Safety; Technical Parameteres - LG multi V ARUM Series Installation Manual

A set for the application of an outdoor compressor condensation unit for a nonoriginal evaporation / hvac unit
Table of Contents

Advertisement

1. SAFETY

The equipment was designed to pose minimum risks during installation and for the operator during use.
However, it is technically impossible to eliminate all risks and therefore, it is absolutely necessary to observe
the below specified instructions.
MANIPULATION AND HANDLING
Upon delivery make sure that the equipment does not show any visible signs of damage and matches the
parameters in the accompanying documentation.
SYMBOLS
Read the user's guide before use.
INSTALLATION
The equipment may only be installed by a professional person possessing the necessary electrical an
air-condition system qualification and skills.
The equipment may only be put into operation by a professional person possessing the necessary
electrical and air-condition system qualification and skills.
OPERATION
The operator uses information display, which installed under a transparent cover. The user is not allowed to
interfere with the equipment in any way
2. TECHNICAL PARAMETERS
Technical parameters
Lead wire terminals
Power supply
Power input
Power supply of separate module KM113.22
Other connected devices
Communication properties with an outdoor
unit
Parameters of Log. input (control)
Analogue input parameters
Input temperature
Log. output parameters
EEV output parameters
MODBUS communication
MOV-MV communication
Using the electronic module KM113
Mechanical parameters
Width x Height x Depth
Protection
Work position
Mechanical durability
Temperature
2020/07/23
Spring terminal WAGO max wire cross section 2.5 mm
230 V ~ AC ±10 %/50 Hz (e.g. from the connected outdoor
unit)
Overvoltage category II
Recommended cable CYKY-J 3x1.5
Max. 30 W
24 V
DC ±10 %/max. 800 mA, The source must be
separated by double insulation (SELV)
Must be separated by double insulation (SELV)
Two wires at RS485 safe voltage level
12 VDC/5 mA voltage (passive-switch by free contact)
10 VDC voltage with interconnected 0V potential, load
20 kohm (max. 0.5 mA)
DALLAS digital sensor, 3 m long (lengths 6 m and 10 m
accessories to order)
Contact relay with load of 50 VAC/DC, maximum 200 mA
24 VDC, 500 mA, inductive load, designed for valves EX4, EX5,
EX6
Serial line: RS485, 9.6 kbps, 8 bits, without parity, 1 stop bit
Serial line: RS485
Designed for installation with top layer overlap min. 1 mm
310 x 246 x 145 mm (vertical installation on the wall)
IP65 based on the used cable glands
vertical
IK06
-25 °C to +55 °C