D5060
It is not necessary to connect a MUX
module to the D5060 to program MUX
points with programming DIP switches.
Figure 3: Wiring Diagram When Installing MUX
Points With DIP Switches
1
1 - External power
2 - D8125 MUX
3 - D5060 Multiplex Point Programmer
Figure 4: Cables Included with the Programmer
1
2
3
1 - C318 Serial Cable
2 - C319 External Power Supply Cable
3 - C320 Multiplex Programmer Cable
F01U034899_02
2
RESE T
12 V
IN
OU T
GND
FIRE MAN UA L
PR OG
+
-
+
-
+
-
+
-
PORT
POWER B
ZONEX BU S
WAL K TES T
POWER A
MU X B US A
M UX BU S B
EXT.
SERIAL PORT
MUX
POWER
POINTS
INTERROGATION MODE
3
D5060 User's Guide
3.0
Programming Procedure
3.1
Powering the D5060
To turn the D5060 on, press and hold the [1] key until
the unit beeps. To turn the unit off, press and hold the
[#] and [*] keys simultaneously until the unit beeps.
After 5 min of inactivity, the programmer
powers down automatically to conserve
power.
3.2
Programming the Points
1. The D5060 displays the prompt Adr after it is
powered on. This indicates that it is ready to
begin programming.
2. If the MUX device has no DIP switches, connect
the D5060 to the point to be programmed (Figure
2). If the MUX device has DIP switches, program
the device using its DIP switches.
The point must be connected only to the
programmer and not to the D8125MUX or
the MUX bus.
If programming points for a Bosch
Security Systems control panel, and if the
MUX device has no DIP switches,
connect the D8125MUX and the MUX
device to be programmed to the D5060
for simultaneous programming (Figure 2).
If the MUX device has DIP switches,
program the device using its DIP
switches.
3. Enter the point's three-digit address. The address
must be between 1 and 255. Press [#].
4. The programmer displays tyP. Enter the number
corresponding to the point type you are
programming (Table 2), then press [#]. The
programmer alternately displays the address and
the point type.
When programming a Mux Smoke point
(decimal value 4 or 5, as shown in Table
2), an 18-second timer starts counting. Do
not disconnect the Mux Smoke point until
after the timer counts down to zero.
Page 2