Page 1
SAMURAI SERIES CONDENSERLESS WATER CHILLERS -SCREW TYPE- CLG2 Technical Catalogue Installation, operation and maintenance instructions. Design information. RCUE40CLG2 RCUE50CLG2 RCUE60CLG2 RCUE80CLG2 RCUE100CLG2 RCUE120CLG2...
Page 3
Specifications in this manual are subject to change without notice in order that HITACHI may bring the latest innovations to their customers. Whilst every effort is made to ensure that all specifications are correct, printing errors are beyond Hitachi’s control; Hitachi cannot be held responsible for these errors.
Page 5
Contents o n t e n t s Important Notice Features and Benefits Operation Instructions Components of chiller Preparation Initial Check Installation Test Running Controller Adjustment Self-Inspection Functions Control System Maintenance Troubleshooting General Specifications Drawings Model Selection Application Data Components Data TCGB0051 rev.0 - 09/2009...
Page 8
11.5. Winter shutdown ............................ 70 11.6. Spring start-up ............................70 11.7. Part replacement............................ 71 11.8. Refrigeration cycle ..........................71 11.9. Refrigerant cycle diagram of Hitachi condenserless Chiller (RCUE(40,50,60,80,100,120)CLG2 ....................72 11.10. Compressor removal..........................73 11.11. Safety and protection control ....................... 73 11.12.
Page 9
Contents Technical Catalogue Unit code list ¡ NOTE: Please check by model name your condenserless type, its abbreviation and MODEL CODIFICATION reference number in this technical catalogue. CLG2 SERIES Unit Code Unit Code RCUE40CLG2 8E042072 RCUE80CLG2 8E082072 RCUE50CLG2 8E052072 RCUE100CLG2 8E102072 RCUE60CLG2...
Technical Catalogue I m p o r t a n t n o t i c e HITACHI pursues a policy of continuing improvement in design and performance of Products. The right is therefore reserved to vary specifications without notice.
Features and Benefits Technical Catalogue F e a t u r e s a n d B e n e f i t s Contents 2. Features and benefits ................13 2.1. Chiller picture........................14 2.2. Compressor ........................14 2.3. Control ..........................16 2.4. Heat Exchanger .......................17 2.5.
Features and Benefits Technical Catalogue 2.1. Chiller picture HITACHI is a world leader in technology and with continual research and product development, now offers a screw type Condenser less Chillers. A range of capacity are available from 120 kW to 360 kW.
Page 15
Suction Port CONTINUOUS CAPACITY CONTROL ¡ HITACHI´s Continuous Capacity Control system uses advanced electronic controls to position the infinitely variable slide valve within each compressor. This modulation allows exact load control and accurate chilled water temperature without the need for expensive inverters.
Features and Benefits Technical Catalogue Energy Saving ¡ Thanks to Continuous Capacity Control, 15~20% energy saving is possible compared with current step control systems due to the following: The cooling load can be more closely matched − Continuous Capacity Control takes advantage of high efficiency part load performance. −...
Technical Catalogue Precise Temperature Control ¡ Combination of “Continuous Capacity Control Compressor” and “HITACHI´s unique electronic controls” enable the Chiller to control outlet water temperature precisely, independent of cooling load. This control benefits not only air-conditioning but also industrial process use.
Features and Benefits Technical Catalogue 2.5. Electronic Expansion Valve This unit are equipped with an electronic expansion valve to provide sophisticated control under any temperature condition. The electronic expansion valve provides reduced electrical power consumption compared to the classical system. TCGB0051 rev 0 - 09/2009...
Technical Catalogue O p e r a t i o n I n s t r u c t i o n s Contents 3. Operation instructions................19 3.1. HITACHI condenserless Water Chiller Models: RCUE(40~120)CLG2 ......20 TCGB0051 rev 0 - 09/2009...
Operation Instructions Technical Catalogue 3.1. HITACHI condenserless Water Chiller Models: RCUE(40~120)CLG2 To Start the Unit. ¡ 1. Open the water inlet and outlet valves. 2. After assuring that all control switches have been cut OFF, and the “LOCAL/REMOTE” switch on the printed circuit board is in the “LOCAL”...
Components of Chiller Technical Catalogue C o m p o n e n t s o f C h i l l e r Contents 4. Components of chiller ................21 4.1. Structure drawing ......................22 TCGB0051 rev 0 - 09/2009...
Components of Chiller Technical Catalogue 4.1. Structure drawing HITACHI Condenser less Water Chiller (Example of 1 Compressor Chiller) ¡ STRUCTURE DRAWING OF HITACHI CONDENSER LESS WATER CHILLER UNIT (Example: RCUE60CLG2) N° Name Compressor Water Cooler Electrical Box ...
Preparation initial check Technical Catalogue P r e p a r a t i o n I n i t i a l C h e c k Contents 5. Preparation initial check ................23 5.1. Initial check ........................24 5.2. Placing the unit ........................25 5.3.
Preparation initial check Technical Catalogue 5.1. Initial check Required Materials ¡ Measure and Architectural Information Regarding Installation Location Remote Condenser ¡ Check the capacity of the selected remote condenser. Installation Location ¡ Confirm that the final installation location is provided with convenient piping and wiring work. Strong water runoff should be avoided.
Preparation initial check Technical Catalogue 5.2. Placing the unit Service space ¡ DANGER - Do not install the unit outdoors. If installed outdoor, an electrical leakage will occur, since the unit has not been designed for dew protection - If leakage is detected, stop the unit and contact the installer or a service Chiller...
Preparation initial check Technical Catalogue 5.3. Centre of gravity Centre of Gravity Centre of Gravity Control Panel RCUE - CLG2 Model Location Weight Distribution (kg) Operating Weight (kg) 1250 1370 1450 Location of Centre of Gravity (mm) Dimension Dimension TCGB0051 rev 0 - 09/2009...
Preparation initial check Technical Catalogue 5.4. Service space and foundation RCUE 40, 50 60CLG2 RCUE 80, 100, 120CLG2 Detail of foundation (example: RCUE60CLG2) Nº Name Nº Name 4-Ø 26 (Mounting Holes) Steel Plate (1 mm) Electrical Box Concrete Bottom Frame Vibration proof Rubber Mat (1 mat per position) (option) Vibration proof Rubber Mat (4 positions) Washer...
The rigging angle shall be greater than 60° as shown. The weight of the unit is wires and the unit to indicated on the unit label. avoid damages. Lifting drawing of Hitachi condenser less water chiller unit (Example: RCUE60CLG2) N° Name ...
6.5.2. Evacuation and Refrigerant charge ..................37 6.6. BMS connection ......................37 6.6.1. System ..........................37 6.6.2. Signal ...........................38 6.6.3. Caution on use HARC70-CE1 (op) ..................38 6.6.4. Dimensional drawing and Specifications of Hitachi gateway (model HARC70-CE1/HARC70-CE1 0P) ................39 6.7.CSC-5S ..........................44 6.7.1. System ..........................44 6.7.2. Signal ...........................44 6.7.3.
Installation Technical Catalogue 6.1. Electrical Wiring Tools and Instruments ¡ One set of wiring tools and electrical tester (clamp meter) Schedule Check ¡ DANGER: Switch OFF main interruptor (M.I) for any work inside Electrical Box. WARNING: - Confirm that the field-selected electrical components (main power switch, fuses, wires, conduit connections, wire terminals and others) are properly selected according to the “Electrical Data“...
Page 31
Installation Technical Catalogue N° Name In case of remote control operation this wire must be removed. S Phase Neutral Low Voltage / Remote Control Run/Stop Signal Alarm Signal Alarm Lamp Pump Interlock Pump Operation Remote Control Switch (RSW-A) (OPTION) 2 cycles 2 nd.
To prevent freezing of the water, it is effective to operate the pumps even during shutdown period. HITACHI Chiller has the pump ON/OFF operation control (see Wiring Diagram) water from piping. Additionally, in a case where measures such as water draining are difficult, utlize antifreeze mixture of ethylene glycol type or propylenen glycol type.
