Smoke Detector Trouble Conditions
There are several different models of Smoke Detectors. If yours is not listed below, please refer
to the
Peripheral Device Manual
Ademco Honeywell 5806 W3
These Trouble Conditions apply to the
5806W3
wireless smoke detector. This smoke detector has 2
LEDs and a sounder to indicate the detector's status.
State
Green LED
Normal
Blinks every
(standby)
10 seconds
Smoke Alarm
Off
Thermal
Off
o
Alarm (>135
)
Freeze
Off
Trouble
o
(<41
)
Smoke & Heat Detector Troubleshooting
page to locate the user's manual for your device.
Ademco Honeywell
Red LED
Sounder
Off
Off
Blinks every
Pattern
1 second
Blinks every
Pattern
4 seconds
Blinks every
Off
10 seconds
Action
The device is operating normally. No
action needed.
Smoke has been detected. ADT has
been contacted. Press the recessed
test switch to silence the smoke
detector sounder for 5 minutes. If
necessary, silence the alarm keypad.
Remove the source of the smoke, if it
can be done safely. If necessary, fan
the smoke detector for a few minutes
to further dissipate any smoke or
particles. If the device still indicates a
problem, it may be necessary to clean
it. Please refer to Caring for Your
Smoke Detector below.
The unit has detected that the
temperature is above 135
o
been contacted. Press the recessed
test switch to silence the smoke
detector sounder for 5 minutes. If
necessary, silence the alarm keypad.
Remove the source of the heat, if it
can be done safely.
The unit has detected that the
o
temperature is below 41
F, which
could lead to a freeze situation within
the premises. Investigate the cause
and resolve.
F. ADT has
Page 1 of 8