●FR-A800-LC configuration example(Using Progurammable Controller Remote I/O Module)
RESET
Emergency
 
stop button
 
T1
X1
T0
NZ2GFSS2-32D
IO24V
IO24G
Mitsubishi Electric Programmable Controller
CC-Link IE Field Network
Remote I/O Module (With Safety Functions)
NZ2GFSS2-32D/ NZ2EXSS2-8TE
NOTE
• When starting up the system operation, press the RESET switch to reset the safety stop function first,
then turn ON the START switch to run the motor.
• In the above configuration, after resetting the of emergency stop button, the inverter will be in the safe-
state until the RESET switch is pressed.
Caution
 To prevent restart of the inverter when the power is restored after a power failure, 3-wire connection
is recommended for the START/STOP control. In case of 2-wire connection and using latching type
switch to short between STF and SD/PC for starting, ensure the compliance with safety standards for
the restarting when the inverter power is restored after a power failure.
   
X0
X3 COM+
COM+ X2
Y1
Y0 COM-
NZ2EXSS2-8TE
IO24V
IO24G
 
 
 
 
Figure 4 Safety system example of the FR-A800-LC inverter
EXAMPLE OF SAFETY SYSTEM CONFIGURATION