I N S TA L L AT I O N I N S T R U C T I O N S
ReliaGear
lighting panelboard -
AMP1 integrated power and energy

Advertisement

Table of Contents
loading

Summary of Contents for ABB GE ReliaGear AMP1

  • Page 1 I N S TA L L AT I O N I N S T R U C T I O N S ReliaGear lighting panelboard - ™ AMP1 integrated power and energy...
  • Page 3: Table Of Contents

    Table of contents AMP1 AMP1N4 Safety Enclosure for AMP1 series energy Specifications meters with swing panel kit Product identification Product overview Product diagram Installation Wiring diagram symbols Wiring Control power Pulse contact inputs User interface menu abbreviation User interface for data configuration Alert/reset information User interface for setup RS-485 communications...
  • Page 4: Amp1

    • Do not install this product in hazardous or classified locations. • The installer is responsible for conformance to all applicable codes • Mount this product inside a suitable fire and electrical enclosure. For troubleshooting or service related questions, contact ABB at 800-782-8061 or at epis.component.support@abb.com...
  • Page 5: Specifications

    0.37 ft./lb. (0.5 N-m) nominal; Torque 0.44 ft./lb/ (06. N-m) maximum Terminal Block Wire Size 24 to 14 AWG (0.2 to 2.1 mm Rail T35 (35 mm) DIN Rail per EN50022 For troubleshooting or service related questions, contact ABB at 800-782-8061 or at epis.component.support@abb.com...
  • Page 6: Product Identification

    60 days of data) (31 mm) 0.3" • • Continuous and Single Shot logging modes: user selectable (8 mm) 3.9" (99 mm) 4.3" (109 mm) 0.4" (10 mm) For troubleshooting or service related questions, contact ABB at 800-782-8061 or at epis.component.support@abb.com...
  • Page 7: Product Diagram

    • DO NOT USE CURRENT OUTPUT (e.g. 5A) CTs ON THIS PRODUCT. • Failure to follow these instructions can result in overheating and permanent equipment damage. For troubleshooting or service related questions, contact ABB at 800-782-8061 or at epis.component.support@abb.com...
  • Page 8: Wiring

    White USE SYSTEM TYPE 12 (2L + 1n) White Black L1 L2 N L1 L2 L3 Black White White Black Black White White Black Black White Black For troubleshooting or service related questions, contact ABB at 800-782-8061 or at epis.component.support@abb.com...
  • Page 9: Control Power

    • Use the earth connection for electromagnetic compatibility (EMC), not a protective earth ground. Direct connect control power (DC control power) DC control power from 125 VDC to 300 VDC (UL and CE max.) For troubleshooting or service related questions, contact ABB at 800-782-8061 or at epis.component.support@abb.com...
  • Page 10: Pulse Contact Inputs

    Operating System Reset System Serial Number RESET RESET Reset Data PASWD PASWD Enter Reset or Setup Password ENERG ENERG Reset Energy Accumulators DEMND DEMND Reset Demand Maximums For troubleshooting or service related questions, contact ABB at 800-782-8061 or at epis.component.support@abb.com...
  • Page 11: User Interface For Data Configuration

    Counters Accumulated Accumulated Accumulated Pulse Counter 1 Pulse Counter 2 Real Energy Reactive Energy Apparent Energy (Wh if present) (VARh if present) (Ph) (Qh) (Sh) ENRGY ALERT For troubleshooting or service related questions, contact ABB at 800-782-8061 or at epis.component.support@abb.com...
  • Page 12: Alert/Reset Information

    Press “+” or “-“ to Reset. Password Accumulators to 0 Maximums to Present Cou nters to 0 PASWD Setup SETUP -------- To Setup Meter 00000 Enter Setup Password To: DEMND For troubleshooting or service related questions, contact ABB at 800-782-8061 or at epis.component.support@abb.com...
  • Page 13: User Interface For Setup

    This value is read only. For troubleshooting or service related questions, contact ABB at 800-782-8061 or at epis.component.support@abb.com...
  • Page 14 SETUP - The Password to enter the SETUP menu. SPASS -------- Back -------- RESET - The Password to enter the RESET menu. 00000 00000 Setup Passwords Next To Setup page 1 “S BAC” For troubleshooting or service related questions, contact ABB at 800-782-8061 or at epis.component.support@abb.com...
  • Page 15: Rs-485 Communications

    • When tightening terminals, apply the correct torque: 0.37-0.44 ft·lb (0.5-0.6 N·m). (Down) Select (Left) Back (Right) Next – • Use 14-24 gauge (2.1-0.2 mm2) wire. (Down) Select – (Down) Select For troubleshooting or service related questions, contact ABB at 800-782-8061 or at epis.component.support@abb.com...
  • Page 16: Quick Setup

    RATIO screen and through the digits. Use the buttons to select the Potential Transformer step down ratio. b. Press to go back to the S PT screen. For troubleshooting or service related questions, contact ABB at 800-782-8061 or at epis.component.support@abb.com...
  • Page 17: Bacnet Default Settings

    AV, AI or BI objects. The AMP1H5 data logging capability is implemented using three Trend_Log objects. These are described in more detail in the section on data logging For troubleshooting or service related questions, contact ABB at 800-782-8061 or at epis.component.support@abb.com...
  • Page 18 Lists the physical units that a register holds. - AV4: May only write values 1 and 3 - AV5: May only write values from 0.01 to 320.0 For troubleshooting or service related questions, contact ABB at 800-782-8061 or at epis.component.support@abb.com...
  • Page 19 0b0000000000001011010000000000000 – 011110000 – Protocol_Object_Types_ 0b1011000010000000000010000000000 – Supported DE1,AI1,AI2,AI3,AI4,AI5,AI6,AI7,AI8,AI9,AI10,AI11 ,AI12, AI13,AI14,AI15,AI16,AI17,AI18,AI19,AI20,AI21 ,AI22,AI23, AI24,AI25,AI26,AI27,AI28,AI29,AI30,AI3 1,AI32,AI33,AI34,AI35,AI36,AI37,AI38,AI39,AI40,AI4 Object_List – 1,AI42 ,AI43,AI44,AI45,AI46,AI47,AI48,AI49,AI50,AI 51,AI52,AV1,AV2,AV3,AV4,AV5,AV6,AV 7,AV8,AV9,A V10,AV11,BI1,BI2,BI3,BI4,BI5, BI6,BI7,BI8,BI9,BI10,B I11,BI12,BI13,BI14,BI15,TL1,TL2,TL3 Device_Address_Binding – Database_Revsion – For troubleshooting or service related questions, contact ABB at 800-782-8061 or at epis.component.support@abb.com...
  • Page 20: Analog_Value Objects

    Log_Interval property of all three Trend_Log objects (their value is always the same as this one). Changing any of these four properties changes all of them. For troubleshooting or service related questions, contact ABB at 800-782-8061 or at epis.component.support@abb.com...
  • Page 21: Analog_Input Objects

    0 - Max_Power (AI45) – Demand Present Demand KVA_Present_ Total Apparent Power AI36 – 0 - Max_Power (AI45) – Demand Present Demand table continued on next page For troubleshooting or service related questions, contact ABB at 800-782-8061 or at epis.component.support@abb.com...
  • Page 22 15-bit hexidecimal value produced by combining the 15 alert bits into one number, where the bit value of Object BI1 is the least significant bit and BI15 is the most significant bit. For troubleshooting or service related questions, contact ABB at 800-782-8061 or at epis.component.support@abb.com...
  • Page 23: Binary_Input Objects

    (00:00:00:00 on Jan 1, 2000) and should not be relied upon. The clock run, the meter will operate and even log data, but the date and time will not be correct until a Time_Synchronization occurs. For troubleshooting or service related questions, contact ABB at 800-782-8061 or at epis.component.support@abb.com...
  • Page 24: Data Logging

    (a value of 90000 in the Log_Interval property). The Buffer_Length is fixed at 5760, so at a 15 minute interval setting, the buffers hold 60 days of data. For troubleshooting or service related questions, contact ABB at 800-782-8061 or at epis.component.support@abb.com...
  • Page 25 Unsigned 32-bit integer were created (the factory state of the meter). This count is unaffected by resetting the Record Count or by power failures. Event_State Binary – For troubleshooting or service related questions, contact ABB at 800-782-8061 or at epis.component.support@abb.com...
  • Page 26: Installation

    3. To prevent horizontal shifting across the DIN rail, use two end stop clips. Figure 7. DIN rail mounting Clip flush with outside edge Snap onto DIN rail Insert clips from inside For troubleshooting or service related questions, contact ABB at 800-782-8061 or at epis.component.support@abb.com...
  • Page 27: Supported System Types

    Delta AB, BC, CA AB-BC-CA Grounded AN-BN-CN & A, B, C A, B, C, N 3L + 1n AB, BC, CA AN, BN, CN AB-BC-CA 5, 6 For troubleshooting or service related questions, contact ABB at 800-782-8061 or at epis.component.support@abb.com...
  • Page 28: Troubleshooting

    • Verify the terminating resistors are properly installed on both ends of a chain of units. Units in the middle of a chain should not have a terminator. • Verify the shield ground is connected between all units. For troubleshooting or service related questions, contact ABB at 800-782-8061 or at epis.component.support@abb.com...
  • Page 29: Amp1N4

    Examples of critical control functions are • Mount this product inside a suitable fire and electrical emergency stop and over-travel stop. enclosure. For troubleshooting or service related questions, contact ABB at 800-782-8061 or at epis.component.support@abb.com...
  • Page 30: Product Overview

    3. Hinged lid 4. Clasp 5. Brackets for swing panel cover 6. Swing panel cover 6.75" (172 mm) 7. Mounting feet 4.25" (Hardware not pictured) (108 mm) For troubleshooting or service related questions, contact ABB at 800-782-8061 or at epis.component.support@abb.com...
  • Page 31: Installation

    180° so they are flush the top edge of the housing, and the black clip must against the back of the enclosure. protrude slightly past the bottom edge. For troubleshooting or service related questions, contact ABB at 800-782-8061 or at epis.component.support@abb.com...
  • Page 32 If necessary, remove the meter from the DIN rail using a flat screwdriver to pry out the bottom (black) clip while lifting out the bottom of the meter For troubleshooting or service related questions, contact ABB at 800-782-8061 or at epis.component.support@abb.com...
  • Page 33 Optional: Use included hardware to secure the hinged lid at all four Optional: corners. Attach locking mechanism here (not included) For troubleshooting or service related questions, contact ABB at 800-782-8061 or at epis.component.support@abb.com...
  • Page 34 A M P 1 I N T E G R AT E D P O W E R A N D E N E R G Y I N S TA L L AT I O N I N S T R U C T I O N S This page left blank intentionally.
  • Page 35 A M P 1 I N T E G R AT E D P O W E R A N D E N E R G Y I N S TA L L AT I O N I N S T R U C T I O N S This page left blank intentionally.
  • Page 36 We reserve all rights in this document and in the subject matter and illustrations contained therein. Any reproduction, disclosure to third parties or utilization of its contents – in whole or in parts – is forbidden without prior written consent of ABB Inc. © 2022 ABB All rights reserved...

Table of Contents