Mechanical Operation Check - GE Limitamp CR194 Installation Instructions Manual

Two-high vacuum control
Hide thumbs Also See for Limitamp CR194:
Table of Contents

Advertisement

CR194 Two-High
Vacuum Limitamp*
Control
HANDLE
AND
ISOLATION
SWITCH
OPERATION
WARNING:
Confirm
that equipment
is de-ener-
gized before
performing
this check.
REF: HANDLE IN
"ON" POSITION
Step
1.
With the high-voltage
door open,
push in the door op-
erated
release
pin as shown in Figure
39. This is not a
normal
operation
and should
only be used for equip-
ment
check
out or servicing.
Step
2.
Push in the handle
latch
release
(See Figure
39) and
move the handle
up to the full "ON" position
(i.e. the
handle
latch
release
pops back out)
by rotating
the
handle
up with a rapid,
positive
motion.
Step 3.
The isolation
switch contacts
may be viewed by looking
through
the window
supplied
in the main fixed
barrier
(See Figure
10). The contacts
should
be fully seated
on all three
phases,
and the word "ON" should
be
visible
in three
places
on the rotating
shaft.
Step 4.
Push in the handle
latch
release
(See Figure
39) and
move the handle
down to the full "OFF" position
(i.e.
the handle
latch
release
pops back out) by rotating
the
handle
down with a rapid,
positive
motion.
lOOR
DOOR
INTERLOCK
INTERLOCK
BAR
DEFEATER
Step 5.
WARNING:
By looking
through
the window
on the main fixed
bar-
rier, confirm
that the isolation
switch contacts
are fully
open,
as indicated
by being
able to read the word
"OFF" in three
places
on the movable
contact
mold-
ing. See Figure
11.
ALL POWER MUST BE REMOVED FROM THE CONTROLLER
BEFORE MAKING THIS CHECK
TO CHECK FOR PROPER INTERLOCKING
BETWEEN THE
HIGH-VOLTAGE
DOOR AND THE DOOR SAFETY INTERLOCK
THE FOLLOWING
CHECK SHOULD BE MADE:
A. OPEN HIGH VOLTAGE DOOR
HIGH-VOLTAGE
DOOR
SAFETY
INTERLOCK
B. WITH THE DOOR OPEN, CLOSE THE ISOLATION SWITCH
AS SHOWN IN FIG. 39
WARNING:
Confirm
that equipment
is de-ener-
gized before
performing
this check.
The operation
of the high-voltage
door safety
interlock
should
be checked
per the procedure
shown
in Figure
41.
C. CLOSE THE DOOR AGAINST THE DOOR INTERLOCK BAR
D. LOOK THROUGH
THE HANDLE CUTOUT IN THE DOOR
AND VISUALLY DETERMINE THERE IS AN OVERLAP
BETWEEN THE DOOR INTERLOCK DEFEATER AND THE
DOOR INTERLOCK BAR AS SHOWN IN THIS FIGURE
E. FOR FINAL CHECK, OPEN THE ISOLATION SWITCH,
CLOSE THE HIGH-VOLTAGE
DOOR, RE-CLOSE THE
ISOLATION SWITCH, AND TRY TO PULL THE DOOR
OPEN. THE DOOR SHOULD NOT OPEN.
Figure 41. Checking procedure
for high-voltage
door safety interlock
23