Power Cables Connection - AEG PROTECT 1 LCD User Manual

Table of Contents

Advertisement

3.4 Power cables connection

This chapter introduces how to wire AC IN/OUT cables to UPS in different
modes, and UPS connecting with EBM/MBP.
3 3 3 3 . . . . 4 4 4 4 . 1 . 1 . 1 . 1 Input /Output wiring
Input /Output wiring specification
Input /Output wiring
Input /Output wiring
Before wring UPS, upstream breaker and backfeed contactor should be
configured to avoid power backfeed to unity. And 'backfeed voltage danger'
warning label should be added in backfeed contactor or device. Before
operating, UPS input should cut off, and check all terminals voltage to avoid
voltage dangerous. Backfeed contactor rating current should be larger than
UPS rating input current.
Below figures show the wiring system of UPS input.
specification
specification
specification
Single phase input system
Three phase input system