Installation Technical Catalogue CAUTION: In case of connecting some units to the same water piping, design the water piping so that the water distribution to each unit is equal (refer to figure below) Imbalance of water distribution may cause a serious damage like a water freezing in the heat- exchanger.
Installation Technical Catalogue 6.4. Water control CAUTION: When industrial water is applied for chilled water and condenser water, industrial water rarely causes deposits of scales or other foreign substances on equipment. However, well water or river water may in most cases contain suspended solid matter, organic matter, and scales in great quantities.
Page 35
Installation Technical Catalogue Maximum piping length and lift ¡ Maximum Equivalent Piping Maximum Difference in Heigh Length (m) Water Chiller is below Remote Condenser Water Chiller is above Remote Condenser CAUTION: Do not charge Oxygen, Acetylene or other flammable and poisonous gases into the refrigeration cycle when performing a leakage test or an airtight test.
Page 36
Installation Technical Catalogue Refrigerant Piping Arrangement ¡ - Water chiller is below the remote condenser: Field-Supplied Liquid Loop Liquid Loop Remote Condenser Remote Condenser Oil Trap Oil Trap Maximum 25 meters At each At each 10 meters 10 meters Chiller Unit Oil Trap Oil Trap Receiver...
Chiller 3 Chiller 4 Chiller 1 One interface HARC70-CE1 can connect up to 4 Chillers from a remote place using H-Link connection (Hitachi communications protocol). Protocol used by HARC70-CE1 (OP) is LonWorks. Physical channel connection with interface is FTT-10ª TCGB0051 rev 0 - 09/2009...
Installation Technical Catalogue 6.6.2. Signal ON/OFF Chiller All HARC’S Control Operation Outlet Water Setting All HARC’S ON/OFF All HARC’S Chilled Water Outlet Setting All HARC’S Chilled Water Outlet Temperature All HARC’S Chilled Water Inlet Temperature. All HARC’S Alarm Codes All HARC’S Operation Status All HARC’S Discharge Pressure 1,2...
Monitoring Device corresponds with the condition of HARC in the interval of MaxSendTime . 14. It can’t be used with the except for “ stop signal of input terminal of Chiller unit “. 6.6.4. Dimensional drawing and Specifications of Hitachi gateway (model HARC70-CE1/HARC70-CE1 0P) Structural Drawing ¡...
Page 40
Ground Earth Wire (Field Supplied) Connection Wire Between LonWorks Signal Wire DC 5V (Field Supplied) Marking of Terminals ¡ CONTROL SYSTEM G/W HITACHI AC / AC / LON / H-LINK MCLR LON-SERV. LON H-LINK S202 S201 Mark Indication...
Page 41
Installation Technical Catalogue Network Variables and Setting (HARC70-CE1) ¡ Chiller Water Condenser Air Heat SVNT LONMARK Name Type Description Contents Remarks Number Cooled less Cooled Pump Number SNVT No Byte 1: Value 0 (Fixed) nviChillerEnable_0 SNVT_switch On/Off Order Byte 2: State 0/1 = STOP/RUN nviCoolSetpt_0 SNVT_temp_p Cool Water Temperature Setting 2 Bytes: -2000 ~ 2500 = -20 ~ 25 ºC...
Page 42
Installation Technical Catalogue Network Variables and Setting (HARC70-CE1 OP) ¡ Water Condenser Air Heat SVNT LONMARK Name Type Description Contents Remarks Cooled less Cooled Pump Number SNVT No Byte 1: Value 0 (Fixed) nviChillerEnable_0 SNVT_switch On/Off Order Byte 2: State 0/1 = STOP/RUN Cool Water Temperature nviCoolSetpt SNVT_temp_p...
Page 43
Transceiver Using FTT-10A No warranty shall be applied for the control and operation of the upper “LonWorks” side. Warranty Hitachi’s liability shall cover only Hitachi Chillers, this gateway, and accessibility by “LonWorks” Transmitting Setting (On Chiller Control PCB) ¡ Operation Before shipment, No.
Installation Technical Catalogue 6.7.CSC-5S CSC-5S is a remote controller for Hitachi Water Chillers 6.7.1. System CSC-5S allows the individual control of a Chiller Unit as well as it allows a centralized and grouped controls of a maximum number of 8 chillers.
Installation Technical Catalogue 6.7.3. Caution on use of CSC-5S Follow strictly instructions of CSC-5S Installation Manual. This control requires power supply ~1 220-240 V. 6.7.4. Transmitting setting (on chiller control PCB) Operation Before shipment, No. 1 pin of DSW10 is set at ON side In case that Chiller Unit quantity in the same H-Link is 2 or more, set No.
Test Running Technical Catalogue Te s t R u n n i n g Contents 7. Test running .....................47 7.1. Preparation ........................48 7.2. Test running procedure ....................48 7.3. Instructions after test running ..................48 TCGB0051 rev 0 - 09/2009...
CAUTION: When the unit is wired according to the HITACHI standard wiring shown on the wiring label. Switch ON the main power switch, and energize the oil heater for 12 hours before start-up to sufficiently warm the oil. Each rotation direction of two rotors in the compressor is fixed so that a reversal phase protection device is equipped.
Controller Adjustment Technical Catalogue C o n t r o l l e r A d j u s t m e n t Contents 8. Controller adjustment ................49 8.1. PCB Drawing ........................50 8.2. Control System ........................51 8.3. Controller Adjustment ......................51 TCGB0051 rev 0 - 09/2009...
Controller Adjustment Technical Catalogue 8.2. Control System Electrical Operation Control advanced HITACHI Condenser less Chillers are as follows. Capacity Control ¡ All models are equipped with an unloading system for each compressor, in order to adjust the cooling capacity and to provide precise temperature control for the chilled water, coupled with electronic thermostats..
Page 52
Controller Adjustment Technical Catalogue Neutral Zone Setting Switch = RSW8 ¡ = 2 degrees is standard. The RSW8 dial is already set at 3 (= 2 degrees). The figures at the RSW8 dial mean as follows: Figure Band (degree) Continuous Capacity Control Setting Switch = DSW5 ¡...
Page 53
Controller Adjustment Technical Catalogue Temperature Band for Restart Setting Switch = 2 degree is standard. The figure 3 and 4 of the DSW5 switch are already set at figure 3 = ON side, 4 = OFF side. The locations at the figure 3 and 4 of the DSW5 mean as follows. Figure Location Band(degree)
Page 54
Controller Adjustment Technical Catalogue Manual Set Switch A = DSW3 ¡ * Compressor Forcedly Stop Mode Setting Switch * Switches “DSW3-1” is for No.1 compressor, “DSW3-2” for No.2. If necessary to stop any compressors, turn these switches (DSW3-1, DSW3-2) to the OFF side, the compressors corresponding to these switches are turned to the OFF side will be stopped.
Self-Inspection Functions Technical Catalogue S e l f - I n s p e c t i o n f u n c t i o n s Contents 9. Self-Inspection functions .................55 9.1. Alarm Indication .......................56 9.2. Normal Indication......................57 9.3.
Self-Inspection Functions Technical Catalogue 9.1. Alarm Indication If the unit is operated under abnormal conditions, an alarm code (refer to the SEG.1 SEG.2 table below) is indicated and the “Alarm” LED lamp is lighted. 7 Segments on Function of 7-Segment Light Emitted Diode on Control Panel is as shown in Control Panel the table below.
Self-Inspection Functions Technical Catalogue 9.2. Normal Indication If the unit is operated under a normal operation condition, the operation code (refer to the table below) is indicated on 7-Segment LED’s of the control panel. Code No.1 No.2 Content Cycle Cycle Power Supply, After Stoppage Cooling Operation Stoppage by Thermo-OFF or Retry by Alarm Cx-5x...
Page 58
Self-Inspection Functions Technical Catalogue Indication Mode of Alarm Occurrence Data ¡ The content of abnormal stoppage including activation of safety devices is memorised and indicated on the control panel Alarm Occurrence Data (Max.10 data) Example: In case of No.
Page 60
Self-Inspection Functions Technical Catalogue Memory Data Indication in Alarm ¡ Data is indicated same as Checking Indication. In addition the checking data, below data is added. ∆↓ ↑∇ Evaporating Temperature (°C) ∆↓ ↑∇ Water Outlet Temperature (Cooler ...
Page 61
Self-Inspection Functions Technical Catalogue 3) Press the check “ “ and “ ” switches simultaneously for more than 3 seconds. At the same time, the setting value shown on display is memorized and available. ⇔ . * The setting is changed to 9.5ºC. * Hot water temperature setting change is performed by same procedure mention above.
Control System Technical Catalogue C o n t r o l S y s t e m Contents 10. Control system..................63 10.1. Standard operating sequence for RCUE40CLG2, RCUE50CLG2 and RCUE60CLG2 ................64 10.2. Standard operating sequence for RCUE80CLG2, RCUE100CLG2 and RCUE120CLG2 ................65 TCGB0051 rev 0 - 09/2009...
Control System Technical Catalogue 10.1. Standard operating sequence for RCUE40CLG2, RCUE50CLG2 and RCUE60CLG2 Control Stage Starting Control Capacity Control Safety Devices Shut Down Control Devices Main Power Switch Chilled Water Pump Condenser Water Pump Operation Switch (ON/OFF) Load Up Neutral Controller Load Down...
Control System Technical Catalogue 10.2. Standard operating sequence for RCUE80CLG2, RCUE100CLG2 and RCUE120CLG2 Control Stage Starting Control Capacity Control Safety Devices Shut Down Control Devices Main Power Switch Chilled Water Pump Condenser Water Pump Operation Switch (ON/ OFF) Load Controller Neutral Load Down...
The semi-hermetic screw compressor requires periodic maintenance, including explosion. replacement of parts. See the HITACHI Service Handbook for Screw Compressors, for Turn OFF the main details. switch when electrical...
Maintenance Technical Catalogue CAUTION: - Correctly select cleaning agent depending on scales in the plate type heat exchangers. The cleaning chemicals are different depending on fouling degree. - This plate type heat exchanger is made of stainless steel. Do not use a cleaning agent containing hydrochloric acid or fluorine compound.
Maintenance Technical Catalogue 4. Waste Fluid - Stop the acid-resistant pump. - Put the waste fluid into the waste fluid tank. - Supply water into the cleaning tank and operate the pump for water cleaning. - Put the cleaning water into the waste fluid tank as same as the waste fluid. - Measure pH degree by using a pH test sheet and neutralize the waste fluid by gradually adding neutralizing agent.
Maintenance Technical Catalogue 11.7. Part replacement Replacement of parts should be undertaken by ordering from the HITACHI Spare Parts List. CAUTION: Do not replace with spare parts which are not the equivalent. 11.8. Refrigeration cycle Strainer ¡ Check for clogging each time when the refrigeration cycle is opened.
(water-cooled) hours or 5 years. and 24,000 (air-cooled) hours or 3 years pass after installation, exchange the bearings of the compressor. For details, refer to the Service Handbook for HITACHI Screw Compressors. - For R407C refrigerant system, charge the refrigerant with liquid condition to avoid its composition change.
Maintenance Technical Catalogue 11.11.1. Safety and control device setting RCUE Model CLG2 For Compressor Manual reset, non-adjustable (one switch for each compressor motor ) High Pressure Switch Cut-Out 2,80 2,80 2,80 2,80 2,80 2,80 Low Pressure Switch Electronic control (Pressure Sensor) 0,05 0,05 0,05...
Maintenance Technical Catalogue 11.12. Normal operating pressure Check to ensure that Chiller is operating within the working range as shown below, after at least 15 minutes operation. Low Pressure: The normal operating low pressure of the water chiller is indicated in the figure below; lower than 0.3 MPa indicates an abnormal condition.
Maintenance Technical Catalogue 11.13. Test running and maintenance record MODEL: RCUE MFG. NO. COMPRESSOR MFG. NO. CUSTOMER’S NAME AND ADRESS: DATE: 1. Is there adequate water flow for the condenser (in case of water cooled type) and the water cooler? 2.
Maintenance Technical Catalogue 11.14. Daily operating records Model: Date: Weather: Time of Operation Start: Stop. ( Ambient Temperature ºC ºC Room Temperature ºC Compressor High Pressure Pressure Voltage Current Condenser Water Inlet ºC Temperature: (Water-Cooled Type) Outlet ºC Condenser Air Temperature: (Air-Cooled Type) Chilled Water Inlet...
Maintenance Technical Catalogue 11.15. Servicing for R407C refrigerant system Refrigerant ¡ This R407C refrigerant is HFC type so that it has a feature of no ozone depletion. If it is mixed with another refrigerant, the serious changing would occur on its character. Therefore notice the following point when handling this refrigerant.
Troubleshooting Technical Catalogue T r o u b l e s h o o t i n g Contents 12. Troubleshooting ..................79 12.1. Troubleshooting table ....................80 TCGB0051 rev 0 - 09/2009...
Troubleshooting Technical Catalogue 12.1. Troubleshooting table The following table shows efficient checking procedures for trouble. Fault Possible Cause Check/Corrective Action Interlock Circuit for Chilled Water Pump is Open 1. Check the pump contactor. Repair or replace, if necessary. 2.Check for the faulty pump. Compressor Does Not Operate Electrical Protective Devices Are Tripped.
Page 81
Troubleshooting Technical Catalogue Fault Possible Cause Check/Corrective Action Too Much Water Flowing through the Condenser, 1.Adjust the water cock or the regulating valve. or Water is too Cold 2.Check the operation of cooling tower. Insufficient Refrigerant Charge 1.Add Refrigerant. Leakage from the Condenser Gas Outlet Valve 1.
General Specifications Technical Catalogue G e n e r a l S p e c i f i c a t i o n s Contents 13. General specifications ................83 13.1. General data ........................84 13.2. Option line up ........................86 TCGB0051 rev 0 - 09/2009...
Drawings Technical Catalogue 14.1. Dimensional Drawings 14.1.1. RCUE40CLG2 Electrical Box Inlet for power supply wiring Inlet for control wiring Cooler Water Inlet 4x Lifting Holes Cooler Water Outlet 0 (welding connection) 54 (3B Victaulic connection) 14.1.2. RCUE50CLG2 Electrical Box Inlet for power supply wiiring Inlet for control wiring...
Drawings Technical Catalogue 14.2.6. Customer wiring NOTE: 1. All the setting must be performed before Power ON. 2. Remote / Local Change over Switch on Operation Switch must be set, to Remote. 3. Terminals 1 ~ n57 are for AC220-240V. Terminals A ~ D are for DC24V. Terminals E ~ F are H-link (Low signal). TCGB0051 rev 0 - 09/2009...
Drawings Technical Catalogue 14.2.7. Parts list Mark Name Remark Mark Name Remark Compressor motor Solenoid valve for starting 11-n1 Main isolator Solenoid valve for load-down 12-n2 Solenoid valve for load-up Contactor for compressor motor 13-n3 Contactor for compressor motor (start Solenoid valve operation) s1-sn...
Model Selection Technical Catalogue M o d e l S e l e c t i o n Contents 15. Model selection..................99 15.1. Selection Example .......................100 15.2. Performance Table ......................101 15.3. Electrical Data ......................105 15.4. Sound Data........................106 TCGB0051 rev 0 - 09/2009...
Model Selection Technical Catalogue 15.1. Selection Example 1. Determine the system requirements Condensing Temperature: 40 °C Chilled Water Inlet Temperature: 12 °C Chilled Water Outlet Temperature: 7 °C Cooling Load: 300 kW Refrigerant: R407C 2. Select Model and Read the Performance. From the cooling capacity table, model RCUE100CLG2 can be selected with the following performance.
