Please check the following before commencing startup.
Power must be supplied to the monobloc unit for at least 8 hours before start up in or-
der to provide sufficient power to the compressor heater
Check all electrical wiring and connections
Make sure all auto air vents are open and the pressure relief valves are closed
Make sure the system is filled with the correct coolant fluid to around 2 Bar
Check the expansion vessel is large enough. The Yutaki M unit contains a 6 litre expan-
sion tank large enough for 150 litres. For larger water volumes or more than 8m
height difference then an extra expansion vessel is required.
Check all fuses and circuit breakers.
Once you have selected Configuration Assistant Answer the questions -
Is this device attached to the
Is this device controlling the
Is this device used as the room thermostat of a
How many circuits do you
What are the heat emitters installed on circuit
Do you have a domestic hot water tank
Do you have a swimming pool
Do you have a boiler
Do you have an electric backup heater
How many thermostats are
As soon as you are set up as above enter Installer mode by pressing OK & Return
for 3 seconds and then entering the password right, down, left, right, enter.
The spanner icon should appear on the display. You are now ready for setup
T: 0191 516 6554

Pre-Start Checks

Controller Setup on Start Up
unit—YES
unit—YES
have—ONE
installed—NO
installed—NO
installed—NONE
W:
www.seconrenewable.com
zone—NO
one—RADIATORS*
installed—YES
installed—NO
E:
info@seconrenewables.com

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents