Setting the brightness (LUX)
You can set different brightness values with the brightness potentiometer (factory setting 500 lx).
Set potentiometer to desired switch-on brightness (5 to 1000 lux/on).
On the on setting the detector always responds to movement, regardless of the brightness.
Turn the potentiometer to Teach-in
as the new switch-on brightness.
Setting the time delay (TIME)
If the detector detects no further movement, it switches off after the set time delay. If you want to change the preset time
(factory setting 10 min)
Set the potentiometer to the desired time (10 s, 1 min, 5 min, 10 min, 30 min).
If you wish to use the pulse function (e.g. for a staircase light timer switch)
Set the potentiometer to
Test detection area (walking test)
The walking test is used to test the detection area and to restrict it if necessary.
Set the time potentiometer (TIME) to test
▻ The detector always responds to movements (regardless of brightness and configuration type).
▻ After the detector has detected a movement, the contact switches on for 2 s.
Performing the walking test using the button (only for slave devices)
Press the button for 10 s
▻ If motion is detected the red LED on the slave lights up.
▻ Test mode is activated for 10 min.
Briefly press the button
▻ The test mode is ended and the detector returns to normal operation.
Recommended guide values
; after 20 s (red LED flashes) the detector saves the current surrounding brightness
. As long as motion is detected, the contact closes every 10 s for 0.5 s.