Model Selection Technical Catalogue 15.3. Electrical Data Commpressor Applicable Maximum Motor Unit main power Instantaneous Unit Unit Model Voltage (V) Current Maximum (kW) (Hz) Maximum Minimum 59.4 34.4 RCUE40CLG2 56.4 34.4 54.4 34.4 73.2 42.4 RCUE50CLG2 69.5 42.4 67.0 42.4 90.0 52.1 RCUE60CLG2...
Model Selection Technical Catalogue 15.4. Sound Data Standard Models ¡ Sound Pressure Level (dB) Overall Frequency Band (Hz) Model (dBA) 1000 2000 4000 8000 RCUE40CLG2 RCUE50CLG2 RCUE60CLG2 RCUE80CLG2 RCUE100CLG2 RCUE120CLG2 Sound Power Level (dB) Overall Frequency Band (Hz) Model (dBA) 1000 2000 4000...
Application Data Technical Catalogue A p p l i c a t i o n D a t a Contents 16. Application Data...................107 16.1. Working Range ......................108 16.2. Part Load Performance ....................108 16.3. Ethylene Glycol Application ..................110 TCGB0051 rev 0 - 09/2009...
Humidity ≤ 50% (40 °C) Altitude ≤ 1000 m Minimum working range requeriments according to EN60204-1. In case of different working range conditions, ask conformity to HITACHI Distributor.) 16.2. Part Load Performance Model: RCUE40CLG2, RCUE50CLG2 and RCUE60CLG2 ¡ Compressor Load...
Page 109
Application Data Technical Catalogue Model: RCUE80CLG2, RCUE100CLG2 and RCUE120CLG2 ¡ Compressor Load Condensing Performance 7.5* 15~99% Full Temperature Capacity 55°C Input Capacity Input 50°C Capacity 45°C Input Capacity 40°C Input Capacity Input 35°C :Standard Condition (Condensing temperature: 45°C) (Cooler Water Inlet/Outlet: 12/7°C) ...
Application Data Technical Catalogue 16.3. Ethylene Glycol Application Low ambient application ¡ Under the condition where the ambient temperature is low in winter, there is a case where the unit and piping will become damaged by freezing during the shutdown periods. To prevent freezing, it is effective to operate the pump.
Page 111
Application Data Technical Catalogue 2. Performance Condensing Temperature (°C) CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT CAP IPT (wt%) (°C) (Kf) (Kp) ( % ) ( % ) ( % ) ( % ) ( % ) ( % ) ( % ) ( % ) ( % ) ( % ) ( % ) ( % ) ( % ) ( % ) ( % ) ( % ) 1,011 1,15 1,012...
Components Data Technical Catalogue C o m p o n e n t s D a t a Contents 17. Components data ................113 17.1. Compressor .........................114 17.2. Water Cooler .......................114 TCGB0051 rev 0 - 09/2009...
Components Data Technical Catalogue 17.1. Compressor Model 40ASC-Z 50ASC-Z 60ASC-Z Type Semi-Hermetic Revolution 2880 Displacement 137.4 169.5 208.7 Capacity Control 100 ~ 15, 0 Pneumatic Pressure High Side Low Side Motor Type Special Squirrel Cage, Three-Phase Motor Starting Method Star-Delta Starting Nominal Output Poles Insulation...
Page 115
Components Data Technical Catalogue SINGLE TYPE COOLER DUAL TYPE COOLER Water In Water In Nº 1 Refrigerant Out Nº 2 Refrigerant Out Refrigerant Out Water Out Water Out Nº 1 Refrigerant In Nº 2 Refrigerant In Refrigerant In Water Water Plates Plates Nº...
Page 118
-ken, Japan ISO 9001 Certified by JQA, Japan ISO 14001 Certified by JQA, Japan Hitachi Air Conditioning Products (M) Sdn. Bnd. Lot No. 10, Jalan Kemajan Bangi Industrial Estate 43650 Bandar Baru Bangi, Selangor Darul Ehsan, Malaysia Certification ISO 9001, Malaysia Certification ISO 14001, Malaysia TCGB0051 rev.0 - 09/2009 - Printed in Spain...