Produktinformation FMC−210−DM / SM / EST LSN

3.3. Use in explosive areas

All non−automatic detectors of types DM 210 LSN and SM 210 LSN
conform to device category 3G, gas group IIB and temperature
class T6 as per the European guideline 94/9/EG (ATEX). Thus the
detectors may be used in Zone 2 areas where there is danger of
explosion!
Limiting values:
D Detectors may only be operated with central units whose line output is energy−limited
according to EN 50021.
.
This applies to all Bosch fire panels.
D The line voltage (U
D The maximum current (I
Fire detector cable:
D Only fire detector cables that conform to DIN VDE 0814 may be used.
D The total cable capacity (C
D The total cable inductivity (L
.
The cable type J−Y(ST)Y08, in accordance with DIN VDE 0815 (table 10),
has a capacity of 120

3.4. Labelling variants

The detectors have basic labelling and can be individually adapted to the location/applica-
tion with optional labelling variants. This excludes detector variants FMC−210−DM−G−R and
FMC−210−DM−H−R, to which the burning house" symbol has already been applied.
The self−adhesive labelling foils are stuck on the front panel of the detector.
) must not exceed 33 V!
max
) must be limited to 130 mA!
max
) must not exceed 1 mF!
max
) must not exceed 0.01 H!
max
h
F at a length of 1000 m.