Hitachi L300P Series Service Manual page 15

Hitachi inverter service manual
Hide thumbs Also See for L300P Series:
Table of Contents

Advertisement

Function Mode
Code
Function name
s t
A061
1
frequency upper limiter
nd
A261
2
frequency upper limiter
s t
A062
1
frequency lower limiter
nd
A262
2
frequency lower limiter
A063
Jump frequency1
A064
Jump frequency Width 1
A065
Jump frequency2
A066
Jump frequency Width 2
A067
Jump frequency3
A068
Jump frequency Width 3
A069
Acceleration stop frequency
A070
Acceleration stop time
A071
PID selection
A072
PID-P gain
A073
PID-I gain
A074
PID-D gain
A075
PID scale
A076
PID feedback selection
A081
AVR selection
A082
Motor voltage selection
A085
Operation mode selection
Energy-saving response-
A086
accuracy adjustment
A092
Acceleration time2
nd
A292
2
acceleration time2
A093
Deceleration time2
nd
A293
2
deceleration time2
nd
A094
2
stage adjustable selection
nd
2
stage adjustable
A294
nd
selection(2
motor)
nd
A095
2
acceleration frequency
nd
2
acceleration
A295
nd
frequency(2
motor)
nd
A096
2
deceleration frequency
nd
2
deceleration frequency
A296
nd
(2
motor)
A097
Acceleration pattern selection
A098
Deceleration pattern selection
A101
OI start
A102
OI end
A103
OI start rate
A104
OI end rate
A105
OI start selection
A111
O2 start
A112
O2 end
A113
O2 start rate
A114
O2 end rate
A131
Acceleration curve constant
A132
Deceleration curve constant
b001
Retry selection
Allowable under-voltage
b002
power failure time
b003
Retry wait time
Instantaneous power-
b004
failure/under-voltage trip
during stop
Instantaneous power-
b005
failure/under-voltage
retry time selection
b006
Open-phase selection
b007
Frequency setting to match
b012
Electronic thermal level
Electronic thermal level
b212
nd
(2
motor)
Electronic thermal
b013
characteristic selection
Electronic thermal
b213
characteristic selection
nd
(2
motor)
Free electronic thermal
b015
frequency 1
Free electronic thermal
b016
current 1
Free electronic thermal
b017
frequency 2
Free electronic thermal
b018
current 2
Free electronic thermal
b019
frequency 3
Free electronic thermal
b020
current 3
L300P Setting range
s t
0.00, 1
frequency lower limiter-maximum frequency(Hz)
nd
0.00, 2
frequency lower limiter-2
frequency(Hz)
0.00, start frequency-maximum frequency(Hz)
nd
0.00, start frequency-2
setting maximum frequency(Hz)
0.00-99.99/100.0-400.0(Hz)
0.00-10.00(Hz)
0.00-99.99/100.0-400.0(Hz)
0.00-10.00(Hz)
0.00-99.99/100.0-400.0(Hz)
0.00-10.00(Hz)
0.00-99.99/100.0-400.0(Hz)
0.00-60.0(s)
00(invalid)/01(valid)
0.2-5.0
0.0-3600.(s)
0.00-100.0(s)
0.01-99.99
00(feedback : OI)/01(feedback : O)
00(ON always)/01(OFF always)/02(OFF on decelerating)
200/215/220/230/240, 380/400/415/440/460/480
00(normal operation)/01(energy-saving operation)
0.0-100.0
0.01-99.99/100.0-999.9/1000.-3600.(s)
0.01-99.99/100.0-999.9/1000.-3600.(s)
0.01-99.99/100.0-999.9/1000.-3600.(s)
0.01-99.99/100.0-999.9/1000.-3600.(s)
00(change with 2CH terminal)/01(change with setting)
00(change with 2CH terminal)/01(change with setting)
0.00-99.99/100.0-400.0(Hz)
0.00-99.99/100.0-400.0(Hz)
0.00-99.99/100.0-400.0(Hz)
0.00-99.99/100.0-400.0(Hz)
00(straight line)/01(S-curve)/02(U-curve)/03(reverse U-curve)
00(straight line)/01(S-curve)/02(U-curve)/03(reverse U-curve)
0.00-99.99/100.0-400.0(Hz)
0.00-99.99/100.0-400.0(Hz)
0.-100. ( %)
0.-100. ( %)
00(external start frequency)/01(0Hz)
-400.--100./-99.9-0.00-99.9/100.-400.(Hz)
-400.--100./-99.9-0.00-99.9/100.-400.(Hz)
-100. - 100. (%)
-100. - 100. (%)
01(small swelling)-10(large swelling)
01(small swelling-10(large swelling)
00(trip)/01(0Hz start)/02(start after equal frequency)/
03(trip after equaling frequency and deceleration stop)
0.3-1.0(s)
0.3-100.(s)
00(invalid/01(valid)/
02(invalid during stop and deceleration by stop command)
00(16 times)/01(free)
00(invalid)/01(valid)
0.00-99.99/100.0-400.0(Hz)
0.2*constant current-1.20*constant current(A)
0.2*constant current-1.20*constant current(A)
00/(reduced characteristic)01(constant torque characteristic)/
02(free setting)
00/(reduced characteristic)01(constant torque characteristic)/
02(free setting)
0.-400.(Hz)
0.0-1000.(A)
0.-400.(Hz)
0.0-1000. (A)
0.-400.(Hz)
0.0-1000.(A)
1- 12
Initial data
-FE/-FU/-FR
nd
setting maximum
00/00/02
(230/400)
(230/460)
(200/400)
Rated
Current of
inverter
Rated
Current of
inverter
01/01/00
01/01/00
N o t e
0.00
0.00
0.00
0.00
0.00
0.50
0.00
0.50
0.00
0.50
0.00
0.0
00
1.0
1.0
0.00
1.00
00
00
50.0
15.00
15.00
15.00
15.00
00
00
0.00
0.00
0.00
0.00
00
00
0.00
0.00
20.
100.
01
0.00
0.00
-100.
100.
02
02
00
1.0
1.0
00
00
00
0.00
0.
0.0
0.
0.0
0.
0.0

Hide quick links: