CONNECTION SCHEME A – TWO‐WIRE CONNECTION Connect the 24V power supply from the control panel to each terminal: GND 0V => +24V CONTROL PANEL +24V => GND 0V B – SIX‐WIRE CONNECTION Connect the lines output to each terminal: GND 0V => +24V CONTROL PANEL SOUND 1 +24V => GND 0V GND 0V => +24V SOUND 2 +24V => GND 0V GND V0 =>...
Page 3
DIP‐SWITCH SETTING and TERMINALS CHART 1 Terminals Connections ON OFF + S1/RC (1) Sound control 1: 24V = sound, 0V = silent ‐ S1/RC (2) Sound control 1: 0V = sound, 24V = silent +S2 (3) Sound control 2: 24V = sound, 0V = silent R (4) Not Connected. Free to use ‐S2 R (5) Sound control 2: 0V = sound, 24V = silent + S3 (6) Sound control 3: 24V = sound, 0V = silent ‐ S3 (7) Sound control 3: 0V = sound, 24V = silent ANM (8) Syncronism TEST (9) LED Control see DIP 3 CHART 2 DIP Function DIP1 Alarm timing CHART 3: SOUNDER TIMING DIP2 Alarm timing DIP 1 DIP 2 ALARM TIMING DIP3 Flash control OFF OFF INFINITE (BY DEFAULT, COMPLYING TO EN54‐3) DIP4 ...
Page 4
Diagram 1 DIP 5 OFF 6 OFF 7 OFF DIP 5 ON 6 OFF 7 OFF DIP 5 OFF 6 OFF 7 OFF DIP 5 ON 6 OFF 7 OFF 100mA 100mA 100mA 100mA S1 S2 S3 S1 S2 S3 S1 S2 S3 S1 S2 S3 min min min min min min min min min min min ...
Page 5
SOUNDER INSTALLATION Fasten the sounder to the wall. Insert the connection cables through the holes located on the base. If required, modify the default settings by adjusting the dip switches as indicated in the charts above. Connect the power supply to the control panel. Close the internal and external covers with the screws provided. WARNING: The power supply must be of SELV type. Note: to avoid formation of condensation inside the sounder, any air flow must be avoided. Once the cables have been connected, seal the hole using some silicone. This operation will prevent the warm and humid air of the building from forming condensation inside the sounder during winter time, thus avoiding the risk of malfunctioning. ...
Page 6
1293 Notifier s.r.l. Via A: Grandi, 22, 20097 S. Donato Milanese (MI) Italy 17 DoP 1293 ‐ CPR ‐ 0600 EN54‐3 DSE1‐PW ‐ FIRE ALARM SOUNDER Intended for use in fire detection and fire alarm systems in and around buildings TYPE B: for outdoor use Other technical data: see the supplier’s technical dossier. Essential characteristics Performance Performance under fire conditions Pass Operational reliability Pass Durability of operational reliability and response delay, Pass temperature resistance Durability of operational reliability, humidity resistance Pass Durability of operational reliability, shock and vibration resistance Pass Durability of operational reliability, corrosion resistance Pass Durability of operational reliability, electrical stability Pass Durability of operational reliability, resistance to ingress Pass ...