.
As the installer, it is your responsibility to ensure
compliance with all relevant building and safety
codes, (ie: AS/NZS 3000, AS/NZS 2293). Refer to
the applicable standards for data and mains
This document covers
What's inside the box
Safety warning
Exit LED weatherproof
Installation instructions
Installation manual
Removal instructions
Warranty information
Testing precautions
Troubleshooting guide
cabling installation procedures and
requirements.
Important to note:
• This product is designed for indoor and
outdoor use.
• Not suitable for installations where
exposure to direct sunlight may occur.
No mains or mains carrying cables are to be
connected to the terminals in the cool-room
LED exit remote body.
The output from the remote power supply only
to be connected to the LED exit remote body.
Doc no. 29-00005_1

Advertisement

loading

Summary of Contents for ABB Stanilite Standard

  • Page 1 I N S TA L L AT I O N M A N U A L If the fitting still does not work after checking these possible causes, contact ABB customer Stanilite®...
  • Page 2 4. Determine the mounting location, hold the enclosure in position and secure it in place by requires that fittings operate in emergency mode ABB does not recommend such practices and appropriate M6 screws (the housing mounting holes diameter is 6.4mm) (due to the wide variety...

This manual is also suitable for:

Stanilite nexus lxStanilite nexus rf