18 | Installation

5
Installation
▶ Check that the DHW cylinder is complete and undamaged.
5.1

Installation location

NOTICE: System damage due to inadequate load-bearing
capacity of the installation area or unsuitable substrate!
▶ Ensure that the installation area is level and offers
sufficient load-bearing capacity.
If there is a danger that water may collect on the floor of the installation
site:
▶ Place DHW cylinder on a plinth.
▶ Position the DHW cylinder in dry internal areas that are free from the
risk of frost.
▶ Observe the minimum room height ( tab. 11, page 102 and
tab. 12, page 103) and the minimum wall clearances in the
installation location ( Fig. 10, page 106).
5.2

Positioning the DHW cylinder, fitting the thermal

insulation

NOTICE: Material damage from a low ambient
temperature.
If the ambient temperature is below 15 °C, the foil jacket
tears while closing the zipper.
▶ Warm the foil jacket (in a warmed-up room) to above
15 °C.
400/500 litre cylinder "B"/"C" ( Fig. 11ff, page 106)
▶ Remove packaging.
▶ Unscrew the DHW cylinder from the pallet.
▶ Fit the adjustable feet (accessories).
▶ Position and align the DHW cylinder.
▶ Lay the foil jacket (ErP class "C") or additional thermal protection
(ErP class "B") around it.
▶ Close the zipper.
▶ Attach the front hand-hole cover.
▶ Remove the cap.
▶ Place the casing lid on.
▶ Attach Teflon tape or thread.
750/1000 litre cylinder with separate thermal insulation "E"
( Fig. 11ff, page 106)
▶ Unscrew the DHW cylinder from the pallet.
▶ Remove packaging.
▶ Fit the adjustable feet (accessories).
▶ Position and align the DHW cylinder.
▶ Attach the floor insulation.
▶ Lay the thermal insulation around it.
▶ Close the zipper.
▶ Place the top insulation and casing lid on.
▶ Attach the front hand-hole cover.
▶ Remove the cap.
▶ Attach Teflon tape or thread.
6 720 810 364 (2015/05)
750/1000 litre cylinder with PU rigid foam halves "C"
( Fig. 11ff, page 106)
▶ Remove packaging.
▶ Store the packed foil jacket temporarily.
▶ Release the tensioning strap.
▶ Remove the casing lid.
▶ Pull off the PU rigid foam halves with two persons.
▶ Fit the adjustable feet (accessories).
▶ Position and align the DHW cylinder.
▶ Attach the floor insulation.
▶ Lay the PU rigid foam halves, bottom tensioning strap and foil jacket
around it.
▶ Close the zipper.
▶ Place the top insulation piece for the hand-hole cover and the casing
lid on.
▶ Attach the front hand-hole cover.
▶ Remove the cap.
▶ Attach Teflon tape or thread.
5.3

Hydraulic connection

WARNING: Risk of fire from soldering and welding!
▶ When soldering or welding, apply suitable protective
measures (e.g. cover the thermal insulation), since
the thermal insulation is combustible.
WARNING: Risk to health through contaminated water!
Work carried out without due care for cleanliness
contaminates the potable water.
▶ Install and equip the DHW cylinder hygienically in
accordance with national standards and guidelines.
5.3.1

Connecting the DHW cylinder on the water side

System example with all recommended valves and taps ( Fig. 22,
page 110 [WS...] and Fig. 21, page 109 [W...]).
▶ Use installation material that is heat-resistant to 160 °C (320 °F).
▶ Never use open expansion vessels.
▶ Use metal connection fittings in potable water heating systems with
plastic pipes.
▶ Size the drain line in accordance with the connection.
▶ To facilitate blow-down, never install elbows in the drain pipe.
▶ If using a non-return valve in the supply pipe to the cold water inlet:
install a pressure relief valve between the non-return valve and the
cold water inlet.
▶ Install a pressure reducer, if the static pressure in the system is > 5
bar.
▶ Seal all non-used connections.
▶ Only fill DHW cylinders with potable water.
▶ During filling, open the highest positioned tap ( Fig. 24,
page 110).
W 500-1000-5... | WS 500-1000-5 E... | WS 400-1000-5 EL...