Installation
8
Preparation for Installation
Prior to installation of the panel,
study this instruction manual and
the drawing package, such as
general arrangement, one line
diagram, schematic drawings, wiring
diagrams, panel arrangement and
electrical bill of material.
Installation should be in accordance
with the National Electrical Code,
NEMA and UL Standards. Unless the
panel has been designed for unusual
service conditions, it should not be
located where it will be exposed to
ambient temperature above 40 C
(105 F), corrosive or explosive
fumes, dust, vapors, dripping or
standing water, abnormal vibration,
shock or tilting, or other unusual
operating conditions.
For installation/replacement of i-3
Control Technology in Siemens P1
panel, the following conditions have
to be met:
1.Branch circuit breakers are Siemens
BQD type breakers up to 20A
2.The panel gutter has to be clear,
only wires for electrical loads are
allowed in this area
3.No feed through lugs, sub-feed
breaker or TVSS installed
4.Sub-feed area is clearly designated
for i-3 controller
For more detail information on
the installation/replacement
instruction of individual i-3 Control
Technology components, refer to
Chapter 6 - System Components.